English (GB)  

Caution  

Caution  

Open the isolating valve on the discharge manifold. 2. 
Close the isolating valve on the discharge manifold. 
3. Turn the main switch to  “I” 

position.  

4. Open the ball valve for testing the pressure switches for the  

main pump and the jockey pump.  

10.2 Electrical connection 

Warning 
During electrical installation, make sure that the  

power supply cannot be accidentally switched  on.  

Check that the supply voltage and frequency correspond to the  
values stated on the nameplate. 

The electrical connection must be made in accordance with the  

wiring diagram in the control cabinet. 

Procedure 

• The connection to the mains supply must be fitted with a fuse  of 

the correct size, in accordance with local regulations, and  con-

nected to the main switch in the control cabinet. PE must  be 

connected using the PE terminal block. 

• Pressure switch 1 for the main pump must be connected to  termi-

nals 6 and 7 in the control cabinet, and pressure switch 2  for the 

main pump to terminals 8 and 9. 

• The pressure switch for the jockey pump must be connected to  

terminals 2 and 52 in the control cabinet. 

• The pressure switch for dry running protection of the jockey  pump 

must be connected to terminals 53 and 54 in the control  cabinet. 

If this pressure switch should not be used, put a  cable/bridge 

between terminal 53 and 54 

• The additional pressure switch for the “Pump running”  indication is 

to be connected to terminals 12 and 13. If no  additional pressure 

switch is used, put a cable/bridge between  terminal 12 and 13. 

• If there is a level switch for measuring the filling level in the  

priming tank, it must be connected to terminals 10 and 11. 

• If status and alarm indications are to be transmitted to a  building 

management system, terminals 31 to 40 must be used  for this 

purpose.   

14  

11. Commissioning 

Warning  

Start-up must be carried out by authorised  

personnel. The control cabinet of the controller  

must remain closed during start-up. Danger of  

death through electric shock!.  

The sprinkler pump is not allowed to run against  a 

closed valve as this may cause an  unacceptable 

temperature increase or the  formation of steam. 

This may cause damage to  the sprinkler pump.  

11.1 Preparations before start-up 

Before start-up the following have to be done: 
1. Check that all screw connections are fitted securely. 
2. Check that all pipes are installed correctly. 
3. Check that all electrical connections inside and outside the  

controller are correctly connected and fitted securely. 4. Check 

that all fuses in the control cabinet are switched on. 
5. Check that all safety devices are installed. 
6. Make sure that any storage tank and pump priming tank are  

filled with enough water. 

7. Set pressure values on the three pressure switches, see  pres-

sure switch operating manual. The value of the pressure  

switches for the main pump should be 0.5 bar higher than the  

value of the pressure switch for the jockey pump. 

11.2 Start-up  

Before switching on the extinguishing water  

booster set it must be filled with water. In case 

of dry running the main pump will not  stop.  

Step 

Illustration  

1. Open the isolating valve on the suction manifold. Open the 

isolating valve on the suction side of the main  pump. 

Open both isolating valves of the bypass line.  

English 

(G

B)

14

10.2 Electrical connection

Check that the supply voltage and frequency correspond to the 

values stated on the nameplate.
The electrical connection must be made in accordance with the 

wiring diagram in the control cabinet.
Procedure
• The connection to the mains supply must be fitted with a fuse 

of the correct size, in accordance with local regulations, and 

connected to the main switch in the control cabinet. PE must 

be connected using the PE terminal block.

• Pressure switch 1 for the main pump must be connected to 

terminals 6 and 7 in the control cabinet, and pressure switch 2 

for the main pump to terminals 8 and 9.

• The pressure switch for the jockey pump must be connected to 

terminals 2 and 52 in the control cabinet.

• The pressure switch for dry running protection of the jockey 

pump must be connected to terminals 53 and 54 in the control 

cabinet. If this pressure switch should not be used, put a 

cable/bridge between terminal 53 and 54

• The additional pressure switch for the "Pump running" 

indication is to be connected to terminals 12 and 13. If no 

additional pressure switch is used, put a cable/bridge between 

terminal 12 and 13.

• If there is a level switch for measuring the filling level in the 

priming tank, it must be connected to terminals 10 and 11.

• If status and alarm indications are to be transmitted to a 

building management system, terminals 31 to 40 must be used 

for this purpose. 

11. Commissioning

11.1 Preparations before start-up

Before start-up the following have to be done:
1. Check that all screw connections are fitted securely.
2. Check that all pipes are installed correctly.
3. Check that all electrical connections inside and outside the 

controller are correctly connected and fitted securely.

4. Check that all fuses in the control cabinet are switched on.
5. Check that all safety devices are installed.
6. Make sure that any storage tank and pump priming tank are 

filled with enough water.

7. Set pressure values on the three pressure switches, see 

pressure switch operating manual. The value of the pressure 

switches for the main pump should be 0.5 bar higher than the 

value of the pressure switch for the jockey pump.

11.2 Start-up

Warning
During electrical installation, make sure that the 

power supply cannot be accidentally switched 

on.

Warning
Start-up must be carried out by authorised 

personnel. The control cabinet of the controller 

must remain closed during start-up. Danger of 

death through electric shock!.

Caution

The sprinkler pump is not allowed to run against 

a closed valve as this may cause an 

unacceptable temperature increase or the 

formation of steam. This may cause damage to 

the sprinkler pump.

Caution

Before switching on the extinguishing water 

booster set it must be filled with water.
In case of dry running the main pump will not 

stop.

