Enginnering Data
16
50Hz (without the return air box), 3+1-row pipes
Type
Item
Concealed
ceiling type
FP-34WA
T-R
FP-51WA
T-R
FP-68WA
T-R
FP-85WA
T-R
FP-102W
AT-R
FP-136W
AT-R
FP-170W
AT-R
FP-204
WAT-R
P
e
rfo
rman
c
e
Airflow
Hi
m
3
/h
340
510
680
850
1020
1360
1700
2040
Mid
248
393
510
638
788
1095
1275
1575
Low
213
263
340
425
525
730
850
1050
Cooling
capacity
Hi
W
2300
3600
4350
5400
6700
8100
10350
11000
Heating
capacity
Hi
W
2100
3350
4000
4600
5350
7000
8300
8950
Flow rate
m
3
/h
0.446
0.697
0.808
0.98
1.171
1.45
1.747
1.964
Water resistance
kPa
5.83
13.50
19.86
30.81
51.67
17.20
25.24
29.34
Noise
30Pa
40
42
44
46
47
48
50
52
External static
pressure
Pa
30pa
Coil
Type
Copper, high-efficiency louvered fins
Pressure
≤1.6MPa
Motor
Type
Class B, capacitor start
Quantity
/
1
2
Power supply
220-240V
~
50Hz
Protection class
IP20
Input power 30Pa
W
43
59
70
84
105
151
174
206
Power lines
mm
2
0.5×3
Protection class
I
Fan
Type
Front-forward multi-vane low-noise centrifugal fan
Quantity
/
1
2
3
4
Connection pipe
Inlet water
Rc3/4(female thread)
Outlet water
Rc3/4(female thread)
Condensate
R23/4(female thread)
Weight
Without return
air box
kg
14.4
17.2
19.2
20.5
23.2
34.2
37.5
37.5
Thermostat (optional)
Mechanical
Z54352A1
Digit
WK-110PA0
Deluxe digit
WK-010PA-K-K
Notes:
a) The left and right modes can be switched over on site. The correction coefficient for both
cooling and heating is 0.9.
b) Nominal cooling conditions: (27/19.5
℃
) indoor dry/wet bulb temperature, (7/12
℃
) entering
and leaving water temperature. Nominal heating conditions: 21
℃
indoor dry bulb
temperature, 60
℃
entering water temperature.
c) The noise is tested under the semi-anechoic chamber and the actual value will change
under different environments.
Summary of Contents for FCU Series
Page 1: ...Concealed Ceiling Type FCU...
Page 3: ...Enginnering Data 1 Engineering Data...
Page 57: ...Design Selection 55 Design Selection...
Page 61: ...Unit Control 59 Unit Control...
Page 63: ...Unit Installation 61 Unit Installation...
Page 72: ...Unit Installation 70 2 2 Installation Steps...
Page 73: ...Test Operation Troubleshooting Maintenance 71 Test Operation Troubleshooting Maintenance...
Page 79: ...No JF00303582...