background image

15

2.

Upflow 

and 

Counterflow 

units

.

Loosen the worm gear hose clamps on the rubber elbow
and detach it from both the induced draft blower and the
vent/flue pipe.

3.

Upflow 

and 

Counterflow 

units

.

Remove the vent/flue pipe from the furnace.

4.

Cut the vent/flue pipe 3.75 inches from the flanged end of
the pipe. 

See Vent/Flue Pipe Cuts figure.

 The section of

pipe attached to the coupling will reach through the side
panel to the induced draft blower. Discard remaining pipe
and elbows.

Counterflow 

units.

Cut the vent/flue pipe 3.75 inches from the blower deck
coupling. 

See Vent/Flue Pipe Cuts figure.

 Save vent/flue pipe

attached to blower deck coupling for use in the alternate
location. Discard remaining pipe and elbows.

FLANGE

CUT

 

HERE

3.75"

5.

Remove plastic plug from alternate vent/flue location.
Relocate and install plug in standard vent/flue location (top
cover).

Counterflow

 units.

Remove plastic plug from alternate vent/flue location.
Relocate and install plug in standard vent/flue location
(basepan).  Plug remaining hole in blower deck with plastic
plug included in the drain kit bag.

6.

Upflow 

and 

Counterflow 

units

.

Insert cut section of vent/flue pipe and coupling into alternate
vent/flue location.  Using a rubber coupling and worm gear
hose clamps from the drain kit bag, attach the vent/flue pipe
and coupling to the induced draft blower.  Secure the
coupling to the cabinet using the screws removed in step 1
or with field-supplied 3/8”  #8 self drilling screws.

WARNING

T

HE RUBBER ELBOW IS NOT DESIGNED TO SUPPORAT A LOAD.  

W

HEN THE

RUBBER ELBOW IS MOUNTED EXTERNALLY TO THE FURNACE CABINET,

EXTREME CARE MUST BE TAKEN TO ADEQUATELY SUPPORT FIELD-SUPPLIED

VENT/FLUE PIPING, AS DAMAGE CAN RESULT IN LEAKS CAUSING BODILY

INJURY OR DEATH DUE TO EXPOSURE TO FLUE GASES, INCLUDING CARBON

MONOXIDE.

7.

Upflow 

and 

Counterflow 

units

.

For 

upright installations

, externally mount the rubber elbow

to the vent/flue coupling using a worm gear hose clamp.
Secure field supplied vent/flue piping to the rubber elbow
using a worm gear hose clamp.  

NOTE:

  Use of the alternate

vent/flue location for upright installations, requires the drain
trap be installed on the same side of the unit as the flue
pipe.

8.

Upflow 

and 

Counterflow 

units

.

For

 

horizontal installations

, externally secure the field-

supplied vent/flue pipe directly to the vent/flue coupling using
a PVC or ABS coupling or elbow.

5

ADDITIONAL PLUG

FROM DRAIN KIT

7

EXTERNALLY

 MOUNT

RUBBER ELBOW

6

SECURE TO

ID BLOWER WITH

RUBBER COUPLING

AND HOSE

CLAMPS

COUNTERFLOW/UPRIGHT

(UPFLOW SIMILAR)

        UPFLOW 

REMOVE

4 SCREWS

3

REMOVE

PIPE 

2

DETACH RUBBER

ELBOW FROM

 ID BLOWER AND 

VENT/FLUE

PIPE 

1. 

REMOVE

4 SCREWS

2

DETATCH RUBBER

ELBOW FROM

 ID BLOWER AND 

VENT/FLUE

PIPE 

    COUNTERFLOW

3

REMOVE

PIPE 

REMOVE

AND RELOCATE

5

REMOVE

AND RELOCATE

REMOVE

3 SCREWS

1

UPFLOW/HORIZONTAL

(COUNTERFLOW SIMILAR)

6

SECURE TO

ID BLOWER WITH

RUBBER COUPLING

AND HOSE

CLAMPS

6

SECURE TO

CABINET WITH

SCREWS

Alternate Vent/Flue Location

A

LTERNATE

  C

OMBUSTION

  A

IR

 I

NTAKE

  L

OCATION

The alternate combustion air intake location consists of a large,
unobstructed hole (alternate vent connection is aligned with the
Induced Draft Blower).  To use the alternate combustion air intake
location, refer to the following steps, and the “Alternate Combus-
tion Air Intake Location” figure.

NOTE:

  Counterflow unit instructions follow the upflow instructions.

1.

Remove and save the four screws securing the combustion
air intake coupling to the furnace’s top panel (upflow).

Counterflow 

units.

Remove and save the four screws securing the combustion
air intake coupling to the basepan.  Remove an additional
three screws securing the furnace’s internal combustion
air intake pipe to the blower deck.

2.

Remove the combustion air intake coupling and gasket from
the top panel.

Counterflow

 units.

Remove the combustion air intake pipe from the furnace
and cut the pipe at the basepan coupling.  Save the basepan
coupling and gasket from the blower deck coupling for use
in the alternate location.  Discard the remaining pipe.

3.

Remove plastic plug from alternate combustion air intake
location.  Relocate and install plug in standard air intake
location (top cover).

Summary of Contents for GMS95

Page 1: ...f in a position which is more hazardous than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer...

Page 2: ...ROPER VENT FLUE AND COMBUSTION AIR PIPING PRACTICES 13 TERMINATION LOCATIONS 13 CANADIAN VENTING REQUIREMENTS 14 STANDARD FURNACE CONNECTIONS 14 ALTERNATE FURNACE CONNECTIONS 14 NON DIRECT VENT SINGLE...

Page 3: ...afety Circuit Description 31 GENERAL 31 INTEGRATED CONTROL MODULE 31 PRIMARY LIMIT 31 AUXILIARY LIMIT 31 ROLLOUT LIMIT 31 PRESSURE SWITCHES 31 FLAME SENSOR 31 XVIII Troubleshooting 31 ELECTROSTATIC DI...

Page 4: ...warranty certificate is also supplied with the unit Read the warranty carefully and note what is covered Keep the warranty cer tificate in a safe location for future reference If additional informatio...

Page 5: ...lectrical Connection Inlets Alternate 19 Coil Front Cover Pressure Tap 20 Coil Front Cover Drain Port 21 Drain Line Penetrations 22 Drain Trap 23 Blower Door Interlock Switch 24 Capacitor 25 Integrate...

Page 6: ...are set per the furnace rating plate The input rate and temperature rise are set per the furnace rating plate 100 outside air is provided for combustion air requirements during construction Temporary...

Page 7: ...ly air opening and the combustible floor Exposure to contaminated combustion air will result in safety and performance related problems Do not install the furnace where the combustion air is exposed t...

Page 8: ...g system properly vents when tested as outlined above re turn doors windows exhaust fans fireplace dampers and any other gas burning appliance to their previous conditions of use halogen type refriger...

Page 9: ...input rating of all appliances installed in that space Rooms communicating directly with the space in which the appliances are installed through openings not furnished with doors are considered a par...

Page 10: ...nsion of rectangular air ducts shall not be less than 3 inches ing shall have a minimum free area of 1 square inch per 1 000 BTU per hour of the total input rating of all gas utilization equipment in...

Page 11: ...tallation Positions figure for appropriate in stallation positions ductwork connections and resulting airflow arrangements VII HO VII HO VII HO VII HO VII HORIZO RIZO RIZO RIZO RIZONT NT NT NT NTAL AP...

Page 12: ...ane gas installations require an orifice change to compensate for the energy content difference between natural and propane gas High altitude installations may require both a pressure switch and an or...

Page 13: ...nt flue pipe and a combustion air intake pipe Refer to the appropriate section for details concerning piping size length number of elbows furnace connections and terminations MATERIALS AND JOINING MET...

Page 14: ...DIRECT VENT INSTALLATIONS On upflow units secure the combustion air intake pipe directly to the air intake coupling On counterflow units secure the combus tion air intake pipe to the air intake coupl...

Page 15: ...ue piping to the rubber elbow using a worm gear hose clamp NOTE Use of the alternate vent flue location for upright installations requires the drain trap be installed on the same side of the unit as t...

Page 16: ...ould be in stalled on either side of the wall and solvent cemented to a length of pipe connecting the two couplings The length of pipe should be the wall thickness plus the depth of the socket fitting...