Step

Illustration

1. Open the isolating valve on the suction manifold.

Open the isolating valve on the suction side of the main 

pump.

Open both isolating valves of the bypass line.

Open the isolating valve on the discharge manifold.

2. Close the isolating valve on the discharge manifold.
3. Turn the main switch to 

"I" position.

4. Open the ball valve for testing the pressure switches for the 

main pump and the jockey pump.

Summary of Contents for Fire RS

Page 1: ...Fire CONTROLLER Installation and operating instructions GRUNDFOS INSTRUCTIONS SS EN12845 SS 883001 INSTA 900...

Page 2: ...Person authorised to compile technical file and empowered to sign the EC declaration of conformity Declaration of conformity 2 Declaration of conformity GB EC declaration of conformity We Grundfos de...

Page 3: ...tomatic water supply and pressure boosting of fire protection appliances in small residential buildings The extinguishing water booster set is designed for the direct connection to the water supply ne...

Page 4: ...English GB 4...

Page 5: ...meter S1 Selector switch TEST 0 AUT main pump SA1 Selector switch MAN 0 AUT jockey pump Q1 Main switch English GB 5 4 3 Controller 4 3 1 General description The Fire RS extinguishing water booster set...

Page 6: ...tor current TR Transformer 400 24 V for control voltage TR1 Transformer 400 230 V for control voltage English GB 6 4 3 4 Inputs and outputs Inputs The controller has six digital inputs See table below...

Page 7: ...7 Rated voltage 8 Nominal frequency 9 Max current 10 Rated short circuit current 11 Protection class English GB 7 Manual operation of the jockey pump During start up and for test purposes the jockey p...

Page 8: ...ining additives 7 2 Maximum operating pressure The maximum operating pressure of the extinguishing water booster set is limited to 12 bar by a safety valve However some of the CR pumps are designed fo...

Page 9: ...g factors must be multiplied 0 89 x 0 89 0 79 9 1 0 37 0 55 2 0 75 22 3 30 E n g l is h G B 9 Relation between steam pressure scale and liquid temperature tm Fig 5 Steam pressure scale 7 4 Maximum per...

Page 10: ...or lights Fig 8 Control panel 8 1 Button functions Button Description 10 Indicator light test English GB 10 8 Control panel The control panel is divided into three areas operating buttons status indic...

Page 11: ...tus Text Potential free signal The jockey pump is running automatic or manual start On JOCKEY RUN 11 English GB 11 8 2 Status indications The operating status of the main pump and the controller is in...

Page 12: ...atus Text Potential free signalling The jockey pump does not start due to a fault On JOCKEY ALARM 12 English GB 12 8 3 Fault indications Faults of the main pump are indicated by means of the two indic...

Page 13: ...manifolds of the extinguishing wa ter booster set Use the end not closed by a screw cap or blanking flange Arrows on the pump base show the direction of flow of water through the pump Secure the pipes...

Page 14: ...he isolating valve on the suction side of the main pump Open both isolating valves of the bypass line English GB 14 10 2 Electrical connection Check that the supply voltage and frequency correspond to...

Page 15: ...rect direction of rotation is indicated by arrows on the fan cover of the motor Step Illustration 15 English GB 15 5 Turn the selector switch for the jockey pump to MAN position The jockey pump will s...

Page 16: ...ng the main switch to OFF position To restart the system the main switch must be set to I again English GB 16 12 Operation Status and alarm messages are indicated via indicator lights in the control p...

Page 17: ...valve on the discharge manifold After stopping the pump set returns to automatic mode 17 English GB 17 12 2 Manual operation Both pumps can also be started and stopped manually for a functional test a...

Page 18: ...ection 15 Fault finding 18 Stopping procedure After stopping the main pump is in automatic mode again English GB 18 12 2 2 Main pump Starting procedure Stopping procedure Step Illustration 1 Turn the...

Page 19: ...pump Step Illustration 6 Switch off the main pump again as described in section 12 2 2 Main pump 19 English GB 19 12 3 Test run In this section the testing of the function of the two pressure switches...

Page 20: ...e isolating valve on the discharge manifold 2 Close the isolating valve on the suction manifold English GB 20 13 Shut down If pumps are not used during periods of frost they must be drained to avoid d...

Page 21: ...essure switch for dry run protection or mount a bridge with a cable between the terminals 53 and 54 21 English GB 21 15 Fault finding Warning Only trained personnel are allowed to open the cabinet doo...

Page 22: ...rrectly Set the pressure switches correctly Close the ball valves for testing the pressure switches English GB 22 7 Jockey pump does not start in manual mode despite power supply a Selector switch for...

Page 23: ...ection service 2 If this is not possible contact the nearest Grundfos company or service workshop 23 English GB 23 16 Service accessories spare parts The installation and or use of such products may n...

Page 24: ...Appendix NPSH 24 TM02 7387 3403 TM01 9882 3801 TM01 9883 3300 TM01 9884 3801 TM02 7125 2703 TM02 7126 2703 TM02 7127 2703 TM01 1934 0899 TM01 1935 0899 Appendix 1...

Page 25: ...25 25...

Page 26: ...26 26...

Page 27: ...n 38a Oybek street Tashkent 998 71 150 3290 71 150 3291 998 71 150 3292 Addresses Revised 24 01 2014 Grundfos companies Argentina Bombas GRUNDFOS de Argentina S A Ruta Panamericana km 37 500 Centro In...

Page 28: ...os Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding A S XXXXXXX 98598034 1213 ECM XXXXXXX The name Grundfos the Grundfos logo and be think innovate are regi...

Reviews: