Service Manual
End
No
Yes
No
Yes
Yes
Yes
Yes
No
No
No
Yes
Yes
No
Turn the fan blades
by hand under
power-off condition
Whether the fan blades
can run smoothly?
Adjust the motor and blade
assembly so that rotor can run
smoothly.
Under power-off condition,
check whether the wiring terminal
between indoor fan and main
board is loose.
Turn unit on
to check whether the
malfunction is
eliminated.
Turn unit on
to check whether the
malfunction is
eliminated.
Reinsert the wiring
terminal of indoor fan.
It's the malfunction of main board.
Replace a new main board that is
of the same model.
It's the malfunction of main board.
Replace a new main board that is
of the same model.
Replace a new main board that is
of the same model.
It's the malfunction of main board.
Then check whether the voltage
between terminal 2 and terminal 3
of the motor interface is 15VDC.
Connect power and restart the unit.
Test whether the voltage between terminal 1 and terminal 2
of motor interface is within 280~310VDC.
Then check whether there is voltage
between terminal 2 and terminal 4
of the motor interface.
It's the malfunction of motor.
Replace a new motor that is
of the same model.
Start
No
63
Summary of Contents for LIVV09HP230V1A Series
Page 103: ...190 Service Manual 100 ...
Page 109: ...214 Service Manual LIVV24HP230V1AO LIVV18HP230V1AO Note Take heat pump for example 106 ...
Page 110: ...215 Service Manual 107 ...
Page 111: ...216 Service Manual 108 ...
Page 112: ...217 Service Manual 109 ...
Page 113: ...218 Service Manual 110 ...
Page 114: ...219 Service Manual 111 ...