Section 7: Sealed Systems
page 20
All Grant Vortex Boiler House models are suitable for use with
sealed systems complying with the requirements of BS EN 12828,
BS EN 12831 and BS EN 14336.
The system must be provided with the following items:
•
Diaphragm expansion vessel complying with BS EN 13831
•
Pressure gauge
•
Pressure relief (safety) valve
•
Approved method for filling the system
7.1.1 ExpaNSiON VESSEL
The expansion vessel should be fitted in the return pipework
as shown in Figure 7-2. To reduce the operating temperature
of the expansion vessel, position it below the pipe to which it is
connected.
The expansion vessel may be positioned away from the system,
providing the connecting pipe is not less than 13 mm diameter. If
the expansion vessel is connected via a flexible hose, care must
be taken to ensure that the hose is not twisted or kinked.
7.1 SEaLED SYStEm
REQUiREmENtS
Figure 7-1:
Key to sealed system diagram
Key
1
Expansion vessel
2
Pressure gauge
3
Pressure relief valve
4
Tundish
5
Removable filling loop
6
Double check valve
7
Automatic air vent
8
Thermostatic radiator valve
9
Automatic bypass
10
Drain point
Static head of system
Figure 7-2:
Sealed system
7 SEaLED SYStEmS
Highest point of primary circuit
Centre of expansion vessel