background image

 

Euro-System Separator 

GENO

 

DK 2-Mini

  

 

 

 

 

 

Order no. 085 133 944-inter   Edited by: fger/mrie G:\BA-133944-INTER_085_SYSTEMTR-DK_2-MINI.DOCX 

9

 

Troubleshooting  

 

 

Even carefully designed and manufactured technical systems that are operated 
properly, may experience malfunctions. The table below provides an overview of 
possible problems that may occur during the operation of system separators and 
indicates the causes and their elimination.

 

 

Attention! 

Short-term, undefined water leakage at the discharge valve of the sys-

tem separator does not represent a malfunction but is a normal control behaviour 
of the system separator caused by pressure fluctuations on the inlet side in the 
water supply system.

 

 

Note: 

In case of disturbances, e.g. permanent water leakage at the discharge 

valve, proceed as per the checklist below:   
Irrespective of the disturbance, you may identify the fault by systematically per-
forming the individual steps.

 

Test step 1 

 

Close shut- off 
valve on outlet  
side. 

 

Permanent 
discharge. 

 

Non-return valve  
on inlet side or dis-
charge valve leaky. 

 

Remove and  
check. 

 

Put system separator 
into operation again. 

 

No draining. 

 

Put system separator 

into operation again. 

 

 

Test step 2 

 
Close the shut

-

off 

valve on the inlet 
side and then open 
the sampling  
valve (pressure 
measuring point). 

 
Discharge valve  
does not open; dis-
charge is minimal  
and lasts for  
more than 1 minute.  

 
Discharge valve 
blocked 
 
Aeration and  
deaeration clogged 
 

 
Remove and  
check. 
 

 
Put system separator 
into operation again. 

 

Discharge valve 
opens abruptly.  
Devices empties  
in less than 1  
minute. 

Put system separator 
into operation again. 
 

 

 

Test step 3 

 
Open  
shut-off valve  
on outlet side. 

 
Permanent 
draining. 

 
Non-return valve 
on outlet side  
leaky. 

 
Remove and  
check.  
Put system separator 
into operation again. 

 
Remove and  
check.  
Put system separator 
into operation again. 

 

No 
draining. 

Put system separator 

into operation again. 

 

 

 

 

Note:

 In case of disturbances that you cannot remedy yourself, please contact 

your local Grünbeck service/Grünbeck's authorised service company (see 
www.gruenbeck.de). 

Summary of Contents for GENO DK 2-Mini

Page 1: ...Operation manual Euro system separator GENO DK 2 Mini Euro system separator GENO DK 2 mini Nominal diameter DN 15 Edition July 2017 Order no 085 133 944 inter...

Page 2: ......

Page 3: ...chments Warranty card Publisher s information All rights reserved Copyright by Gr nbeck Wasseraufbereitung GmbH Printed in Germany Effective with the date of edition indicated on the cover sheet We re...

Page 4: ...9 9074 41 120 Email service gruenbeck de We can connect you with the appropriate expert more quickly if you provide the required system data In order to have the required data handy at all times pleas...

Page 5: ...an installation directory of a water company as per 12 2 AVBWasserV German Ordinance on General Conditions for the Supply of Water 4 Shipping and storage Attention The systems and devices may be damag...

Page 6: ...cluding water originating from a drinking water installation that may exhibit modifications with regard to taste smell colour or temperature heating up or cooling down Examples Coffee heated drinking...

Page 7: ...hapter B classification of liquid categories Attention System separators are safety devices They protect the drinking water from modified drinking water They can only work reliably provided inspection...

Page 8: ...m 54 H Distance to wall mm 35 H Space required above centre of pipe connection e g for maintenance mm 200 L Clearance for the drain connection has to be provided in accordance with the planned running...

Page 9: ...xperts Attention Dirt and corrosion particles might cause malfunctions or damage the system separator Prior to start up flush the feed pipe at maximum performance 2 Water installation Binding rules Th...

Page 10: ...re that the discharge valve item 5 is closed 2 Completely deaerate the system separator by opening the bleeding screws item 3 3 Perform a visual check Make sure that no water leaks from the device any...

Page 11: ...steps Test step 1 Close shut off valve on outlet side Permanent discharge Non return valve on inlet side or dis charge valve leaky Remove and check Put system separator into operation again No drainin...

Page 12: ...service authorised service company Note A maintenance contract ensures that all the required maintenance work will be performed in due time 2 Inspection Check for tightness visual check If no water is...

Page 13: ...wearing parts Note Although these are wearing parts we grant a limited warranty period of 6 months Fig F 1 Spare parts for Euro system separator GENO DK 2 Mini Item Order no Designation PU Remarks 1...

Page 14: ...INTER_085_SYSTEMTR DK_2 MINI DOCX 12 Operation log Customer Name Address Euro system separator GENO DK please check appropriate box Serial number Installed by 1 1 1 2 DN 50 DN 65 DN 80 DN 100 DN 150...

Page 15: ...__________________________________________________________________ __________________________________________________________________ _________________________________________________________________...

Page 16: ...__________________________________________________________________ __________________________________________________________________ _________________________________________________________________...

Page 17: ...__________________________________________________________________ __________________________________________________________________ _________________________________________________________________...

Reviews: