10.3.2 I
EA
– LN-Probe
Measurement is performed with the DUT in
the de-energized state.
This measurement is conducted between
LN and accessible parts insulated from PE
(also SELV parts – e.g. the secondary side of
chargers).
Connection
➭
Insert the test object’s mains plug into
the test socket.
➭
Connect the probe to the red probe
socket.
Procedure
➭
Press the
I
EA
key.
➭
Select the “
LN-Probe
” menu with the help
of the
scroll keys.
➭
Start the measurement by pressing the
OK
key.
➭
Contact all insulated, accessible, con-
ductive (and SELV) parts with the probe.
➭
If the respective measured value is larger
than the specified limit value,
OK
appears
at the display and the
LED lights up
green.
➭
You can repeat the measurement by
pressing the
scroll key (reset), after
which the LED
goes out briefly until
the next measurement is performed.