12

BLOWER PERFORMANCE SPECIFICATIONS

1. Units are shipped without filter(s). CFM in chart is without filter(s).
2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as

needed. The first task is to determine the proper aiflow for the cooling system.

3. For most cooling applications, about 400 CFM per ton is desirable.
4. The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on rating

plate.

5. Do not operate above 0.5" w.c. ESP in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling

purposes only.

6. * Motor CFM minimum.

GMV95 Heating Speed Charts

Heating

Speed

Tap

Adjust

Tap

Low Stage

CFM

at .1" - .5" w.c.

ESP

High Stage

CFM

at .1" - .5" w.c.

ESP

Rise

(°F)

Heating

Speed

Tap

Adjust

Tap

Low Stage

CFM

at .1" - .5" w.c.

ESP

High Stage

CFM

at .1" - .5" w.c.

ESP

Rise

(°F)

Minus(-)

495

713

57

Minus(-)

756

1089

56

Normal  

550

792

51

Normal  

840

1210

50

Plus (+)

605

871

46

Plus (+)

924

1331

46

Minus(-)

540

778

52

Minus(-)

828

1192

51

Normal  

600

864

47

Normal  

920

1325

46

Plus (+)

660

950

43

Plus (+)

1012

1457

42

Minus(-)

585

842

48

Minus(-)

900

1296

47

Normal  

650

936

43

Normal  

1000

1440

42

Plus (+)

715

1030

39

Plus (+)

1100

1584

38

Minus(-)

630

907

45

Minus(-)

972

1400

43

Normal  

700

1008

40

Normal  

1080

1555

39

Plus (+)

770

1109

36

Plus (+)

1188

1711

35

Heating

Speed

Tap

Adjust

Tap

Low Stage

CFM

at .1" - .5" w.c.

ESP

High Stage

CFM

at .1" - .5" w.c.

ESP

Rise

(°F)

Heating

Speed

Tap

Adjust

Tap

Low Stage

CFM

at .1" - .5" w.c.

ESP

High Stage

CFM

at .1" - .5" w.c.

ESP

Rise

(°F)

Minus(-)

1013

1458

56

Minus(-)

1107

1594

63

Normal  

1125

1620

50

Normal  

1230

1771

57

Plus (+)

1238

1782

45

Plus (+)

1353

1948

52

Minus(-)

1076

1549

52

Minus(-)

1139

1639

62

Normal  

1195

1721

47

Normal  

1265

1822

56

Plus (+)

1315

1893

43

Plus (+)

1392

2004

50

Minus(-)

1139

1639

49

Minus(-)

1170

1685

60

Normal  

1265

1822

44

Normal  

1300

1872

54

Plus (+)

1392

2004

40

Plus (+)

1430

2059

49

Minus(-)

1202

1730

47

Minus(-)

1202

1730

58

Normal  

1335

1922

42

Normal  

1335

1922

53

Plus (+)

1469

2115

38

Plus (+)

1469

2115

48

C

D

GMV950453BX*  (Rise Range:  30 - 60°F)

A

B

D

GMV950704CX*  (Rise Range:  30 - 60°F)

A

B

C

GMV950905DX*  (Rise Range:  30 - 60°F)

GMV951155DX*  (Rise Range:  30 - 60°F)

A

A

D

D

B

B

C

C

Summary of Contents for GMV95 Series

Page 1: ...as provided in the Service Manual Refer to the appropriate Parts Catalog for part number information Copyright 2005 2007 Goodman Manufacturing Company L P RT6612012Rev 1 June2007 This manual is to be...

Page 2: ...his unit without such background may result in product damage personal injury or death WARNING WARNING Goodman will not be responsibile for any injury or property damage arising from improper service...

Page 3: ...vice that is not design certified by Goodman for use with this unit Serious property damage personal injury reduced unit performance and or hazardous conditions may result from the use of such non app...

Page 4: ...ic ignition device to light the burners and an induced draft blower to exhaust combustion products An interlock switch prevents furnace operation if the blower door is not in place Keep the blower acc...

Page 5: ...Electrical Connection Inlets Alternate 18 Coil Front Cover Pressure Tap 19 Coil Front Cover Drain Port 20 Drain Line Penetrations 21 Drain Trap 22 Blower Door Interlock Switch 23 Inductor NotAll Model...

Page 6: ...FLANGES AIR DISCHARGE AIR DISCHARGE Cabinet Size A B C D E 13 5 8 17 1 2 20 7 8 All dimensions are in inches 24 1 2 12 1 8 16 19 3 8 12 15 16 15 15 16 20 7 16 GMV950453BX GMV950904CX GMV950905DX GMV95...

