background image

4

5

6

7

8

9

10

11

Each AXE 5.0L consists of 100Ah cells which form 51.2V voltage battery module and 
sixteen serial connection (1P16S). A single cluster can connect up to 10 batteries in 
parallel, and up to 8 clusters in parallel to expand the capacity and power of the energy 
storage system.

 

The same type of cell and the same software version of the PACK can be 

used in parallel. Specifically, the AXE battery system powers the loads through PCS at 
nighttime without solar; when solar becomes available during daytime, solar energy 
powers the loads as a priority and store residual solar power into the AXE batter system. 

1.2 Appearance

1

 

Product Overview

1.1 Intended Use

AXE 5.0L consists of battery module (including cell and mechanical parts), battery 

management system (BMS) as well as power and communication terminals. Product 

appearance is shown as below. 

Fig 1.1: Battery size diagram

1

2

1.3 Working Principle and Function

AXE 5.0L is an energy storage unit composed of electrochemical cells, switch button, 

battery management unit, power and signal terminals, and mechanical parts.

It features better charge and discharge performance, more precise status monitor, longer 

cycle life, and less self-discharge loss than other batteries. 

The scalability is very strong, a single cluster can connect up to 10 batteries in parallel, 

and up to 8 clusters in parallel to expand the capacity and power of the energy storage 

system.

The whole battery system communicates to Power Conversion System (PCS) via CAN. 

Ø

Monitoring: voltage, current and temperature detection of both single cells and PACK.

Ø

Protection and Alarm: protection and alarm when overvoltage, under voltage, over 

current, over-temperature or under temperature occurs. See Appendix I for details.

Ø

Report: report all alarm and status data to PCS.

Ø

Power off triggered by fault: PACK and PCS communication drop for 25 minutes or 

under voltage protection for 2 minutes.

650mm

1

4

0

m

m

350mm

1.2.1 Dimension

1.2.2 Introduction to the battery operation panel

1

2

3

5

Communication interface

Communication between battery 

packs of single cluster

6

USB interface

USB interface for system upgrade

7

Communication interface

Link-out for multi-cluster in parallel 
communication

8

Link-in for multi-cluster in parallel 

communication

9

PCS CAN communication

10

GND terminal

Terminal connect to ground

11

Negative terminal

Stands for PACK cathode output

b

3

3
3

c

3

d

3

e

3

3

f

a

Location

Port

Function

1

Fault light

Display battery alarm and fault status

2

SOC light

Display battery SOC status

3

Power button

Turn the battery on and off

4

Positive terminal

Stands for PACK anode output

No.

Name

Color

Description

A

RUN

Green

Normal operation

B

ALM

Red

Failure or protection status

C

LED 4

Blue

76%-100%

D

LED 3

Blue

51%-75%

E

LED 2

Blue

26%-50%

F

LED 1

Blue

0%-25%

Fig 1.2: Introduction to the battery operation panel

Fig 1.3: LED lights

Summary of Contents for AXE 5.0L-C1

Page 1: ...ndustrial Park Hangcheng Ave Guxing Community Xixiang Subdistrict Bao an District Shenzhen China 86 755 2747 1942 www ginverter com T E W service ginverter com Download Manual Growatt New Energy Resid...

Page 2: ...es the installation electrical connection operation commission maintenance and troubleshooting of AXE 5 0L C1and AXE 5 0L X1 Battery System hereafter simply put AXE 5 0L Before installing and operatin...

Page 3: ...to 8 clusters in parallel to expand the capacity and power of the energy storage system The whole battery system communicates to Power Conversion System PCS via CAN Monitoring voltage current and tem...

Page 4: ...ts such as wires Do not dispose the batteries in fire which may cause an explosion The PACK shall not come in contact with liquids The PACK can only be installed indoors Regarding indoor installation...

Page 5: ...er frapper planter un clou ou pi tiner le PACK Cela peut provoquer un d gagement de chaleur une explosion ou un incendie En cas de fuite d lectrolyte ne pas mettre l lectrolyte en contact avec les yeu...

Page 6: ...allation environment requirements Max 50 Min 0 Indoor installation 7 8 Avertissement 3 1 Storage Requirements Place the PACK follow the identification on the packing case during storage Do not put the...

Page 7: ...Shoes 4 4 Check Check the package Check the PACK package before open it If any abnormity is detected do not open the Package and contact your distributor Check the power Check and confirm the PACK is...

Page 8: ...n parall le 4 Please install indoors and ensure the level of the ground Veuillez installer l int rieur et assurer le niveau du sol Fig 4 5 Multiple AXE 5 0L with base installation process 4 5 2 Electr...

Page 9: ...y cluster 4 5 2 3 Multi cluster wiring CAN communication Power Power PE To PCS Cluster 1 Cluster 2 Cluster 3 Cluster 8 Fig 4 9 Block diagram of multi cluster system PCS Link in Link out PCS Link in Li...

Page 10: ...er off the PACK immediately After problem confirmed proceed again Si des anomalies surviennent pendant la phase de d marrage mettez imm diatement le PACK hors tension Une fois le probl me confirm reco...

Page 11: ...e Suggested actions ALM ALM Light Flickers Discharge under voltage protection Single cell voltage below the threshold for under voltage protection There is over discharge risk User should stop dischar...

Page 12: ...5 0L C1 X1 AXE 10 0L C1 X1 3 Nominal Capacity Energy 100Ah 5 0kWh 200Ah 10 0kWh 4 Rated Capacity Energy 90Ah 4 6kWh 180Ah 9 2kWh 5 Rated Voltage 51 2V 6 Operating Voltage 46 4 57 6V 7 Rated Charging...

Page 13: ...1P16S 3P M 0 50 90 IFpP 51 161 119 1P16S 4P M 0 50 90 26 Multiple clusters in parallel Max 8 Clusters No Items Specification 1 Parallel number of Battery systems 5 6 2 Battery Model AXE 25 0L C1 X1 A...

Page 14: ...P16S 7P M 0 50 90 IFpP 51 161 119 1P16S 8P M 0 50 90 26 Multiple clusters in parallel Max 8 Clusters No Items Specification 1 Parallel number of Battery systems 9 10 2 Battery Model AXE 45 0L C1 X1 AX...

Page 15: ...arge and over discharge alarm t 1S RUN ALM light flicker green Over charge and over discharge protection t 1S RUN ALM light flicker green Charging current limit does not respond t 1S RUN ALM light fli...

Page 16: ...er red External CAN communicat ion failure t 1S RUN ALM light flicker red Interior CAN communicat ion failure t 1S RUN ALM light flicker red Parallel connection failure t 1S RUN ALM light flicker red...

Reviews: