14
BLOWER PERFORMANCE SPECIFICATIONS
1. Units are shipped without filter(s). CFM in chart is without filter(s).
2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as
needed. The first task is to determine the proper aiflow for the cooling system.
3. For most cooling applications, about 400 CFM per ton is desirable.
4. The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on rating
plate.
5. Do not operate above 0.5" w.c. ESP in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling
purposes only.
6. * Motor CFM minimum.
GMV95 Continuous Fan Speed Chart
Cooling
Speed
Tap
Adjust
Tap
CFM at
.1" - .8"
w.c. ESP
Cooling
Speed
Tap
Adjust
Tap
CFM at
.1" - .8"
w.c. ESP
Minus(-)
380*
Minus(-)
380*
Normal
380*
Normal
380*
Plus (+)
380*
Plus (+)
380*
Minus(-)
403
Minus(-)
403
Normal
448
Normal
448
Plus (+)
493
Plus (+)
493
Minus(-)
504
Minus(-)
554
Normal
560
Normal
616
Plus (+)
616
Plus (+)
678
Minus(-)
505
Minus(-)
720
Normal
672
Normal
800
Plus (+)
739
Plus (+)
880
C
D
GMV950453BX*
A
B
D
GMV950704CX*
A
B
C
Cooling
Speed
Tap
Adjust
Tap
CFM at
.1" - .8"
w.c. ESP
Cooling
Speed
Tap
Adjust
Tap
CFM at
.1" - .8"
w.c. ESP
Minus(-)
513*
Minus(-)
514*
Normal
513*
Normal
514*
Plus (+)
513*
Plus (+)
514*
Minus(-)
554
Minus(-)
554
Normal
616
Normal
616
Plus (+)
678
Plus (+)
678
Minus(-)
706
Minus(-)
706
Normal
784
Normal
784
Plus (+)
862
Plus (+)
862
Minus(-)
907
Minus(-)
907
Normal
1008
Normal
1008
Plus (+)
1109
Plus (+)
1109
GMV951155DX*
GMV950905DX*
B
B
A
A
D
D
C
C