Manual Module M-G2 33302
06
Transmitter low-voltage warning (ALARM VOLT):
you can adjust the low voltage threshold at which
the alarm (continuous beeping) is triggered; the available range is 4 - 15 V.
When the alarm is triggered, “VOLT-E”
fl
ashes at top right in the SMART-BOX transmitter display, and
the parameters ACTION VOLT and ALARM VOLT are displayed in inverse form.
Please note: the transmitter’s own low-voltage warning (beep), as set in the “General settings”
menu, is triggered independently of the value set under TX-Display!
Binding a receiver (RX BIND):
refer to chapter 6.1. Binding
SD card function (SD SAVE):
refer to chapter 6.8. Data storage
C
ountry selection (COUNTRY):
The Country setting is present in order to cater for various directives
(FCC, ETSI, IC etc.). The HoTT 2.4 radio system features a restricted frequency band for France. If
you wish to use the RC system in France, the country setting on the transmitter must be set to “France”
mode, as described. It is essential not to use the Universal/EUROPE mode. Factory setting is GENE-
RAL. See also point 6.4.
Range checking (RANGE TEST):
switches the range test on or off, the remaining time is displayed. The display also works if the range
check is started with the BIND / RANGE button on the transmitter. See also point 6.2.
Multichannel 1 / 2 (MULTIC 1 / 2:
Multi-channel function for the use with the Nautic-Expert-Module
order no. 4108. Up to 2 multi-channel channels can be used, the appropriate channels must be set in
the display under MultiC. If no Nautic module is used, set MULTIC to 00.
Note:
The cycle time (PERIOD) must be set to
20 msec, the channel sequence (CH OUTPUT
TYPE) to SAME so that the function is activated!
Parameters which have different options in the Settings column of the table can be adjusted using the
SMART-BOX. If there are no options, the screen simply displays the parameter data. If you wish to carry
out an adjustment, you must use the INC or DEC buttons above the screen to select the desired para-
meter (e.g. ALARM VOLT) by moving the arrow cursor (INC moves the cursor down, DEC moves it up).
Simultaneously pressing the INC and DEC buttons switches the parameter to be adjusted to inverse
video (white on black); this indicates that it can be programmed: pressing the INC button at this point
increases the value, pressing the DEC button reduces the value. When the adjustment is complete,
save the selected setting by pressing the INC and DEC buttons simultaneously; the dark background
now disappears in order to con
fi
rm this action.
Please note:
the labeling of the arrows of the following displays corresponds the top buttons on the
SMART-BOX.
RX SERVO < >
OUTPUT CH: 01
REVERSE : ON
CENTER
: 1500usec
TRIM :
-000usec
TRAVEL- :
100%
:
100%
PERIOD
:
20msec
RX SERVO TEST <
ALL-MAX : 2000usec
ALL-MIN
: 1000usec
TEST
:
STOP
ALARM VOLT : 3.8V
ALARM TEMP+ : 70°C
ALARM TEMP- : 10°C
CH OUTPUT TYPE: SAME
DEC
INC
RX DISPLAY
ENTER
INC + DEC
ESC
T X : S D - c a r d l o g O N
A: 11.3 VM: 11.4V m: 11.2V
VA R I O T O N E : O N
RANGE TEST : OFF 90s
R X B I N D :
B I N D
ALARM VOLT
:
9.3V
COUNTRY :GENERAL
MULTIC1: 00 MULTIC2: 00
T X : S D - c a r d l o g O N
A: 11.3 VM: 11.4V m: 11.2V
VA R I O T O N E : O N
RANGE TEST : OFF 90s
R X B I N D :
B I N D
ALARM VOLT
:
9.3V
COUNTRY :GENERAL
MULTIC1: 00 MULTIC2: 00