Design & Selection
58
According to the calculation results, the sum of the on-way resistance and the local resistance is:
The dynamic pressure of the diffuser is:
For FP-102WA, based on the air flow of 1020m3/h and the outlet side of 820mm*130mm, the air
speed at the air outlet is 4.95m/s.
The dynamic pressure is:
The required total external pressure is:
The required external static pressure is:
The designed external static pressure is 12Pa, which is approach to the required external static
pressure 13.2Pa. Therefore, the selection result is satisfactory.
When selecting units, the practice is to match the design sensible heat load with the required
sensible load. In most cases, there is enough latent heat for the coils to meet the design requirement.
(1) Power Lines
Model
Power Supply
Sectional Area (mm2)
FP-*WA/G-K
FP-*WAH/G-K
FP-*WAS/G-K
FP-*WAHS/G-K
220-240VAC 1Ph 50Hz
1
FP-*WA/G-D
FP-*WAH/G-D
FP-*WAS/G-D
FP-*WAHS/G-D
208-230VAC 1Ph 60Hz
1
FP-*WA/GHL-K
FP-*WAH/GHL-K
FP-*WAS/GHL-K
FP-*WAHS/GHL-K
220-240VAC 1Ph 50Hz
1
Note:
“*” indicates the air flow between 34~204.
Pa
P
P
J
L
11
.
12
Pa
v
P
d
09
.
3
27
.
2
2
.
1
2
1
2
1
2
2
Pa
v
P
dy
24
.
4
66
.
2
2
.
1
2
1
2
1
2
2
Pa
P
P
P
P
d
J
L
YY
24
.
18
)
09
.
3
11
.
12
(
2
.
1
)
(
2
.
1
Pa
P
P
P
P
P
dy
d
J
L
JY
2
.
13
)
24
.
4
09
.
3
11
.
12
(
2
.
1
)
(
2
.
1
Summary of Contents for FCU Series
Page 1: ...Concealed Ceiling Type FCU...
Page 3: ...Enginnering Data 1 Engineering Data...
Page 57: ...Design Selection 55 Design Selection...
Page 61: ...Unit Control 59 Unit Control...
Page 63: ...Unit Installation 61 Unit Installation...
Page 72: ...Unit Installation 70 2 2 Installation Steps...
Page 73: ...Test Operation Troubleshooting Maintenance 71 Test Operation Troubleshooting Maintenance...
Page 79: ...No JF00303582...