background image

Page  6

Only if 

Relay 

option Installed

Relay 

Dly 0min

Relay 

Test OFF

Use <UP> or <DOWN> to change the Relay Delay time within the limits. The 

delay time may be set from 0 to 9 minutes in 1 minute increments to prevent 

false alarms. The default is 0 minutes (no delay).

Use <UP> or <DOWN> to toggle the relay ON or OFF to test the relay 

operation. Press <MENU> to reset to OFF and advance.

14. RELAY DELAY

15. RELAY TEST

<MENU> 

Press to advance to next menu item

<MENU> 

Press to advance to next menu item

<MENU> 

Press to advance to next menu item

<MENU> 

Press to advance to next menu item

Calibrat

1000 ppm

Cal Ref

1000 ppm

This item is used to calibrate the CO

2

 sensor by applying 1000 ppm CO

2

 calibration 

gas directly to the sensor. Consult the calibration instructions for the detailed 

procedure.
After applying the gas for several minutes, hold either the <UP> or <DOWN> 

key for 5 seconds to start the gas calibration. The display will blink during the 

calibration time (approximately 10 seconds). 
The display will change to “Calibrat / Done” when the calibration is complete. The 

display may indicate “Calibrat / Fail” if the calibration fails.

The calibration reference screen allows user to set the calibration gas level used 

for calibrating the sensor.  Use <UP> and <DOWN> to adjust the ppm value of 

calibration gas.  The minimum value is 400ppm, the maximum value is 2000ppm.  

Increment value is 50ppm for each step.  Press <MENU> to save and advance. If no 

calibration gas is available exposing the sensor to fresh outside can be used and 

calibrate with 400PPM value.  Another method is to determine the CO2 ambient 

level using a calibrated unit as a reference and adjust calibration setting to desired 

value

<MENU> 

Press to advance to exit the Setup Menu and return to normal mode

17. CALIBRATE

16. CALIBRATE

CALIBRATION

Calibration with gas requires a field calibration kit with pressure regulator, tubing, sensor adapter and 

bottle of CO

2

 gas. The certified calibration gas is applied directly to the CO

2

 sensor to perform a gas 

calibration.

Ensure the regulator knob is turned off and then hand tighten the regulator to the CO

2

 gas bottle. A 

length of tubing should be connected between the regulator output and the sensor adapter hood.

Remove the cover of the device to be calibrated to expose the gas sensor. Carefully install the sensor 

adapter hood over the CO

2

 sensor on the PCB. The adapter should fit snuggly and securely over the 

sensor and remain in place during the entire calibration cycle. This will ensure a stabile  ppm CO

2

 

environment during calibration. Turn the regulator knob on to allow gas to flow to the sensor. The CO

2

 

reading on the LCD will begin to approach ppm level of calibration gas . Wait 3 to 5 minutes until the CO

2

 

reading stabilizes.

Enter the Setup Menu and use the <MENU> key to advance to the “Calibrat” item. Press and hold either 

the <UP> or <DOWN> key for 5 seconds to start the gas calibration. The LCD will indicate “Calibrat 

/ Done” if the process was successful. If “Calibrat / Fail” is displayed then the process may have to be 

repeated. Press the <MENU> key to return to normal operation, shut off the gas supply and remove the 

sensor adapter.

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

IN-GE-CD2DTXXX-03

Summary of Contents for CD2DT Series

Page 1: ... intended for life safety applications NOTE This CO2 sensor incorporates a Self Calibration feature to correct CO2 sensor drift This feature is recommended for applications where the CO2 will be exposed to fresh air 400 ppm at least one hour per day If the monitored space is occupied 24 hours or consistently maintains higher or lower levels of CO2 it is recommended that this feature be turned off ...

Page 2: ...ram See Figure 5 This is a 3 wire sourcing device Connect the plus DC or the AC voltage hot side to the PWR terminal and the common is connected to the COM terminal The device is reverse voltage protected and will not operate if connected backwards It has a half wave power supply so the supply common is the same as the signal common Several devices may be connected to one power supply and the outp...

Page 3: ...ired SETUP MENU The device has several parameters that can be configured locally via the Setup menu using the keypad and LCD Any changes made are saved in non volatile memory and are restored in case of a power loss The menu can be accessed at any time after the start up mode and if there is 5 minutes of inactivity the menu will close and normal operation will continue To enter the menu press and ...

Page 4: ...actual output signal will depend on the PCB switch position mA or VOLT and the V Output setting for voltage operation Press MENU to set it back to OFF and advance Factory default is OFF MENU Press to advance to next menu item MENU Press to advance to next menu item 6 OUTPUT TEST Temp Units C Display CO2 ppm CO2 1235 ppm Temp 24 3 C 1235 ppm 24 3 C CO2 1235 ppm Temp 24 3 C The Temp Units setting is...

Page 5: ...nge the setting within the limits as shown in the table Note that only the one previous selection will be available Note that a high alarm activates when the measurement exceeds the setpoint and a low alarm activates when the measurement goes below the setpoint Use MENU to save and advance or 12 RELAY SETPOINT RELAY ASSIGNMENT DEFAULT SETPOINT SETPOINT RANGE RESOLUTION Temp High 26 0 C 79 0 F 5 0 ...

Page 6: ...ue Another method is to determine the CO2 ambient level using a calibrated unit as a reference and adjust calibration setting to desired value MENU Press to advance to exit the Setup Menu and return to normal mode 17 CALIBRATE 16 CALIBRATE CALIBRATION Calibration with gas requires a field calibration kit with pressure regulator tubing sensor adapter and bottle of CO2 gas The certified calibration ...

Page 7: ...ve 24 Vdc Current 550Ω max Voltage 10 000Ω min Ambient Operating Range 0 to 50 C 32 to 122 F 0 to 95 RH non condensing Storage Conditions 40 to 70 C 40 to 158 F 0 to 95 RH non condensing LCD Display Units ppm CO2 C F for optional temperature setpoint Display Range 0 10 000 ppm 0 to 50 C 0 to 122 F Display Size 35mm W x 15mm H 1 4 x 0 6 Digit Height 2 line x 8 character OPTIONAL TEMPERATURE SENSOR ...