Enginnering Data
21
Section two --- countries and areas within the European Union
Horizontal concealed FCU, standard (G series, 220~240VAC, 50Hz, EU)
Model
Item
Unit
FP-34WA/
GHL-K
FP-51WA/
GHL-K
FP-68WA/
GHL-K
FP-85WA/
GHL-K
FP-102WA
/GHL-K
FP-136WA
/GHL-K
FP-170WA
/GHL-K
FP-204WA
/GHL-K
P
e
rfo
rman
c
e
Air flow
High
m³/h
370
570
720
870
1020
1360
1600
1900
Medium
260
400
504
610
788
1095
1120
1330
Low
180
280
353
426
525
730
784
931
Cooling
capacity
High
W
1750
2900
3400
4300
4900
6700
7000
10000
Heating
capacity
High
W
2200
3400
4200
4700
6000
8000
9000
18900
Water flow
m³/h
0.30
0.50
0.59
0.74
0.84
1.15
1.21
1.72
Water resistance
kPa
15
30
23
25
35
40
36
40
Noise
dB(A)
37
38
40.5
44
46
46
47
50.5
External static
pressure
Pa
0Pa
Coils
Type
Copper tube and lourved fins
Working pressure
≤1.6MPa
Motor
Type
Class B insulation, capacitor start
Quantity
piece
1
2
Power lines
220-240V
~
50Hz
Protection class
IP20
Input power
W
35
54
66
84
101
150
154
198
Power lines
mm
2
×piece
0.5×3
Anti electric shock class
I
Fan
Type
Forward multiple-vane low-noise centrifugal fan
Quantity
piece
1
2
3
4
Connection pipe
inlet
Rc3/4(inner thread)
outlet
Rc3/4(inner thread)
condensate
Rc3/4(external thread)
Net weight
kg
14.5
17
18.9
20.8
21.9
31.5
34.1
38
Outline
dimensions
Width
mm
680
800
900
1000
1080
1380
1520
1620
Depth
mm
500
500
500
500
500
500
500
500
Height
mm
235
235
235
235
235
235
235
235
Thermostat (optional)
Mechanical
Z54352A1
Digital
WK-110PA0
Digital (deluxe)
WK-010PA-K-K
Notes:
a) The left and right modes can be switched over on site. The correction coefficient for both
cooling and heating is 0.9.
b) Nominal cooling conditions: (27/19.5
℃
) indoor dry/wet bulb temperature, (7/12
℃
) entering
and leaving water temperature. Nominal heating conditions: 20
℃
indoor dry bulb
temperature, 45
℃
entering water temperature and 40
℃
leaving water temperature.
c) The noise is tested under the semi-anechoic chamber and the actual value will change
under different environments.
Summary of Contents for FCU Series
Page 1: ...Concealed Ceiling Type FCU...
Page 3: ...Enginnering Data 1 Engineering Data...
Page 57: ...Design Selection 55 Design Selection...
Page 61: ...Unit Control 59 Unit Control...
Page 63: ...Unit Installation 61 Unit Installation...
Page 72: ...Unit Installation 70 2 2 Installation Steps...
Page 73: ...Test Operation Troubleshooting Maintenance 71 Test Operation Troubleshooting Maintenance...
Page 79: ...No JF00303582...