Airflow Data — GCEC960403BN

Notes

• 

All furnaces ship as high speed for cooling.  Installer must adjust blower speed as needed.

• 

For most jobs, about 400 CFM per ton when cooling is desirable.

• 

INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.

COOLING

Dipswitch Setting:

S1-1  S1-2  S1-3

Static

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

Tstat Call

CFM

CFM

CFM

CFM

CFM

CFM

CFM

CFM

**OFF OFF OFF

Ylo

647

576

511

449

387

335

280

252

1229

1181

1150

1117

1078

1035

1002

964

ON OFF OFF

Ylo

1137

1096

1056

1018

981

940

897

859

647

576

511

449

387

335

280

252

ON ON OFF

Ylo

1137

1096

1056

1018

981

940

897

859

1229

1181

1150

1117

1078

1035

1002

964

OFF ON OFF^

Ylo

647

576

511

449

387

335

280

252

743

688

628

572

515

459

408

364

OFF OFF ON^

Ylo

647

576

511

449

387

335

280

252

939

894

846

806

759

706

661

614

OFF ON ON

Ylo

1137

1096

1056

1018

981

940

897

859

743

688

628

572

515

459

408

364

ON OFF ON

Ylo

939

894

846

806

759

706

661

614

1229

1181

1150

1117

1078

1035

1002

964

ON ON ON^ 

Ylo

939

894

846

806

759

706

661

614

1137

1096

1056

1018

981

940

897

859

CONTINUOUS FAN

Dipswitch Setting:

S2-2  S2-3  S2-4

Static

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

Tstat Call

CFM

CFM

CFM

CFM

CFM

CFM

CFM

CFM

**OFF  OFF  OFF

G

743

688

628

572

515

459

408

364

ON  OFF  OFF

G

939

894

846

806

759

706

661

614

ON  ON  OFF

G

1137

1096

1056

1018

981

940

897

859

OFF  ON OFF

G

647

576

511

449

387

335

280

252

OFF  OFF  ON

G

1229

1181

1150

1117

1078

1035

1002

964

OFF  ON  ON

G

743

688

628

572

515

459

408

364

ON  OFF  ON

G

743

688

628

572

515

459

408

364

ON  ON  ON 

G

743

688

628

572

515

459

408

364

HEATING

Dipswitch Setting:

S1-4   S2-1

Static

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

CFM

CFM

CFM

**OFF OFF

W1

743

33

688

36

628

40

572

44

515

48

459

408

364

W2

939

38

894

40

846

42

806

44

759

47

706

661

614

ON OFF

W1

1137

NA

1096

NA

1056

NA

1018

NA

981

N/A

940

897

859

W2

939

38

894

40

846

42

806

44

759

47

706

661

614

ON ON

W1

1137

NA

1096

NA

1056

NA

1018

NA

981

N/A

940

897

859

W2

647

55

576

NA

511

NA

449

NA

387

NA

NA

NA

NA

OFF ON

W1

647

38

576

43

511

49

449

55

387

64

335

280

252

W2

1229

29

1181

30

1150

31

1117

32

1078

33

1035

1002

964

**  Factory Default

SINGLE STAGE COOLING^

*NOT RECOMMENDED

Summary of Contents for GCEC96

Page 1: ...down flow horizontal left or right Certified for direct vent 2 pipe or non direct vent 1 pipe Easy to install top venting with optional side venting Convenient left or right connection for gas and ele...

Page 2: ...ontrol Configuration NOx M Upflow Horizontal N Low NOx C Downflow Horizontal Cabinet Width Motor B 17 C 21 V Variable Speed ECM ComfortNet D 24 E Multi Speed ECM S Single Speed Maximum CFM 2 800 CFM 4...

Page 3: ...ipes The optional Combustion Air Pipe is dependent on installation code requirements and must be 2 or 3 diameter PVC Minimum Circuit Ampacity 1 25 x Circulator Blower Amps ID Blower amps Wire size sho...

Page 4: ...ernate Gas High Voltage Electrical Outlet Standard Drain Trap Drain Trap Holes Alternate Gas Supply Alternate Vent High Voltage Electrical Outlet Right Side Exterior Drain Trap Holes Low Voltage Elect...

Page 5: ...78 1035 1002 964 ON ON ON Ylo 939 894 846 806 759 706 661 614 Y 1137 1096 1056 1018 981 940 897 859 CONTINUOUS FAN Dipswitch Setting S2 2 S2 3 S2 4 Static 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Tstat Call CF...

Page 6: ...969 928 ON ON ON Ylo 1328 1287 1249 1215 1170 1131 1085 1046 Y 782 629 547 469 396 333 N A N A CONTINUOUS FAN Dipswitch Setting S2 2 S2 3 S2 4 Static 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Tstat Call CFM CF...

Page 7: ...Ylo 1311 1293 1249 1203 1172 1122 1088 1041 Y 750 644 569 507 442 388 328 N A CONTINUOUS FAN Dipswitch Setting S2 2 S2 3 S2 4 Static 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Tstat Call CFM CFM CFM CFM CFM CFM...

Page 8: ...73 ON ON ON Ylo 1866 1817 1774 1729 1684 1637 1593 1552 Y 1477 1422 1364 1301 1244 1190 1135 1078 CONTINUOUS FAN Dipswitch Setting S2 2 S2 3 S2 4 Static 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Tstat Call CFM...

Page 9: ...BTU HR x 1000 BTU OUTPUT vs TEMPERATURE RISE CHART TEMPERATURE RISE 600 CFM 700 900 1000 1100 1200 1400 1600 1800 2000 2200 2400 CFM FORMULAS BTU OUTPUT CFM x 1 08 x RISE RISE BTU OUTPUT 1 08 CFM 800...

Page 10: ...GND INTERNAL TO SWITCH PRESSURE HIGH FIRE PROT DEVICE INTEGRATED CONTROL PK PU PLUG CONNECTION L N BK C DOOR OPEN OPEN WHEN DOOR SWITCH COMPARTMENT BLOWER SWITCH TEMP GND 1 BLOWER CIRCULATOR JUNCTION...

Page 11: ...5 CFSB21 Downflow Sub Base 21 RF000142 Drain Kit Horizontal Left Vertical Flue 0170K00000S Flush Mount Vent Kit 3 or 2 0170K00001S Flush Mount Vent Kit 2 AFE18 60A Fossil Fuel Dual Fuel Kit HASFK Hig...

Page 12: ...EC96 Goodman Manufacturing Company L P reserves the right to discontinue or change at any time specifications or designs without notice or without incurring obligations 2021 Goodman Manufacturing Comp...

Reviews: