IPU-POD128 build and test guide
3.7.1 IPU-M2000 power cabling
Start by cabling IPU-M2000 #1 using 0.5m power cables. Ensure that only three IPU-M2000s are connected to
the same bank on the PDU. Red cables to the left PDU and blue cables to the right PDU (as seen looking at the
rear of the rack).
defines the power cable lengths for each IPU-M2000:
Table 3.10: Power cables for IPU-M2000s
Cable colour
Cable length
IPU-M2000
Blue
1m
IPU-M2000 #13 to IPU-M2000 #16
Red
1m
IPU-M2000 #13 to IPU-M2000 #16
Blue
0.5m
IPU-M2000 #1 to IPU-M2000 #12
Red
0.5m
IPU-M2000 #1 to IPU-M2000 #12
and
show part of the IPU-M2000 power cabling for the red PDU and blue PDU, respectively.
Fig. 3.64: IPU-M2000 power cabling (red PDU)
Fig. 3.65: IPU-M2000 power cabling (blue PDU)
Version: latest (2021-11-25)