Code
Code
Code
Type
Type
Type
Name
Name
Name
Description
Description
Description
Solution
Solution
Solution
CAC2
Alarm
Communication Error
Solenoid Controller
The control
interface has lost
communication with
the solenoid controller
that is responsible for
color change.
• Verify CAN connection on the
system.
• Verify CAN connection on the
solenoid controller board.
• Check status LEDs on solenoid
controller board.
• Cycle the power.
• Adjust the selector switches on the
solenoid controller board.
CDC1
Alarm
Duplicate Solenoid
Controller
The system detects
multiple solenoid
controllers set to the
same identifier.
• The solenoid controller has the
same CAN ID as another module.
• Adjust the selector switches on the
solenoid controller board.
Table
Table
Table 12
12
12 HydroShield
HydroShield
HydroShield Errors
Errors
Errors
Code
Code
Code
Type
Type
Type
Name
Name
Name
Description
Description
Description
Solution
Solution
Solution
SIL0
Alarm
Pneumatic System
Stop Activated
The system has been
stopped using the
pneumatic system
stop input.
• Verify the wiring of the pneumatic
system stop pressure switch.
• Verify the integrated system
installation intended to stop the
HydroShield system.
SIL1
Alarm
Digital System Stop
Activated
The system has been
stopped using the
digital system stop
input.
• Verify the wiring of the pneumatic
system stop optocoupler.
•
Verify the integrated system
installation intended to stop the
HydroShield system.
P6FX
Alarm
Inlet Air Removed
The system no longer
detects inlet air.
Verify that the inlet air pressure
is greater than 70 psi (0.5 MPa,
4.8 bar), that air flow is sufficient,
and that the wiring on the pressure
switch is connected.
PJ11
Alarm
Linear Sensor Failure
Linear sensor is
not connected or
is reading outside
calibrated values.
• Verify that the linear sensor is
connected.
• Calibrate the linear sensor.
P611
Alarm
Gun Air V2P
Feedback Error
System cannot detect
feedback from air
V2P.
• Verify that the air V2P is
connected.
• Verify that the air V2P has power.
P613
Alarm
Fluid V2P Feedback
Error
System cannot detect
feedback from fluid
V2P.
• Verify that the fluid V2P is
connected.
• Verify that the fluid V2P has
power.
86