Page 7: ...IRE LOW FIRE HIGH FIRE LOW FIRE HIGH FIRE LOW FIRE HIGH FIRE GMV950453BX GMV950704CX 0 10 0 10 20197308 0 30 0 75 11177113 PURPLE PINK 0 10 0 10 0 22 0 55 HAPS28 11177115 GREEN YELLOW GMV950905DX GMV9...

Page 8: ...GMV951155DX 2 ROLLOUT LIMIT SWITCHES Part Number 10123535 10123537 10123536 10123533 Open Setting F 150 140 180 200 GMV950453BX 2 GMV950704CX 2 GMV950905DX 2 GMV951155DX 2 AUXILIARY LIMIT SWITCHES Par...

Page 9: ...al slab only 6 R 22orR 410A 2 R 22 4 R 410A Refrigerant Revision A Revision Coil Matches Alarge array ofAmana brand coils are available for use with the GMV95 furnaces in either upflow or horizontal a...

Page 10: ...Permanent Minimum Filter Area in2 Based on 600 ft min filter face velocity Thermostat Man Auto Programmable Cool Heat Batt Powered Batt Bkup 1213406 Man Or Auto Yes 2 3 No No 1213407 Man Changeover Y...

Page 11: ...43 55 43 55 43 55 43 55 Number of Burners 2 3 4 5 Vent Connector Diameter inches 2 2 3 3 Combustion Air Connector Diameter inches 2 2 3 3 Shipping Weight lbs 133 133 172 184 Refer to airflow charts o...

Page 12: ...71 46 Plus 924 1331 46 Minus 540 778 52 Minus 828 1192 51 Normal 600 864 47 Normal 920 1325 46 Plus 660 950 43 Plus 1012 1457 42 Minus 585 842 48 Minus 900 1296 47 Normal 650 936 43 Normal 1000 1440 4...

Page 13: ...lus 880 Minus 720 Minus 720 Minus 990 Minus 990 Normal 800 Normal 800 Normal 1100 Normal 1100 Plus 880 Plus 880 Plus 1210 Plus 1210 Minus 900 Minus 990 Minus 1260 Minus 1260 Normal 1000 Normal 1100 No...

Page 14: ...oses only 6 Motor CFM minimum GMV95 Continuous Fan Speed Chart Cooling Speed Tap Adjust Tap CFM at 1 8 w c ESP Cooling Speed Tap Adjust Tap CFM at 1 8 w c ESP Minus 380 Minus 380 Normal 380 Normal 380...

Page 15: ...4 3 2 1 4 3 2 1 4 3 2 1 Ramping Profile Tap A Ramping Profile Tap B Ramping Profile Tap C Ramping Profile Tap D Ramping Profiles indicates factory setting 8 7 8 7 8 7 6 5 6 5 6 5 6 5 O N O F F O N O...

Page 16: ...30 140 150 100 90 80 70 60 50 40 30 20 10 OUTPUT BTU HR x 1000 BTU OUTPUT vs TEMPERATURE RISE CHART TEMPERATURE RISE 600 CFM 700 900 1000 1100 1200 1400 1600 1800 2000 2200 2400 CFM FORMULAS BTU OUTPU...

Page 17: ...L PROTECTIVE DEVICE OPEN SWITCH PRESS SWITCH TEMP FIELD SPLICE FIELD GND NO C FRONT COVER PRESSURE SWITCH MANUAL RESET ROLLOUT LIMIT CONTROLS SINGLE CONTROL ON 45 kBTU PK PINK PLUG CONNECTION BURNER C...

Page 18: ...CUT FOR 1 2 3 87 4321 87 4321 Intell Ignition TSTAT S4 S3 OFF ON S1 SINGLE TWO ON OFF YL PK VT HOUSING SIDES OF BLOWER AUXILIARY LIMITS PIN 1 PIN 2 BK WH GN GY OR BK WH PIN 6 SCROLL HOUSING GROUND TO...

Page 19: ...STAGE M P COM MV SWITCH ROLLOUT MVH W2 W2 HUM EAC NEU EAC AIR CLEANER ELECTRONIC INDUCER HUMN HUMIDIFIER W1 G Y R W1 G Y B C TR R TH 24 V A C XFMRN XFMR BLOWER CIRCULATOR HLI HLO PS1 PS2 MVL GND IGNN...

Reviews: