8.4. EZ Boost controller fault finding chart (continued)

Fault

Possible Cause

Remedy

10.  The EZ Boost controller indicates 
 

“Speed reduction” and “Overload”.

Speed reduction is activated so as to maintain a reduced performance

a)  The pump is worn or blocked.
b)  The pump is too large for the installed 
 

motor.

•  The pump must be serviced.
•  Replace pump or motor.

11.  The EZ Boost controller indicates 
 

“Over temperature”.

The temperature sensor in the motor is sensing a temperature above the values stated in 
Section 9, Factory settings:

a) Insufficient cooling of the motor.

•  Restore correct cooling of the motor. 
 

The flow velocity past the motor should 

 

be at least 0.5 ft/s (0.15 m/s).

12.  The EZ Boost controller indicates 
 

“Overload”.

a)  The pump is worn or blocked.
b)  The pump is too large for the installed 
 

motor.

•  The pump must be serviced.
•  Replace pump or motor.

13.  The EZ Boost controller indicates 
 

“Sensor defective”.

a)  The pressure sensor is defective.

•  Check that the sensor is wired correctly. 
 

If the sensor type is 4-20 mA, measure 

 

the DC voltage across the sensor input 

 

terminals. If the DC voltage measured 

 

at the sensor input terminals is not 

 

between 2 and 10 volts the sensor, 

 

or wiring is defective. Refer to Section 

 

10, Pressure Sensor Voltage Chart. 

 

Replace defective parts. Are the LED 

 

“Sensor defective” and the LED, pos. 1, 

 

on? See section 7.3.3., Position of LED’s.

 

Yes:

 The total load of 24 VDC from 

 

terminal 5 is above 100 mA. Disconnect 

 

the sensor in order to determine if it is 

 

defective. Replace defective sensor.

 

No:

 The load is OK, but the EZ Boost 

 

controller sensor input may be 

 

defective.

14.  The pump is operating on/off.

a)  No communication.

•  Check that the LED “No contact to 
 

pump” is on.

 

If so, the control unit EZ Boost controller 

 

starts and stops the pump, based on the 

 

sensor signal only. The EZ Boost 

 

controller has to be reset after each 250 

 

stop.- see fault no. 5 for remedy

18

Summary of Contents for EZ Boost

Page 1: ...GRUNDFOS INSTRUCTIONS EZ BoostTM System USA Installation and operating instructions Please leave these instructions with the pump for future reference...

Page 2: ...a Operating Conditions 6 Storage 6 Frost Protection 6 6 Installation Electrical Connection 6 Cable Sizing 7 Positioning 7 Controller Connection 7 Pressure Sensor 8 Pressure Tank 8 Pressure Relief Valv...

Page 3: ...e controller adjusts the pump performance accordingly to maintain constant pressure by changing the pump speed At low flow the pressure will drop slowly When the pres sure in the tank is 7 PSI below t...

Page 4: ...V or rises above 280 V With a rated voltage of 110 115 V 60 Hz the pump will be cut out if voltage falls below 75 V or rises above 150 V The motor is automatically cut in when the voltage is again wi...

Page 5: ...am The EZ Boost Constant Pressure System should consist of Pos 1 EZ Boost BMQE pump 2 EZ Boost controller 3 Diaphragm tank recommended size 2 U S gallons 8 liter 130 psi 2 3 4 1 5 6 6 Additional boost...

Page 6: ...and when installed in the vertical position the air vent must be at the top of the unit Insert BMQE pump into the open mounting bracket Secure mounting brackets Apply pressure to the BMQE pump until t...

Page 7: ...Consult Troubleshooting Section 11 Verify that EZ Boost controller is operating 11 Verify EZ Boost controller is operating These lights are on These lights are on 12 Optional Lock the buttons 12 Opti...

Page 8: ...f button on the EZ Boost con troller must not be used as a safety switch when installing and servicing the pump Rain tight or wet location hubs that comply with the requirements in the standard for Fi...

Page 9: ...System 6 1 2 Cable sizing Single phase 60 HZ maximum cable length motor service to entrance Motor rating Copper wire size AWG Volts HP 14 12 10 Maximum cable length ft m 115 0 50 100 30 5 160 48 8 250...

Page 10: ...signed to work with a 2 gal diaphragm tank Install a diaphragm tank to insure that the BMQE will shut off at zero flow The diaphragm tank must be installed at some point between the BMQE pump and the...

Page 11: ...um flow for BMQE pumps in parallel will exceed 35 GPM a 4 gallon or two 2 gallon dia phragm tank s should be used 6 9 Generator Operation Power may be supplied to BMQE pumps by an adequately sized gen...

Page 12: ...on the EZ Boost controller face the pipe shows run lights when the pump is operat ing When the pump is not operating none of the flow indicator lights are on see fig 7 Fig 7 7 2 3 Pressure setting Th...

Page 13: ...d pressure drops causing the motor to increase speed If the power consumption falls below the dry run setting for an accumulated time of 5 seconds and the motor speed is within 1000 rpm of the max spe...

Page 14: ...eed Sensor defective Overload Over temperature Speed reduction Voltage alarm No contact to pump see Fig 14 Flashing green light when the pump control is working correctly Permanent yellow light when t...

Page 15: ...2 Parts list for SQE with instructions for dismantling and assembly of pump and motor 8 2 EZ Boost Controller Service Before starting any work on the EZ Boost con troller make sure that the electricit...

Page 16: ...and repair replace the pump e Leakage in the pipe work Check and repair the pipe work f Under voltage has occurred Check the electricity supply 4 Frequent starts and stops a The supply voltage is unst...

Page 17: ...sure sensor If the pump has not started yet proceed as follows Press the on off button for 5 seconds If the pump starts the EZ Boost controller or the sensor may be defective Note The pressure is not...

Page 18: ...motor communication part is defective Reduce the length of the pump cable Switch off the main power supply to the EZ Boost controller Switch on the main power supply again The pump is now connected d...

Page 19: ...ording to the values in Section 5 Note As the voltage is detected at the motor allow for the voltage drop in the pump cable 8 The EZ Boost controller indicates Dry running If the power consumption is...

Page 20: ...ed Replace pump or motor 13 The EZ Boost controller indicates Sensor defective a The pressure sensor is defective Check that the sensor is wired correctly If the sensor type is 4 20 mA measure the DC...

Page 21: ...faults Poor connection in leads possibly in the cable joint Too low supply voltage see item 1 9 Factory settings Alarm 200 240 V motors 100 115 V motors SQ SQE SQE NE 03A and 05A models SQ SQE SQE NE...

Page 22: ...4 54 7 8 0 95 2 2 9 15 0 5 5 55 5 8 1 96 0 2 9 15 7 5 5 56 2 8 1 96 7 3 0 16 5 5 6 57 0 8 2 97 5 3 0 17 2 5 6 57 7 8 2 98 2 3 1 18 0 5 7 58 5 8 3 99 0 3 1 18 7 5 7 59 2 8 3 99 7 3 2 19 5 5 8 60 0 8 4...

Page 23: ...ce under this warranty the defective product must be returned to the distributor or dealer of GRUNDFOS products from which it was purchased together with proof of purchase and installation date failur...

Page 24: ...Road Oakville Ontario L6H 6C9 Telephone 905 829 9533 Fax 905 829 9512 Bombas Grundfos de Mexico S A de C V Boulevard TLC 15 Parque Stiva Aeropuerto Apodaca N L 66600 Mexico Telephone 52 81 8144 4000 F...

Reviews: