p. 20/48
5.
Initial steps and starting of pellet burner of series “GP”
ATTENYION :
The burner should be installed, adjusted and verified
ONLY
by trained staff
of an authorized company
.
5.1.
Basic fuel requirements
The fuel should be dry. The unit producer recommends that the fuel should be stored
in dry and well ventilated rooms;
It is strongly forbidden to store the fuel in close region of the unit, on which the pellet
burner is installed, the minimal safety distance between the fuel and the appliance is
400 mm;
The burner producer recommends an optimal distance between the unit, on which the
pellet burner is installed, and the fuel bunker to be at least 1000mm. It is
recommended to store the fuel in room, next to that, where the system is installed;
At the installation procedure of the burner, as well as the fuel storage one, fire
prevention recommendation should be considered. It is also recommended to install a
fire-extinguisher in a safe and easy accessible place;
5.2.
Staring automatic pellet burner of series “GP”
Basic requirements :
Any maintenance procedures should be performed in accordance with the described in
this manual;
The operating mode of a system
: automatic pellet burner of series “GP” and a heat-
consumer
, should also cover the following requirement : the operating pressure in the
combustion chamber
should be below the atmosphere pressure
within the following
range: 5 - 20 Pa. The incompleteness of this requirement could lead to alarm modes of the
burner and/or ineffective operation regime of the burner. The operating pressure in the
combustion chamber of the heat-consumer strongly depends on the draught of
the flue stack as well as the hydraulic loses in the gas duct of the system (as
well as the operation of induced draught flue gas fan module installed). Any
operating modes, not complying with the requirements for the above defined
combustion chamber pressure range could be detected indirectly by the status
of the reversible thermosticker;
Any intervention in the working process of the unit, which could lead to unit’s failure
and/or dangerous and health threatening situations, are strongly prohibited;
The unit should be checked by the maintenance staff or any trained personal/end user
regularly;
The end-user should not perform any interventions, repairs, etc. of the unit. In case that
warning and failures arise, check the failures table (applied at the end of this manual) and
call the service support if the case is not described there;
Any adjustments of thermal capacity higher than the nominal thermal load of the unit is
not allowed;
The ash residue should be collected in fireproof containers and cooled down to ambient
temperature. The cooled ash should be disposed in appropriate waste containers. Please
take into account that the mineral ash, result of wood biomass pellets could be
considered/utilized as soil fertilizer and dispersed for agricultural purposes for example;