![GORMAN-RUPP PUMPS Super T6A60S-ZPP857-ESP Installation, Operation, And Maintenance Manual With Parts List Download Page 19](http://html1.mh-extra.com/html/gorman-rupp-pumps/super-t6a60s-zpp857-esp/super-t6a60s-zpp857-esp_installation-operation-and-maintenance-manual-with-parts-list_2246947019.webp)
OM-07174
SUPER T SERIES
OPERATION
PAGE C - 3
upon connection of power as a lamp test feature.
However, no relay outputs are closed during test.
3. Switches:
a) The
switch functions as a “round rob
in” type switch. Pressing this switch will
cause the unit to show the next selection
in the order listed above.
b) The
switch functions to decrease the
selection showing. This switch can be
used to decrease the smallest digit by
“bumping” the switch, or to continuously
decrease the digit by pressing and hold
ing for at least one second and releasing
when desired setting is reached.
c. The
switch functions to increase the
selection showing. This switch can be
used to increase the smallest digit by
“bumping” the switch, or to continuously
increase the digit by pressing and hold
ing for at least one second and releasing
when desired setting is reached.
Liquid level adjustment of the Electronic Pressure
Switch is accomplished using the three buttons on
the control. For EPS functions and level adjust
ment, refer to the following instructions.
EPS Functions
Actual functions of the control occur as follows:
Power is applied to the unit.
Unit performs display test for approximately 4
seconds.
When the pressure level showing is equal to or
greater than the “A.on” setpoint, the Horn out
put contacts will close in approximately 1 sec
ond and a delay, equal to the “Hrn dLy” time,
will occur before the A output contacts close.
When the level showing is equal to or greater
than the “B.on” setpoint, the B output contacts
will close in approximately 1 second.
When the pressure decreases to a level equal
to or less than the “B.of” setpoint, B output
contacts will open in approximately one sec
ond.
When the pressure decreases to a level equal
to or less than the “A.of” setpoint, A output con
tacts will open in approximately one second.
If an optional Low Temperature Thermostat is
connected to the unit and the thermostat con
tacts close, the unit displays “lo tpt” on the dis
play. In approximately 1 second, the Horn out
put contacts close, then after the “Hrn dLy”
time, A output contacts close. A output con
tacts will remain closed as long as Low Tem
perature Thermostat contacts are closed.
When the Low Temperature Contacts open, A
output contact will open
only
if the level is
equal to or less than the “A.off” setpoint.
As long a the Low Temperature Thermostat
contacts are closed, the display will show “lo
tpt” unless
switch is pressed to display
some other information. Level is not viewable
until the Low Temperature Thermostat con
tacts open.
The user may wish to check Setpoints Off/On
and Horn output/A output delay times. “Bump
ing” the
switch will display all of the informa
tion desired.
NOTE
One second delays in contact opening/closing is a
result of time sampling of the pressure signal to fil
ter false signals that could cause “nuisance” trip
ping of the contacts.
NOTE
If the “Hrn dLy” is changed during the actual A out
put delay cycle, the current cycle is not changed;
the change becomes effective on the next A output
delay cycle.
Use caution to ensure that the “‐‐.on” set
point (i.e. “A.on”) is not adjusted to a level
less than the corresponding “‐‐.of” set
point (i.e. “A.of”). Improper adjustment of
the off/on setpoints will render the unit non‐
functional, resulting in flooding.