29
Installation Manual
Ø
Outdoor condensation drainage (Heat pump type only)
When the unit is heating, the condensing water
and defrosting water can be drained out reliably
through the drain hose.
Installation: Install the outdoor drain elbow in
25 hole on the base plate, and joint the
drain hose to the elbow, so that the wastewater
formed in the outdoor unit can be drained out
to a proper place.
Chasis
Outdoor drain
elbow
Fig.6
Use soap water or leak hunting meter to check whether
the joints is leak.
Indoor unit check point
Outdoor unit check point
Leak hunting
5
Air purging and leakage test
Liquid pipe
Gas pipe
Valve
cap
Vacuum
gauge
Vacuum pump
Fig.
1. Connect charging hose of manifold valve to charge end of low
pressure valve (both high/low pressure valves must be tightly
shut).
2. Connect joint of charging hose to vacuum pump.
3. Fully open handle of Lo manifold valve.
4. Open the vacuum pump to evacuate. At the beginning, slightly
loosen joint nut of low pressure valve to check if there
is air coming inside. (If noise of vacuum pump has
been changed, the reading of multimeter is 0) Then
tighten the nut.
5. Keep evacuating for more than 15mins and make
sure the reading of multi-meter is
6. Fully open high/low pressure valves.
7. Remove charging hose from charging end of low
pressure valve.
8. Tighten bonnet of low-pressure valve. (As shown in Fig.5)
-1.0 10 pa
(-76cmHg)
Summary of Contents for GWC36LB-D1NNA2A/I
Page 1: ...5 75 33 1 6 1 2 8 6HUYLFH 0DQXDO 02 11 11 5HIULJHUDQW 5...
Page 12: ...9 840 1018 412 3 2 Outdoor Unit Constrction views 572 950 378...
Page 35: ...32 8 Exploded Views and Parts List 8 1 Indoor Unit Exploded Views and Parts list...
Page 38: ...35 Exploded Views and Parts list GWC36LB D1NNA2A O 8 2 Outdoor Unit...
Page 40: ...37 Exploded Views and Parts list GWH36LB D1NNA2A O...