70 310531
Control Panel Operator Interface
PrecisionFlo Module Control Panel
The control panel has these indicators and switches:
Control / Indicator
Name
Device ID
Control / Indicator Description
POWER ON /
GROUND CON-
NECTED
LT113
Light is ON when both electric power and a proper ground are connected
to the PrecisionFlo control assembly. If the main circuit breaker is ON and
the light is either dimly lit or unlit, have a qualified electrician check the
power wiring to the module.
CONTROL ON
LT127
Light is ON when the MASTER CONTROL RELAY (MCR) is engaged.
DISPENSER SYS-
TEM STOP
PB1252
Push this button to disengage the MCR and signal the external controller
that an Dispenser System Stop condition is in effect. The MCR will remain
disengaged until the MASTER START button is pressed.
MASTER START /
STOP RESET
PB1251
Push this button to restart the PrecisionFlo module after power is applied
to the module or the DISPENSER SYSTEM STOP button has been
pressed. This engages the MCR and signal the PrecisionFlo processor
that the module has power applied.