Euro-System Separator
GENO
DK 2-Mini
Order no. 085 133 944-inter Edited by: fger/mrie G:\BA-133944-INTER_085_SYSTEMTR-DK_2-MINI.DOCX
8
Note:
Install strainer/fine filter directly upstream of the system separator, other-
wise malfunctions in the system separator may occur.
Attention!
Observe the flow direction.
Only install the system separator horizontally and without any loads and
stresses.
Provide a drain connection as per the technical specifications.
Make sure there is a free outlet and the water is discharged without back-pres-
sure.
3 | Start-up
1. Slowly open the shut-off valves (items 1 and 4) upstream and downstream of
the system separator. Afterwards, the system separator moves to its operat-
ing position. Make sure that the discharge valve (item 5) is closed.
2. Completely deaerate the system separator by opening the bleeding screws
(item 3).
3.
Perform a visual check. Make sure that no water leaks from the device any-
where.
Gate valve on inlet side
Euro system separator GENO-DK 2-Mini
Bleeding screw
Gate valve on outlet side
Draining of gate valve on inlet side
Fig. D-2: Detailed drawing of Euro system separator GENO-DK 2-Mini
4 | Functional check
After the successful start-up of the system separator, close the shut-off valve
(item 1). Pressure relief in the primary pressure zone is initiated by opening the
discharge valve (item 5).
Note:
Afterwards, the system separator must go into separating position and
thereby drain the middle pressure zone.
Afterwards, close the discharge valve (item 5) and slowly open the shut-off valve
(item 1). Then the system separator must move into the operating position again,
and must be completely tight.