JD Series
OM-05724
PAGE B - 4
INSTALLATION
ELECTRICAL CONNECTIONS
Install and operate this pump in accor
dance with the National Electrical Code
and all local codes. Have a qualified
electrician perform all checks and con
nections in this section.
Never attempt to alter the length of the
pump motor cable or to repair it with a
splice. The power cable and pump mo
tor must be kept completely waterproof.
Serious damage to the pump and injury
or death to personnel can result from
any alteration to the cable.
Field Wiring Connections (Incoming Power)
Field wiring is
not
provided with this pump, and
must be supplied by the user. The field wiring must
be of the proper size and type to ensure an ade
quate voltage supply to the pump. Voltage avail
able at the motor must be within the range indi
cated in Table B‐2.
NOMINAL
VOLTAGE
TABLE B‐2. MOTOR VOLTAGE LIMITS
PHASE
MINIMUM
VOLTAGE
MAXIMUM
VOLTAGE
3
460/3
420
500
Use conduit cable clamps to secure the incoming
field wiring to the control box. Make certain all con
nections are tight. If necessary, support the cable
weight to prevent excessive strain on cable clamps
and cable.
FIGURE B-2. FIELD CONNECTIONS
Motor Cable Grounding Test
Do not connect the pump control cable
to the control box or incoming voltage
before verifying the pump ground;
otherwise, personnel will be exposed to
serious injury or death.