Euro-System Separator
GENO
DK 2-Mini
Order no. 085 133 944-inter Edited by: fger/mrie G:\BA-133944-INTER_085_SYSTEMTR-DK_2-MINI.DOCX
7
D
Installation and start-up
1 | General installation instructions
Please observe the local installation guidelines and the general regulations.
The installation site must be accessible for maintenance work, flood- and frost-
proof and ensure the system's protection from chemicals, dyes, solvents and
vapours.
Installation according to its nominal width in pipes of similar dimensions.
According to DIN EN 806-2, quick-closing shut-off fittings that might cause pos-
itive or negative water hammer may only be used for continuous actuation in
water installations if the max. admissible water hammer pressure and operat-
ing pressure are taken into account. Exceptions apply for fittings that are used
for test purposes only and are operated by experts.
Attention!
Dirt and corrosion particles might cause malfunctions or damage the
system separator. Prior to start-up, flush the feed pipe at maximum performance.
2 | Water installation
Binding rules
The installation of a system separator represents a major interference with the
drinking water system. Therefore, only authorised experts may install such systems.
Preliminary work
1. Unpack all system components.
2. Check for completeness and soundness.
Install as per the installation drawing (fig. D-1).
Make sure that built-in parts (e. g. EBRO flaps) installed upstream or downstream
of the device to not protude into the system separator and damage internal com-
ponents.
Make sure that the system separator's cap sieve is installed with its bulge direct-
ing opposite the flow direction (refer to fig. F-1).
Gate valve
Drinking water filter BOXER-KD
with pressure reducer
Gate valve with draining
○
4
Euro system separator GENO-DK 2-Mini
Waste water connection
Gate valve
Fig. D-1: Installation example: filter combination of fine filter BOXER-KD with Euro system separator GENO
DK 2
Summary of Contents for GENO DK 2-Mini
Page 2: ......