6.3 ST9103A 1028 CONTROL BOARD SEQUENCE
ST9103 Heating Sequence
1) Thermostat calls for Heat.
2) Burner starts
3) Blower starts after 45 seconds
4) Burner shuts down after call for heat is satisfied
5) Blower stops according to adjusted (FAN OFF) Dip switch selection
ST9103 Cooling Sequence
1) Thermostat calls for cooling
2) Blower starts immediately
3) Cooling unit starts
4) Blower stops immediately after cooling demand is satisfied
5) Cooling unit stops
Honeywell ST9103A 1028 Electronic Board