background image

Page  1

INTRODUCTION

The duct CO

2

 device uses a highly accurate and reliable non-dispersive 

infrared (NDIR) sensor in an attractive enclosure with a gasketed, hinged 

cover for duct applications to monitor CO

2

 levels. The sensor uses 

dual channel optics and LTA (long term adjustment) signal processing 

technology to deliver industry leading long term accuracy and reliability. 

These technology features ensure optimum measurement stability for 

both periodic and constant occupancy applications so the device is 

equally suitable for return-air measurement from the classroom or the 

hospital room.

Standard features include a field selectable output signal of either 4-20 mA, 0-5 Vdc or 0-10 Vdc for the 

highest versatility, programmable CO

2

 measurement span, a backlit alpha-numeric LCD and easy menu 

operation for configuration.

Optional features include a resistive temperature sensor output (with LCD display of temperature in 

either °C or °F), a control relay with programmable setpoint, hysteresis and time delay, and either a 

conduit or cable gland connection point.

BEFORE INSTALLATION

Read these instructions carefully before installing and commissioning the device. Failure to follow these 

instructions may result in product damage. Do not use in an explosive or hazardous environment, with 

combustible or flammable gases, as a safety or emergency stop device or in any other application where 

failure of the product could result in personal injury. Take electrostatic discharge precautions during 

installation. De-energize the power supply prior to installation, this device is intended for indoor air 

conditioned spaces, contact factory or other applications. 

Do not exceed device ratings. This product 

is not intended for life-safety applications.
NOTE:

 This CO

2

 sensor incorporates a Self Calibration feature to correct CO

2

 sensor drift. This feature is 

recommended for applications where the CO

2

 will be exposed to fresh air (400 ppm) at least one hour 

per day. If the monitored space is occupied 24 hours or consistently maintains higher or lower levels 

of CO

2

, it is recommended that this feature be turned off, but yearly calibration will be required. If the 

self calibration is disabled at installation time without allowing for 7 day auto calibration cycle, then a 

manual calibration should be performed to ensure accuracy of the device.

MOUNTING

The duct type sensor installs on the outside of a return air duct with the sampling tube inserted into the 

duct. Use the included foam plug to prevent air from entering the enclosure through the conduit and 

causing an incorrect reading.
Mount the sensor in an easily accessible location in a straight section 

of duct at least five feet from corners or other items that may cause 

disturbances in the air flow. Avoid areas where the detector is exposed 

to vibrations or rapid temperature changes. 
The duct CO

2

 detector principal of operation is based on the Venturi 

effect of the probe that extends into the HVAC duct. Air flowing through 

the duct is forced into the vent holes on one side of the probe, into 

the enclosure, over the CO

2

 sensor and then is drawn back out of the 

enclosure via the probe vent holes on the opposite side.

NOTE

: To ensure proper temperature readings, if present, the 

temperature inlet on the probe must be installed directly into the 

airflow. See Figure 1.

EMT Connector

Thread adapter and 

cable gland fitting

Figure 1

Airflow

Figure 3

Figure 2

IN-GE-CD2DTXXX-03

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Duct Carbon Dioxide Transmitter

CD2DT Series - Installation Instructions

Summary of Contents for CD2DT Series

Page 1: ... intended for life safety applications NOTE This CO2 sensor incorporates a Self Calibration feature to correct CO2 sensor drift This feature is recommended for applications where the CO2 will be exposed to fresh air 400 ppm at least one hour per day If the monitored space is occupied 24 hours or consistently maintains higher or lower levels of CO2 it is recommended that this feature be turned off ...

Page 2: ...ram See Figure 5 This is a 3 wire sourcing device Connect the plus DC or the AC voltage hot side to the PWR terminal and the common is connected to the COM terminal The device is reverse voltage protected and will not operate if connected backwards It has a half wave power supply so the supply common is the same as the signal common Several devices may be connected to one power supply and the outp...

Page 3: ...ired SETUP MENU The device has several parameters that can be configured locally via the Setup menu using the keypad and LCD Any changes made are saved in non volatile memory and are restored in case of a power loss The menu can be accessed at any time after the start up mode and if there is 5 minutes of inactivity the menu will close and normal operation will continue To enter the menu press and ...

Page 4: ...actual output signal will depend on the PCB switch position mA or VOLT and the V Output setting for voltage operation Press MENU to set it back to OFF and advance Factory default is OFF MENU Press to advance to next menu item MENU Press to advance to next menu item 6 OUTPUT TEST Temp Units C Display CO2 ppm CO2 1235 ppm Temp 24 3 C 1235 ppm 24 3 C CO2 1235 ppm Temp 24 3 C The Temp Units setting is...

Page 5: ...nge the setting within the limits as shown in the table Note that only the one previous selection will be available Note that a high alarm activates when the measurement exceeds the setpoint and a low alarm activates when the measurement goes below the setpoint Use MENU to save and advance or 12 RELAY SETPOINT RELAY ASSIGNMENT DEFAULT SETPOINT SETPOINT RANGE RESOLUTION Temp High 26 0 C 79 0 F 5 0 ...

Page 6: ...ue Another method is to determine the CO2 ambient level using a calibrated unit as a reference and adjust calibration setting to desired value MENU Press to advance to exit the Setup Menu and return to normal mode 17 CALIBRATE 16 CALIBRATE CALIBRATION Calibration with gas requires a field calibration kit with pressure regulator tubing sensor adapter and bottle of CO2 gas The certified calibration ...

Page 7: ...ve 24 Vdc Current 550Ω max Voltage 10 000Ω min Ambient Operating Range 0 to 50 C 32 to 122 F 0 to 95 RH non condensing Storage Conditions 40 to 70 C 40 to 158 F 0 to 95 RH non condensing LCD Display Units ppm CO2 C F for optional temperature setpoint Display Range 0 10 000 ppm 0 to 50 C 0 to 122 F Display Size 35mm W x 15mm H 1 4 x 0 6 Digit Height 2 line x 8 character OPTIONAL TEMPERATURE SENSOR ...