ID
Object name
R/W
Description
BV,3
Config Primary DeltaT
Limiting ED
R/W
0: Disabled (default)
1: Enabled.
Enabling of primary differential temperature limiter. When enabled, the
differential temperature on the primary side is limited below the configuration
in AV,13 (Config Primary Delta T Limit [°C]).
AV,10
Config Supply Flow Limit
[m
3
/h]
R/W
Primary flow limit for hydronic balancing. The primary flow limit is enabled
BV,0 (Config Supply Flow Limiting ED).
AV,11
Config Thermal Power Limit
[kW]
R/W
Thermal power limit for the hydronic balancing. The thermal power limit is
enabled by BV,1 (Config Thermal Power Limiting ED).
AV,12
Config Return Temp Limit [°C] R/W
Return temperature limit for hydronic balancing. The return temperature limit
is enabled by BV,2 (Config Return Temp Limiting ED).
For heating applications the value works as an upper threshold.
For cooling applications the value works as a lower threshold.
AV,13
Config Primary DeltaT Limit
[°C]
R/W
Differential temperature limit for hydronic balancing. The differential
temperature limit is enabled by BV,3 (Config Primary Delta T Limiting ED).
The value is positive for both heating and cooling applications.
10.4.3 Energy monitoring
ID
Object name
R/W
Description
AI,7
Data Heating Energy [kWh]
R
Accumulated heating energy in total lifetime. Reset via BO,6 (Reset
Accumulated Counters).
AI,8
Data Heating Power [kW]
R
Current thermal power for product running in heating mode.
AI,9
Data Cooling Energy [kWh]
R
Accumulated cooling energy in total lifetime. Reset by BO, 6 (Reset
Accumulated Counters).
AI,10
Data Cooling Power [kW]
R
Current thermal power for product running in cooling mode.
AI,11
Data Heat Temp Difference
[°C]
R
Numerical value of forward pipe and return pipe differential temp. Used for
heat transfer calculation.
AI,12
Data Pump Power [W]
R
Current electrical power consumption of pump.
AI,13
Data Percentage Speed [%]
R
Percentage of maximum pump speed.
AI,14
Data Pump Operating Hours
[h]
R
Counter for pump operating hours. Reset by BO,6 (Reset Accumulated
Counters).
AI,15
Data Pump Energy [kWh]
R
Accumulated pump energy. Reset by BO,6 (Reset Accumulated Counters).
BO,6
Reset Accumulated Counters W
This resets the following counters:
•
Data Heating Energy
•
Data Cooling Energy
•
Data Pump Energy
•
Data Pump Operating Hours.
The reset function is rising edge triggered.
10.4.4 Integrated sensors and signals
ID
Object name
R/W
Description
AI,16
Data Flow Temp [°C]
R
Flow temperature measured in the secondary side via the connected pump.
AI,17
Data Supply Temp [°C]
R
Supply temperature measured at the valve.
AI,19
Data Logical Valve Opening
[%]
R
Valve opening request, linear from algorithm.
AI,20
Data Valve Supply Flow
[m
3
/h]
R
Flow rate at primary side measured at the A-port.
AI,21
Data Return Temperature [°C] R
Return temperature measured at the valve.
AI,22
Data Controlled Temp [°C]
R
Actual controlled temperature: zone air, flow temperature or feedback signal
at AI,28 (Data Bus Temperature Feedback).
AI,23
Data Boiler Setpoint [°C]
R
Boiler temperature reference derived from setpoint and mode of mixing loop.
AI,24
Data Pump Flow [m
3
/h]
R
Actual pump flow.
AI,25
Data Pump Head [m]
R
Actual pump head.
30