Page 17: ...s in each Vent Flue Combustion Air Intake pipe Elbows and or tees used in the terminations must be included when determining the number of elbows in the piping systems If the combustion air intake pip...

Page 18: ...es If the pipes must go below the joist and then up into the last joist space to penetrate the header two 45 elbows should be used to reach the header rather than two 90 elbows VENT INTAKE TERMINATION...

Page 19: ...t installations using the standard vent flue outlet require drain hoses to be connected as follows The following quantity of hoses tubes and hose clamps are provided with the unit HOSE A QTY 1 HOSE B...

Page 20: ...flow models relocation of the front cover pressure switch hose is required Make connections as follows 1 Remove the rubber plug from the coil front cover drain port Counterflow furnaces Relocate the f...

Page 21: ...is an integral part of this furnace Field alter ation to comply with electrical codes should not be required Wires are color coded for identification purposes Refer to the wiring diagram for wire rout...

Page 22: ...at 120 VAC Turn OFF power to the furnace before installing any accessories Follow the humidifier or air cleaner manufacturers instructions for locating mounting grounding and controlling these access...

Page 23: ...field convertible for use with propane gas by replacing the regulator spring with a propane gas spring from an appropriate manufacturer s propane gas conversion kit Taps for measuring the gas supply p...

Page 24: ...rotect against external corrosion when in contact with masonry plaster or insulation or subjected to repeated wetting by liquids such as water except rain water detergents or sewage MANUAL SHUT OFF VA...

Page 25: ...nace manifold with all gas appliances in operation Maintaining proper gas pressure depends on three main factors 1 Vaporization rate depending on temperature of the liquid and wetted surface area of t...

Page 26: ...the dampers or other means used to control the flow of air must be adequate to prevent chilled air from entering the furnace and if manually operated must be equipped with means to prevent operation...

Page 27: ...nace is equipped with an ignition device which automatically lights the burner Do not try to light the burner by hand 5 Move the furnace gas valve manual control to the OFF position 6 Wait five minute...

Page 28: ...soap suds check for leaks at hose connection Bubbles forming indicate a leak SHUTOFF GASAND FIXALLLEAKS IMMEDIATELY BEFORE PROCEEDING TO NEXT STEP 6 Measure furnace gas supply pressure Supply pressure...

Page 29: ...uals the installation s gas heating value multiplied with a conversion factor hours to seconds divided by the number of seconds per cubic foot The measured input must not be greater than the input ind...

Page 30: ...sensed Circulator blower is energized on heat speed following a fixed thirty second blower on delay Electronic air cleaner terminals are energized with circulator blower Furnace runs integrated contro...

Page 31: ...DISCHARGE ESD PRECAUTIONS NOTE Discharge body s static electricity before touching unit An electrostatic discharge can adversely affect electrical components Use the following precautions during furna...

Page 32: ...e filter s by reversing the procedure for removal 4 Turn ON electrical power to furnace MEDIA AIR FILTER OR ELECTRONIC AIR CLEANER REMOVAL Follow the manufacturer s directions for service BURNERS Visu...

Page 33: ...he blower until filter clears bottom rail 5 Lower filter down and pull outward Front of Furnace Blower Front of Furnace Blower 6 Replace filter by reversing procedure X X X X XXI BEFO XI BEFO XI BEFO...

Page 34: ...34...

Page 35: ...kage proper length elbows and termination Check drain system Correct as necessary Correct pressure switch setpoint or contact motion Tighten or correct wiring connection Pressure switch hose blocked p...

Page 36: ...e sensor with emery clot See Vent Flue Pipe section for piping details See rating plate for proper gas pressure 7 7 FLASHES Flame sensor is coated oxidized Flame sensor incorrectly positioned in burne...

Page 37: ...OSTAT CONNECTIONS BU GN GND 115 VAC 24 VAC BLOWER COMPARTMENT DOOR SWITCH OPEN WHEN DOOR OPEN DOOR SWITCH WARNING DISCONNECT POWERBEFORE SERVICING WIRING TOUNITMUST BE PROPERLYPOLARIZED AND GROUNDED B...

Reviews: