Enginnering Data
24
Horizontal concealed FCU, 3-row-pipe (G series, 220~240VAC, 50Hz, EU)
Model
Item
Unit
FP-34WAH
S/GHL-K
FP-51WAH
S/GHL-K
FP-68WAH
S/GHL-K
FP-85WAH
S/GHL-K
FP-102WAH
S/GHL-K
FP-136WA
HS/GHL-K
FP-170WA
HS/GHL-K
FP-204WA
HS/GHL-K
P
e
rfo
rman
c
e
Air flow
High
m
3
/h
450
590
750
930
1100
1400
1700
2000
Medium
315
413
525
651
770
980
1190
1400
Low
220
290
367
455
539
686
833
980
Cooling
capacity
High
W
2500
3300
4200
4900
6100
7800
9000
10500
Heating
capacity
High
W
2800
3800
5100
5700
6900
9000
10900
12400
Water flow
m
3
/h
0.43
0.57
0.72
0.84
1.05
1.34
1.55
1.81
Water resistance
kPa
20
21
22
30
35
40
33
40
Noise
dB(A)
39
40
42
46
49
49
49
52
External static
pressure
Pa
0Pa
Coils
Type
Copper tube with lourved fins
Working pressure
≤1.6MPa
Motor
Type
Class B insulation, capacitor start
Quantity
piece
1
2
Power supply
220-240VAC 50Hz
Protection class
IP20
Input power
W
46
57
72
83
108
164
185
221
Power lines
mm
2
×pieces
0.5×3
Anti electric shock class
I
Fan
Type
Forward multi-vane low-noise centrifugal fan
Quantity
个
1
2
3
4
Connection pipe
Inlet
Rc3/4(inner thread)
Outlet
Rc3/4(inner thread)
Condensate
Rc3/4(external thread)
Net weiht
kg
14.9
17.4
19.3
21.3
22.7
30.9
34.5
38
Outline dimensions
Width
mm
680
800
900
1000
1080
1380
1520
Depth
mm
500
500
500
500
500
500
500
Height
mm
235
235
235
235
235
235
235
Thermostat (optional)
Mechanical
Z54352A1
Digital
WK-110PA0
Digital
(Deluxe)
WK-010PA-K-K
Notes:
a) The left and right modes can be switched over on site. The correction coefficient for both
cooling and heating is 0.9.
b) Nominal cooling conditions: (27/19
℃
) indoor dry/wet bulb temperature, (7/12
℃
) entering
and leaving water temperature. Nominal heating conditions: 20
℃
indoor dry bulb
temperature, 45
℃
entering water temperature and 40
℃
leaving water temperature.
c) The noise is tested under the semi-anechoic chamber and the actual value will change
under different environments.
Summary of Contents for FCU Series
Page 1: ...Concealed Ceiling Type FCU...
Page 3: ...Enginnering Data 1 Engineering Data...
Page 57: ...Design Selection 55 Design Selection...
Page 61: ...Unit Control 59 Unit Control...
Page 63: ...Unit Installation 61 Unit Installation...
Page 72: ...Unit Installation 70 2 2 Installation Steps...
Page 73: ...Test Operation Troubleshooting Maintenance 71 Test Operation Troubleshooting Maintenance...
Page 79: ...No JF00303582...