How to measure

Use a volt meter (set to proper scale) to 
measure the voltage at the pump termi-
nal box or starter.
On single-phase units, measure between 
power leads L1 and L2 (or L1 and N for 115 
volt units).  On three-phase units, meas-
ure between:
•   Power leads L1 and L2
•   Power leads L2 and L3
•   Power leads L3 and L1

What it means

When  the  motor  is  under  load,  the 
voltage  should  be  within  ±  10%  of  the 
nameplate  voltage.  Larger  voltage  vari-
ation may cause winding damage.
Large  variations  in  the  voltage  indicate 
a  poor  electrical  supply  and  the  pump 
should not be operated until these vari-
ations have been corrected.
If the voltage constantly remains high or 
low, the motor should be changed to the 
correct supply voltage.

Supply voltage

How to measure

Use  an  ammeter  (set  on  the  proper 
scale)  to  measure  the  current  on  each 
power  lead  at  the  terminal  box  or 
starter.  See  the  motor  nameplate  for 
amp draw information.
Current  should  be  measured  when  the 
pump is operating at constant discharge 
pressure.

What it means

If the amp draw exceeds the listed serv-
ice  factor  amps  (SFA)  or  if  the  current 
imbalance  is  greater  than  5%  between 
each leg on three-phase units, check the 
following:

1.  Burned contacts on the motor starter.
2. Loose terminals in starter or terminal  
     box or possible wire defect.
3. Too high or too low supply voltage.
4. Motor windings are shorted or  

 

     grounded. Check winding and insula- 
     tion resistances.
5. Pump  is  damaged  causing  a  motor
     overload.

Current measurement

How to measure

Turn  off  power  and  disconnect  the 
supply  power  leads  in  the  pump 
terminal  box.    Using  an  ohm  or  mega 
ohm  meter,  set  the  scale  selector  to
R x 100K and zero adjust the meter.
Measure  and  record  the  resistance 
between  each  of  the  terminals  and 
ground.

What it means

Motors  of  all  HP,  voltage,  phase  and 
cycle  duties  have  the  same  value  of 
insulation resistance.  Resistance values 
for new motors must exceed 1,000,000 
ohms.  If they do not, the motor should 
be repaired or replaced.

Insulation resistance

Troubleshooting

WHEN WORKING WITH ELECTRICAL CIRCUITS, USE CAUTION 
TO AVOID ELECTRICAL SHOCK. 

 It is  recommended that rub-

ber  gloves  and  boots  be  worn,  and  metal  terminal  boxes 
and motors be properly grounded before any work is done.

WARNING:  Failure  to  ground  the  pump  may  result  in
serious electrical shock.

Preliminary tests

Summary of Contents for HS 100 0505

Page 1: ...GRUNDFOS INSTRUCTIONS HS Horizontal single stage end suction pumps Installation and operating instructions discard fm Page 1 Tuesday June 7 2011 9 24 PM...

Page 2: ...Do not destroy packing materials until the shipment is inspected and the claim is settled The position of the coupling that connects the pump shaft to the motor shaft is set at factory specifications...

Page 3: ...kets to form Discharge piping It is suggested that a check valve and isolation valve be installed in the discharge pipe Pipe valves and fittings should be at least the same diameter as the discharge p...

Page 4: ...e motors should remain mounted with the cooling vents positioned downward especially where there is the possibility that liquid might splash onto the pump from above i e rain FIGURE 3 Motor mounting p...

Page 5: ...t be purged while the system is being filled Replace the drain vent plug and securely tighten Connect and or seal the discharge piping Check motor rotation 1 Make sure power is off 2 Check to make sur...

Page 6: ...Over greasing will cause increased bearing heat and can result in bearing motor failure Do not mix petroleum grease and silicon grease in motor bear ings Bearing grease will lose its lubricating abil...

Page 7: ...y torque 15 to 20 ft lbs 4 Using the appropriate edge of impeller spacing tool SV00201 see Table C position the impeller at the cor rect axial location and tighten allen shaft set screw s into the mot...

Page 8: ...AND SPARE PARTS PRICE LISTS FOR A COMPLETE LISTING OF KIT COMPONENTS Part Lists and Diagrams Model B HS 100 0505 to HS 125 1515 HS100 0305 to HS125 1520 Motor Stool 56C Frame Pump Base 3 4 Type 21 Joh...

Page 9: ...0 2020 to HS 150 3030 Motor Stool 182TC 184TC 1 Type 21 John Crane Seal Stub Shaft 416ss Impeller HS 150 5050 Impeller HS 150 7575 Pump Volute Volute Gasket 5 16 18 x 3 8 Shaft Set Screw Woodruff Key...

Page 10: ...it means If the amp draw exceeds the listed serv ice factor amps SFA or if the current imbalance is greater than 5 between each leg on three phase units check the following 1 Burned contacts on the mo...

Page 11: ...start pump gradually close the dis charge valve and read pressure at shut off Disassemble and inspect pump passageways Fault A Pump does not run B Pump runs but at reduced capacity or does not deliver...

Page 12: ...ecord values Check proper wiring and loose terminals Turn off power and manually rotate pump shaft Turn off the power and discharge the capacitor Check with ohm meter R x 100K Use a thermometer to che...

Page 13: ...erating instructions To obtain service under this warranty the defective product must be returned to the distributor or dealer of GRUNDFOS products from which it was purchased together with proof of p...

Page 14: ...English US 14 chapter discard fm Page 14 Tuesday June 7 2011 9 29 PM This page intentionally left blank...

Page 15: ...Kansas 66061 Phone 1 913 227 3400 Telefax 1 913 227 3500 Canada GRUNDFOS Canada Inc 2941 Brighton Road Oakville Ontario L6H 6C9 Phone 1 905 829 9533 Telefax 1 905 829 9512 M xico Bombas GRUNDFOS de M...

Page 16: ...the essence The name Grundfos the Grundfos logo and the payoff Be Think Innovate are registrated trademarks owned by Grundfos Management A S or Grundfos A S Denmark All rights reserved worldwide L EP...

Reviews: