background image

Page  2

Drill or punch a 7/8” or 1” hole in the duct at the preferred location and 

insert the probe into the hole to mark the enclosure mounting holes. 

Remove the unit and drill the two mounting holes. 

Clean all drilled holes of debris before mounting the device. Mount 

the enclosure to the duct with two sheet metal screws such that the 

duct air flow is parallel with the vent holes in the probe (i.e.: air flows 

directly into the probe holes). To prevent air leaks, ensure the gasket is 

compressed around the probe between the device enclosure and the 

air duct. See Figure 1.

The enclosure has a hinged cover with a latch. Open the cover by pulling slightly on the latch on the 

bottom of the enclosure, at the same time pulling on the cover. See Figure 2. A 1/2" NPT threaded 

connection hole is provided in the side of the enclosure. Screw an EMT connector or cable gland 

connector in until tight. A weatherproof conduit or cable gland fitting is recommended. There is an 

optional 1/2" NPT to M16 thread adapter and cable gland fitting. See Figure 3.

Two security screws are provided which can be installed to help secure the cover once settings and wiring 

connections are complete. See Figure 4.

WIRING

Deactivate the power supply until all connections are made to the device to prevent electrical shock 

or equipment damage. Use 16-22 AWG shielded wire for all connections (only ground the shield at the 

controller end) and do not locate the device wires in the same conduit with wiring used to supply inductive 

loads such as motors. Pull at least six inches of wire into the enclosure and complete the wiring connection 

according to the wiring diagram. See Figure 5.

This is a 3-wire sourcing device. Connect the plus DC or the AC voltage hot side to the PWR terminal 

and the common is connected to the COM terminal. The device 

is reverse voltage protected and will not operate if connected 

backwards. It has a half-wave power supply so the supply 

common is the same as the signal common. Several devices 

may be connected to one power supply and the output signals 

all share the same common. Use caution when grounding the 

secondary of a transformer or when wiring multiple devices 

to ensure the ground point is the same on all devices and the 

controller. See Figure 6.

The CO

2

 analog output is available on the CO

2

 terminal. This 

signal is switch selectable for either 4-20 mA or voltage output 

(0-5 / 0-10 Vdc) and connects to the controller analog input. See 

Figure 7.

Check the controller Analog Input to determine the proper connection before applying power. Both 

current and voltage signals are referenced to the COM terminal. The current output operates in the active 

mode and does not require a loop power supply (the signal current is generated by the transmitter and 

must not be connected to a powered input or device damage will result).

Figure 5

Figure 7

Figure 8

Figure 9

Figure 6

Power Supply

Wiring for CO

2

 output signal and 

24 Vdc power from controller

Wiring for all output and external 24 Vac power 

transformer or external 24 Vac power supply

CO

2

COM

PWR

RELAY

TEMP

CO

2

COM

PWR

Analog Input

COMMON

+24 Vdc

COMMON

Digital Input

Analog Input

COMMON

Analog Input

COMMON

COMMON

24 Vac

Controller

Alarm

Controller

24 Vac Transformer / 

Power Supply

mA

VOLT

Current

4-20 mA

Voltage

0-5 or 0-10 Vdc

VOLT

mA

Figure 4

PWR

COM

CO

2

TEMP

UP

DOWN

MENU

RELAY

VOLT

mA

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

IN-GE-CD2DTXXX-03

Summary of Contents for CD2DT Series

Page 1: ... intended for life safety applications NOTE This CO2 sensor incorporates a Self Calibration feature to correct CO2 sensor drift This feature is recommended for applications where the CO2 will be exposed to fresh air 400 ppm at least one hour per day If the monitored space is occupied 24 hours or consistently maintains higher or lower levels of CO2 it is recommended that this feature be turned off ...

Page 2: ...ram See Figure 5 This is a 3 wire sourcing device Connect the plus DC or the AC voltage hot side to the PWR terminal and the common is connected to the COM terminal The device is reverse voltage protected and will not operate if connected backwards It has a half wave power supply so the supply common is the same as the signal common Several devices may be connected to one power supply and the outp...

Page 3: ...ired SETUP MENU The device has several parameters that can be configured locally via the Setup menu using the keypad and LCD Any changes made are saved in non volatile memory and are restored in case of a power loss The menu can be accessed at any time after the start up mode and if there is 5 minutes of inactivity the menu will close and normal operation will continue To enter the menu press and ...

Page 4: ...actual output signal will depend on the PCB switch position mA or VOLT and the V Output setting for voltage operation Press MENU to set it back to OFF and advance Factory default is OFF MENU Press to advance to next menu item MENU Press to advance to next menu item 6 OUTPUT TEST Temp Units C Display CO2 ppm CO2 1235 ppm Temp 24 3 C 1235 ppm 24 3 C CO2 1235 ppm Temp 24 3 C The Temp Units setting is...

Page 5: ...nge the setting within the limits as shown in the table Note that only the one previous selection will be available Note that a high alarm activates when the measurement exceeds the setpoint and a low alarm activates when the measurement goes below the setpoint Use MENU to save and advance or 12 RELAY SETPOINT RELAY ASSIGNMENT DEFAULT SETPOINT SETPOINT RANGE RESOLUTION Temp High 26 0 C 79 0 F 5 0 ...

Page 6: ...ue Another method is to determine the CO2 ambient level using a calibrated unit as a reference and adjust calibration setting to desired value MENU Press to advance to exit the Setup Menu and return to normal mode 17 CALIBRATE 16 CALIBRATE CALIBRATION Calibration with gas requires a field calibration kit with pressure regulator tubing sensor adapter and bottle of CO2 gas The certified calibration ...

Page 7: ...ve 24 Vdc Current 550Ω max Voltage 10 000Ω min Ambient Operating Range 0 to 50 C 32 to 122 F 0 to 95 RH non condensing Storage Conditions 40 to 70 C 40 to 158 F 0 to 95 RH non condensing LCD Display Units ppm CO2 C F for optional temperature setpoint Display Range 0 10 000 ppm 0 to 50 C 0 to 122 F Display Size 35mm W x 15mm H 1 4 x 0 6 Digit Height 2 line x 8 character OPTIONAL TEMPERATURE SENSOR ...

Reviews: