Instructions
EZ Boost
TM
System
8.5. Instruments not allowed
Note:
The use of the following instruments is not
allowed during fault finding:
Note:
When measuring, use RMS-instruments.
8.6. Checking of motor and cable
1. Supply voltage
Measure the voltage (RMS) between
line and neutral. Connect the voltmeter
to the terminals at the connection.
When the motor is loaded, the voltage
should be within the range specified in
section 5, Technical Data.
Large variations in supply voltage
indicate poor electricity supply, and
the BMQE should be stopped until the
defect has been remedied.
2. Current consumption
Measure the current (RMS) while the
pump is operating at a constant dis-
charge head (if possible, at the capac-
ity where the motor is most heavily
loaded).
For maximum current, see nameplate.
If the current exceeds the full load cur-
rent, there are the following possible
faults:
• Poor connection in leads, possibly
in the cable joint.
• Too low supply voltage, see item 1.
9. Factory settings
Alarm
200-240 V motors
100-115 V motors
SQ/SQE/SQE-NE 03A and
05A models
SQ/SQE/SQE-NE05B and
07B models
SQ/SQE/SQE-NE1.0C and
1.5C models
All models
Sensor defective
4-20 mA (the value is stored in the EZ Boost controller)
Overload
5.2 A
8.4 A
12.0 A
12.0 A
Over temperature
Stop limit:
163°F (73°C)
Stop limit:
162°F (72°C)
Stop limit:
203°F (95°C)
Stop limit:
185°F (85°C)
Restart:
145°F (63°C)
Restart:
144°F (62°C)
Restart:
185°F (85°C)
Restart:
167°F (75°C)
Speed reduction
In connection with under voltage or overload
Over voltage *)
315 VAC
315 VAC
315 VAC
180 VAC
Under voltage
Speed reduction: 198 V
Stop limit: 150 V
Speed reduction: 198 V
Stop limit: 150 V
Speed reduction: 198 V
Stop limit: 150 V
Speed reduction: 90 V
Stop limit: 75 V
Dry-running
300 W
680 W
800 W
300 W
*) 200-240 V motors: Operation is guaranteed up to 280 VAC, 100-115 V motors: Operation is guaranteed up to 150 VAC. In order to avoid
unnecessary stops, the over voltage stop limit is as stated.
19