5.5 SPH System electrical connection
Limit:
Max PV voltage: 550V (consider the lowest temperature)
Max PV input current: 13A
Remark:
1. Please do not connect to DC source!
2. For RSD function, the default brand of RSD supplier is Tigo, including AP system
and other brand RSD can be integrated. The more information please turns to
manufacturer.
Wire suggest length
5.5.1 Connection of PV terminal
Step 1 Turn off the PV switch.
Step 2 Remove the locking nut and waterproofing bolt.
Step 3 Secure the pipe fitting to the enclosure using the nut provided with the pipe.
Step 4 Route the PV input power cable through the conduit and then fitting of the pipe.
Step 5 Connect the PV input power cable to the terminal block. connect positive
pole(+) of connection cable to positive pole(+) of PV input terminal block, connect
negative pole(-) of connection cable to negative pole(-)of PV input terminal block,
please pay attention to PV input voltage and current within permission.
Step 6 Secure the fitting to the conduit.
Step 7 Checks that the cables are connected correctly and securely. Then take
appropriate measures to ensure that the pipe conduit and fittings are secured reliably,
and seal the cable holes.
5.5.2 Connection of AC terminal and off grid terminal
SPH has a grid output terminal and off grid out terminal, look down on the SPH from
the front, the terminal on the right (on grid) is grid outlet for connecting grid, the
terminal on the left is an uninterrupted power outlet for connecting critical load.
Conduct
or cross
section
Max cable length
SPH3000
SPH3600
SPH4000
SPH4600
SPH5000
SPH6000
5.2mm2
10AWG
40m
33m
28m
26m
25m
23m
6.6mm2
9AWG
50m
42m
36m
33m
32m
29m