U0594061-C
Page 22 / 82
CORFIRST / CORSUN 2 / CORFLOW
EN
• Anode: The anodes should be inspected every year and replaced when three quarters of
the magnesium has been consumed. If there is not enough headroom beneath the ceiling,
anodes are available in a chain version (refer to the specific anode manual).
For insulated versions, inspect for wear without removing the anode. The values are given
as a guide, and were produced for water with a conductivity of 500 µs/cm.
Disconnect the anode from the tank, pulling out the lug on the anode. Measure the amperage
between the lug and the anode using a multimeter. If the amperage is less than 0.5 mA of
direct current on the first reading, replace the anode.
If the anode does not need to be
replaced, do not forget to reconnect it.
• If the tank is to remain without operating over the winter in premises where there is a risk
of freezing, the water must be kept above freezing point.
For all operations on components containing artificial siliceous mineral fibres (ceramic
fibres, glass wool, rock wool), the operator must wear suitable protective clothing and
a breathing mask to avoid any risk specific to these products.
9. TROUBLESHOOTING
•
Continuous flow of water from the safety unit:
Check the network pressure. If it is greater than 5 bar, fit a pressure reducer to the water
supply. If the pressure is correct (lower than 5 bar), clean the safety unit valve.
•
Low pressure at the hot water tap:
Significant scaling: drain the device, de-scale and check the safety valve.
•
If there is a continuous escape of steam or boiling water from the drain or when a water
tap is opened, cut the electrical power and the power to the primary heat exchanger circuit.
Inform the installer.
10. WARRANTY
The equipment must be installed by a qualified professional in accordance with best practice,
the standards, regulations and technical documents in force and the instructions in our
technical manuals.
It must be used in accordance with the instructions and regularly maintained by a specialist.
In no case will operations under the warranty confer eligibility for the payment of damages
or extend the warranty period.
In the event of a clearly established manufacturing fault or defective materials (which must
be proved by the purchaser) acknowledged by Groupe Atlantic, the manufacturer's liability
is limited to:
•
Removable boiler parts:
supplying a replacement for the part acknowledged to be faulty
including transport costs, but excluding the labour costs associated with removing and
replacing the part, for a period of two years from the date of commissioning or, failing this,
the invoice date, without exceeding a period six months longer than the time since the
manufacturing date.
Summary of Contents for CORFIRST