ID
Object name R/W
Description
AV,6
Config
Default Temp
Setpoint [°C]
R/W
Default: 40 °C.
Fall back temperature setpoint in
case setpoint signal from bus or
sensor is lost.
BI,13
Heat Curve
Slope Factor
Enabled
R
0: False
1: True
Indicates whether base curve is
linear or non-linear.
BI,14
Heat Curve
Offset Range
Exceeded
R
0: Exceeded
1: Not exceeded
Used for indicating that heat curve
offset value is out of range [-15 ;
15].
BI,15
Heat Curve
Slope Factor
Range
Exceeded
R
0: Exceeded
1: Not exceeded
Indicating that heat curve slope
factor value is out of range [0.4 ;
2.0].
7.7 Eco schedule
In some applications it can be useful to predefine a start and stop
schedule and apply an automatic temperature setback function in
order to minimise consumption, and thereby energy costs.
With the Eco schedule you can configure start and stop intervals on
a weekly basis as well as set single events.
This function can only be set via Grundfos GO Remote.
7.7.1 Scheduling Eco periods
Grundfos GO Remote menu:
Main menu
>
Settings
>
Eco functions
>
Eco schedule
To customise the system's start and stop intervals, do the following:
1.
Activate the scheduling function by pressing the grey slide-
button in the top right corner of the screen.
2.
Select the weekday for which you want to schedule the pump
performance.
3.
Insert a time period by pressing the light grey perimeter of the
clock.
4.
Customise the time period by dragging the bar clockwise or
counterclockwise on the light grey perimeter.
5.
You can assign more weekdays to the same schedule by
pressing the weekdays at the bottom of the screen. Days are
chosen when they are shown as green.
You can insert up to four time periods per day.
Delete a time period by holding and dragging it to the wastebin
in the top left corner.
6.
Press
Save
to complete the setup.
Specify whether MIXIT must run according to a temperature
setback or shut down in the defined Eco period(s).
7.7.2 Setting temperature setback and system turn off
Grundfos GO Remote menu:
Main menu
>
Settings
>
Eco functions
>
Eco schedule
A temperature setback can be defined for the period in which MIXIT
runs according to
Eco schedule
. In this period, MIXIT sets the
normal operating temperature back with the number of degrees set
in Grundfos GO Remote. Temperature setback is only available for
heating applications. MIXIT can also be set to turn off during the
Eco period
.
Do as follows:
1.
Make sure that
Eco schedule
has been activated and one or
more periods have been defined.
2.
When in the
Eco schedule
menu, press
Settings
at the
bottom of the screen.
3.
Select
Eco period
.
4.
Define a setback temperature or press
MIXIT off
to have MIXIT
turn off.
5.
Press the arrow back at the top of the screen to save and
return to the
Settings
menu.
7.7.3 Setting single events
Grundfos GO Remote menu:
Main menu
>
Settings
>
Eco functions
>
Eco schedule
1.
Activate
Eco schedule
.
2.
Press
Events
at the bottom of the screen and press
Add
event
. Up to 10 single events can be set.
3.
Define an action for the event. Choose if the system must act
according to a temperature setback or shut down.
4.
Define a date and time for the event. Press
Next
.
5.
According to your chosen action, define a temperature setback
or confirm that MIXIT turns off in the given period.
6.
Press
Next
to save the setting and return to the
Events
menu.
18