LIT25 Level Indicating Transmitter
Manual Series 3.5.1
dp10
706.9
721.4
r oFF
r on
r o c 1
20 =
40.6
762.0
4 =
123.4
CALU
638.6
CM
CM
CM
CM
LEVEL CM
PERCENT INCHES CM
RANGE CM
23c
3, 5
1, 2, 4
TEMPERATURE
Displays Temperature at Sensor
RANGE DISPLAY
Displays Distance from Sensor to Target
(Does not affect 4-20mA output or Relay)
NORMAL MODE
CALIBRATION UNITS SELECTION
Press
Ç
to select inches, cm or percent
4mA and 20mA CALIBRATION
Wait for the Numeric value then press
Ç
È
È
or
to increase
or decrease. Value displayed is Distance from the Sensor
in inches or cm.
for Next Function
Wait for 4 = or 20 = and Press
RELAY SET POINTS
Wait for Numeric value and press
C).
°
Ç
È
and
to
adjust Set Points (in Units selected, or
DAMPING (0 - 20 SECS. )
Press
to Adjust
Ç
RELAY OPERATION CHOICE
Press
Ç
to select:
1 = Level Alarm
2 = Level + Echo Loss
3 = Echo Loss Only
4 = Temperature Alarm
5 = Off
13
13
8
8
9
10
11
11
12
12
See Page #
YES?
-C .S-
0.0
OPSL
ELC 1
CM
YES
NO
ECHO LOSS CHOICE (4-20mA OUTPUT)
Press
to Select action when echo lost
1 - Hold
2 = Go to 4mA
3 = Go to 20mA
Ç
OUTPUT SIMULATION
Wait for Numeric value and press
or
to Increase
or Decrease Simulated Output
(Automatically returns to NORMAL mode in 10 min.).
Ç
È
STORE YES?
Press
to Store Calibration (Displays -C.S.-)
Ç
Press
Calibration Not Stored
È
Sb=n
Press
equipped with an optional Intrinsic Safety Barrier for
sensor mounting in hazardous locations. This setting
compensates for the electrical characteristics of an
Intrinsic Safety Barrier.
Ç
to select "Y" (Yes) only when the instrument is
11