background image

Page  4

Altitude

0 m

The Altitude value allows CO

2

 compensation for local atmospheric pressure and 

altitude and ensures the highest CO

2

 accuracy. Altitude can be changed from 0 to 

2550 meters in 50 meter steps using <UP> or <DOWN>. It will take a few moments 

to change the setting, then the menu will advance to the next step. Factory default 

is 0 m (sea level).

<MENU> 

Press to advance to next menu item

3. ALTITUDE

V Output

0-5 Vdc

The V Output value controls the analog output voltage span if the PCB switch is set 

to VOLT. V Output can be set to either 0-5 Vdc or 0-10 Vdc using <UP> or <DOWN>. 

This setting has no effect if the PCB switch is set to mA. Factory default is 0-5 Vdc.

<MENU> 

Press to advance to next menu item

4. OUTPUT VOLTAGE SPAN

Output

Direct

The Output value controls the analog output signal direction. Use <UP> or 

<DOWN> to change the setting from Direct (4-20 mA, 0-5 Vdc or 0-10 Vdc) to 

Reverse (20-4 mA, 5-0 Vdc or 10-0 Vdc) if reverse action is required. Factory 

default is Direct.

<MENU> 

Press to advance to next menu item

5. OUTPUT SIGNAL DIRECTION

Output

Test OFF

The Output Test value controls the analog output signal for testing purposes. 

Use <UP> or <DOWN> to toggle the output signal to OFF (normal operation), 

MIN (minimum output) or MAX (maximum output). The actual output signal will 

depend on the PCB switch position (mA or VOLT) and the V Output setting (for 

voltage operation). Press <MENU> to set it back to OFF and advance. Factory 

default is OFF.

<MENU> 

Press to advance to next menu item

<MENU> 

Press to advance to next menu item

6. OUTPUT TEST

Temp

Units 

°

C

Display

CO2 ppm

CO2

1235 ppm

Temp

24.3 

°

C

1235 ppm

24.3 

°

C

CO2

1235 ppm

Temp

24.3 

°

C

The Temp Units setting is used to select °C or °F display of temperature. Use 

<UP> or <DOWN> to select. The selection will also control available setpoint 

ranges if the setpoint option is installed. Factory default is °C.

Display is used to control what information is displayed on the LCD. The 

selections depend on the installed options. Use <UP> or <DOWN> to select 

either CO

2

 ppm, Temp, CO

2

+Temp, Rotate or None. Factory default is CO

2

 ppm. 

For a basic CO

2

 only device, the selection is limited to CO

2

 ppm or None.

CO

2

 ppm 

Only the actual ppm value of 

 

the CO

2

 reading will be displayed

Temp 

Only temperature is displayed 

 

(°C or °F depends on units setting)

CO

2

 & Temp  CO

2

 ppm and temperature both 

 

displayed at the same time

Rotate 

All available sensor readings rotate 

 

at 2 second intervals

None 

No measurement information is displayed in  

 

normal mode, the menu will still display in  

 

Setup Menu mode

7. TEMPERATURE UNITS

8. DISPLAY

Only if 

Temperature Sensor

 option Installed

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

IN-GE-CD2DTXXX-03

Summary of Contents for CD2DT Series

Page 1: ... intended for life safety applications NOTE This CO2 sensor incorporates a Self Calibration feature to correct CO2 sensor drift This feature is recommended for applications where the CO2 will be exposed to fresh air 400 ppm at least one hour per day If the monitored space is occupied 24 hours or consistently maintains higher or lower levels of CO2 it is recommended that this feature be turned off ...

Page 2: ...ram See Figure 5 This is a 3 wire sourcing device Connect the plus DC or the AC voltage hot side to the PWR terminal and the common is connected to the COM terminal The device is reverse voltage protected and will not operate if connected backwards It has a half wave power supply so the supply common is the same as the signal common Several devices may be connected to one power supply and the outp...

Page 3: ...ired SETUP MENU The device has several parameters that can be configured locally via the Setup menu using the keypad and LCD Any changes made are saved in non volatile memory and are restored in case of a power loss The menu can be accessed at any time after the start up mode and if there is 5 minutes of inactivity the menu will close and normal operation will continue To enter the menu press and ...

Page 4: ...actual output signal will depend on the PCB switch position mA or VOLT and the V Output setting for voltage operation Press MENU to set it back to OFF and advance Factory default is OFF MENU Press to advance to next menu item MENU Press to advance to next menu item 6 OUTPUT TEST Temp Units C Display CO2 ppm CO2 1235 ppm Temp 24 3 C 1235 ppm 24 3 C CO2 1235 ppm Temp 24 3 C The Temp Units setting is...

Page 5: ...nge the setting within the limits as shown in the table Note that only the one previous selection will be available Note that a high alarm activates when the measurement exceeds the setpoint and a low alarm activates when the measurement goes below the setpoint Use MENU to save and advance or 12 RELAY SETPOINT RELAY ASSIGNMENT DEFAULT SETPOINT SETPOINT RANGE RESOLUTION Temp High 26 0 C 79 0 F 5 0 ...

Page 6: ...ue Another method is to determine the CO2 ambient level using a calibrated unit as a reference and adjust calibration setting to desired value MENU Press to advance to exit the Setup Menu and return to normal mode 17 CALIBRATE 16 CALIBRATE CALIBRATION Calibration with gas requires a field calibration kit with pressure regulator tubing sensor adapter and bottle of CO2 gas The certified calibration ...

Page 7: ...ve 24 Vdc Current 550Ω max Voltage 10 000Ω min Ambient Operating Range 0 to 50 C 32 to 122 F 0 to 95 RH non condensing Storage Conditions 40 to 70 C 40 to 158 F 0 to 95 RH non condensing LCD Display Units ppm CO2 C F for optional temperature setpoint Display Range 0 10 000 ppm 0 to 50 C 0 to 122 F Display Size 35mm W x 15mm H 1 4 x 0 6 Digit Height 2 line x 8 character OPTIONAL TEMPERATURE SENSOR ...

Reviews: