F:Inspection
● Check the quality of expanding port. If there is any blemish, expand the
port again according to the steps above.
The length is equal
Improper expanding
leaning
damaged
surface
crack
uneven
thickness
Smooth surface
Downwards
Pipe
Shaper
Union pipe
Pipe
Expander
Hard
mold
Pipe
Pipe
Pipe cutter
Leaning
Uneven
Burr
Improper pipe expanding is the main cause of refrigerant leakage.Please
expand the pipe according to the following steps:
A:Cut the pip
● Confirm the pipe length according to the distance of indoor unit and outdoor unit.
● Cut the required pipe with pipe cutter.
B:Remove the burrs
● Remove the burrs with shaper and prevent the burrs from getting into the pipe.
C:Put on suitable insulating pipe
D:Put on the union nut
● Remove the union nut on the indoor connection pipe and outdoor valve; install
the union nut on the pipe.
E:Expand the port
● Expand the port with expander.
● "A" is different according to the diameter, please refer to the sheet below:
Outer
diameter(inch)
A(inch)
Max
Min
Ф0.24 - 0.25 (1/4")
0.05
0.03
Ф0.37 (3/8")
0.06
0.04
Ф0.47 - 0.50 (1/2")
0.07
0.04
Ф0.63 - 0.625 (5/8")
0.09
0.09
Appendix 3: Pipe Expanding Method
Note:
Note:
113
Summary of Contents for LIVV09HP230V1A Series
Page 103: ...190 Service Manual 100 ...
Page 109: ...214 Service Manual LIVV24HP230V1AO LIVV18HP230V1AO Note Take heat pump for example 106 ...
Page 110: ...215 Service Manual 107 ...
Page 111: ...216 Service Manual 108 ...
Page 112: ...217 Service Manual 109 ...
Page 113: ...218 Service Manual 110 ...
Page 114: ...219 Service Manual 111 ...