background image

Greenfire Pellet Stove and Insert Technical Manual

22

TROUBLESHOOTING

Blocked exhaust / venting system - Have stove and venting cleaned and inspected.

Severe negative pressure in area where unit is installed - Check the operation by opening a window, does this solve the problem? If it does, install 

fresh air intake to unit or room. Venting system may require vertical section to move termination into a low pressure zone.

Vacuum Switch failure - Bypass the vacuum switch, if this corrects the problem check for above problems before replacing the Vacuum Switch.

Damage to gray wires between Circuit Board and Vacuum Switch - Inspect wires and connectors 

Combustion Blower failure - The Combustion Blower is not turning fast enough to generate the proper vacuum in the Exhaust Channel. 

Visual Check; is the blower motor turning?  Check the Exhaust Blower voltage across the blower wires (>=114 V on #5 setting and >= 82 V on #1 

setting). – Replace the Circuit Board if the Voltage reading is less than 82 V. with a line voltage >114 V AC. 

Check Vacuum levels in the exhaust channel by bypassing the vacuum switch, then remove the Vacuum hose from Vacuum Switch.  Check exhaust 

vacuum readings by placing the open end of the Vacuum Hose on a Magnahelic Gauge. (readings must be above .10” W.C. on low fire).  

If the motor fails to reach a 0.10” W.C. readings, then replace the Combustion Blower

 

To reset Ci

rcuit Board after a trouble code - push the ON/OFF button

5. Auger light flashes but auger motor does not turn at all

.

If 

the Auger gear box does not turn but the motor’s armature does try to spin then the auger is jammed. – Try to break apart jam by poking at the 

jam through the drop tube. If this fails then empty the hopper and remove the Auger Cover **Remember to re-seal the cover after installation**  

Check the fuse on the circuit board.

6.

 Light #4 – 200°F ( 93°C) high limit temperature sensor has tripped.

 

 

Res

et sensor and determine cause – was it Convection Blower failure or 160 °F ( 71 °C) Temperature Sensor failure?  Bypass the 160 °F ( 71 °C) 

sensor, does the Convection blower come on high? If not, replace the blower. If yes, replace sensor (located on the left side of the firewall).

Check the fuse on the circuit board.

7

. The convection blower will not function normally.

Clean all grill openings at the back and below unit .

Press the fan button; does the fan come on? Press again to verify that the blower turns on; if, not contact your local dealer for service.

8. Ignitor- the pellets will not light.

Everything else in the stove operates but the ignitor will not light the pellets.

Make sure the burn pot liner is up tight and square to the ignitor tube by pushing the burn pot back against the ignitor tube.

Check to see if the exhaust blower is operating. If not, contact your local dealer for service.

Check the fuse on the circuit board.

NOTE:

 The ignitor should be bright orange in color. If not replace the ignitor.

9. Control settings (Heat Level) has no effect on the fire.

NOT

E: If the system light is flashing the Control Board has complete control of the unit. When the units system light becomes solid then control of 

the unit is given back to the operator.

If there is no control of the Heat Level button make sure the thermostat is calling for heat.

Call your local dealer for service.

10. The stove keeps going out.

If the stove

 goes out and leaves fresh unburned pellets or cigarette-like ashes in the burn pot liner, the fire is going out before the stove shuts off.

Check to see that the Slider / Damper is in the correct position.

Turn the Heat Level up slightly (poor quality pellets will require slightly higher settings).

Set the auger trim till the #1 and #5 lights are illuminated.

If the stove goes out and there are partially burned pellets left in the burn pot liner, the stove has shut down due to a lack of air, exhaust temperature, 

or power failure.

Adjust the Slider / Damper.

Check to see if the stove needs a more complete cleaning.

Did the power go out?

Contact your local Dealer for service.

  

Summary of Contents for Greenfire GF55

Page 1: ...r additional information consult an authorized installer or service agency FOR YOUR SAFETY Donotstoreorusegasolineorotherflammable vapours and liquids in the vicinity of this or any other appliance In...

Page 2: ...Efficiency 74 5 LHV 70 HHV FIRE EXTINGUISHER AND SMOKE DETECTION All home with a pellet burning stove should have at least one fire extinguisher in a central location known to all the household Smoke...

Page 3: ...ough Concrete Wall with Vertical Rise 13 Inside Vertical Installations 13 Outside Vertical Installations 14 Hearth Mount Installations 14 GFI55 Pellet Insert 15 Clearances to Combustibles 15 Fireplace...

Page 4: ...e ALIMENTATION LECTRIQUE 120 Volts 60 Hz 4 3 A Maintenir le c ble lectrique l cart de l appareil de chauffage For Use With Only Pelletized Wood fuels Keep viewing and ash removal doors tightly closed...

Page 5: ...ING PELLET STOVE 341 8 866mm 231 16 586mm 19 16 40mm 197 16 494mm 131 16 332mm 247 16 620mm 24 610mm 1 25mm 191 8 866mm 24 610mm 129 16 319mm 15 8 41mm 145 8 371mm 231 16 586mm 3 76mm 205 16 516mm 511...

Page 6: ...16 582mm 203 8 517mm 241 16 610mm 11 16 26mm 13 329mm 10 253mm 225 16 567mm 13 8 35mm 303 16 766mm 71 4 183mm 2215 16 582mm 203 8 517mm 241 16 610mm 11 16 26mm 13 329mm 10 253mm FACEPLATE DIMENSIONS R...

Page 7: ...ent of the fuel used and the operation of the stove It is advisable to inspect and clean the exhaust vent semi annually or every two tons of pellets ELECTRICAL The use of a surge protected power bar i...

Page 8: ...nd roof REMOVING PELLET STOVE FROM PALLET To remove your new stove from its pallet remove the two 2 screws securing the bottom to the pallet Freestanding One screw can be easily seen from behind but t...

Page 9: ...m Clearances to Combustibles ALCOVE CLEARANCES Minimum Width 36 914mm Minimum Height 48 1219mm Maximum Depth 30 762mm Figure 5 Alcove Clearances CLEARANCES TO COMBUSTIBLES MOBILE HOME INSTALLATION Sec...

Page 10: ...ixture is out of balance a slight discoloration of the exterior of the house might occur Since these factors are beyond the control of FPI we grant no guarantee against such incidents NOTE Venting ter...

Page 11: ...n airtight homes and mobile homes A Fresh air intake is strongly recommended for all installations Failure to install intake air may result in improper combustion as well as the unit smoking during po...

Page 12: ...um of 3 8 cm clear ance from the back of the stove to the wall Seal the vent pipe to the thimble with high temperature silicone 10 The pipe must extend at least 12 30 cm away from the building If nece...

Page 13: ...manner so when the pellet vent is installed vertically it will be 3 76 mm away from a combustible wall 3 Locate the center of the fresh air intake pipe on the unit Match that center with the same poi...

Page 14: ...Rain cap Flashing 24 61 cm 3 7 5cm Tee with cleanout Fresh air intake 3 7 5 cm Clearance Support bracket Type L PL or all fuel vent Figure 16 Outside Vertical Installation HEARTH MOUNT INSTALLATION 1...

Page 15: ...so that the clip will be facing up Thread hex nut onto the bolt till it is approximately 1 25 mm from the bolt head slide washer onto bolt Thread the bolt into the square nut so length of the bolt sh...

Page 16: ...s unit ensure that the pedestal is removed from the inside of the hopper and installed on the bottom of the unit Refer to Installation of Pedestal and Leveling Legs Adjust hopper height refer to Insta...

Page 17: ...rom the chimney from coming back into the fireplace and prevent air from the fireplace from entering the chimney which will affect proper drafting of appliance A qualified installer should evaluate th...

Page 18: ...d on top of the unit while the control panel is removed or disconnected If electrical connection is required for the maintenance remove the circuit board control panel from the surround If electrical...

Page 19: ...lass retainer Ensure the four screws are also hand tight and close door Do not overtighten or you may break screws Cleanallplatedsurfacesbeforestartingthestove Referto Cleaning PlatedSurfacesinRoutine...

Page 20: ...is requires more primary air the slider damper must be pulled out to compensate Pulling the slider damper out gives the fire more air Slider Damper Exhaust Channel Exhaust Blower Note Some parts have...

Page 21: ...ing completely unburned fuel in the burn pot liner Insufficient air will cause build up further restricting the air flow through the Burn Pot Liner This in turn will cause the fuel to burn cold and ve...

Page 22: ...sensor and determine cause was it Convection Blower failure or 160 F 71 C Temperature Sensor failure Bypass the 160 F 71 C sensor does the Convection blower come on high If not replace the blower If y...

Page 23: ...Black White Grey Grey Vacuum Switch Black White Thermostat 120 V Grounded Connector Ground Green White Red Ignitor Auger Motor White Yellow 5 Amp Fuse Convection Blower Connect Thermostat Here High Li...

Page 24: ...Roll Nut GF55 GFI55 2 Set 11 GF55 028 Glass Side GF55 GFI55 12 GF55 029 Glass Front GF55 GFI55 GF55 033 Exhaust Starter Tube 3x2 5 GF55 GFI55 GF55 036 Cleaning Rod Heat Tube GF55 GFI55 13 GF55 037 Bu...

Page 25: ...Greenfire Pellet Stove and Insert Technical Manual 25 7 6 2 9 1 14 8 3 5 PELLET STOVE COMPONENTS PARTS LIST...

Page 26: ...Greenfire Pellet Stove and Insert Technical Manual 26 17 25 26 28 19 16 20 21 4 10 13 18 27 29 34 15 12 11 GF55 FREESTANDING PELLET STOVE PARTS LIST...

Page 27: ...Greenfire Pellet Stove and Insert Technical Manual 27 24 32 33 31 22 23 30 GFI55 PELLET INSERT PARTS LIST...

Page 28: ...t in manufacture or FPI factory assembled components only unless herein specified otherwise Any part s found to be defective during the warranty period as outlined above will be repaired or replaced a...

Page 29: ...cardboard coal or coal products oil based products waxed cartons compressed pre manufactured logs lack of regular maintenance and upkeep acts of God weather related problems from hurricanes tornados...

Page 30: ...ide the U S should consult their local provincial or national legal codes for additional terms which may be applicable to this warranty How to Obtain Warranty Service Customers should contact the auth...

Page 31: ...in order for us to serve you better Warranty Registration Form or Register online immediately at the above Web Site Warranty Details Serial Number required Purchase Date required mm dd yyyy Product De...

Page 32: ......

Page 33: ...___________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ _____...

Page 34: ...___________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ _____...

Page 35: ......

Page 36: ...e following information Dealer Name Address ________________________________________ ___________________________________________________________ Installer _____________________________________________...

Reviews: