background image

19

5.  The difference between the thermometer reading and 

pressure to temperature conversion is the amount of 

subcooling.

Subcooling Formula = Sat. Liquid Temp. - Liquid Line 

Temp.
EXAMPLE:

a. Liquid Line Pressure = 417
b. Corresponding Temp. °F. = 120°
c. Thermometer on Liquid line = 109°F.
To obtain the amount of subcooling, subtract 109°F from 

120°F.

The difference is 11° subcooling. See the specification 

sheet or technical information manual for the design 

subcooling range for your unit.
See R410A Pressure vs. Temperature chart.
Compressor Protection Devices
The compressor includes components which are designed 

to protect the compressor against abnormal operating 

conditions.
Refrigerant Charge Check (Units with Fixed Orifice 

Devices)
After completing airflow measurements and adjustments 

the unit’s refrigerant charge must be checked. The unit 

comes factory charged, but this charge is based on 325 

CFM per ton and minimum ESP per AHRI test conditions 

(generally between .15 -.28 ESP). When air quantity or 

ESP is different than above, the refrigerant charge must be 

adjusted to the proper amount. All package units with fixed 

orifice devices are charged using the super heat method at 

the compressor suction line.
After superheat is adjusted it is recommended to check unit 

sub-cooling at the condenser coil liquid line out. For charge 

adjustments, see superheat and subcooling charts shown 

for each model.

MAINTENANCE

Have the gas heating section of the unit checked at least 

once a year before the heating season begins, to be sure 

that the combustion air inlet and flue outlet hoods are 

not blocked by debris, which would prevent adequate 

combustion air and a properly operating vent system.

Filter Replacement or Cleaning 

A return air filter is not supplied with this unit; however, 

there must be a means of filtering all of the return air. The 

filter(s) may be located in the return air duct(s), or return 

air filter grille(s). Consult with your installing dealer for the 

actual location of the return air filter(s) for your unit.

Dirty filters are the most common cause of inadequate 

heating or cooling performance. Filter inspection should be 

made at least every two months; more often if necessary 

because of local conditions and usage.
Dirty throwaway filters should be discarded and replaced 

with a new, clean filter. Dirty permanent filters should be 

washed with water, thoroughly dried and sprayed with a 

filter adhesive before being reinstalled. (Filter adhesives 

may be found at many hardware stores.) Permanent filters 

should last several years. However, should one become 

torn or uncleanable, it should be replaced.

Cabinet Finish Maintenance

Use a fine grade automotive wax on the cabinet finish to 

maintain the finish’s original high luster. This is especially 

important in installations with extended periods of direct 

sunlight.

Clean Outside Coil  (Qualified Servicer Only)

The coil with the outside air flowing over it should be 

inspected annually and cleaned as frequently as necessary 

to keep the finned areas free of lint, hair and debris.

Condenser, Evaporator, and  Induced Draft Motors 

Bearings on the air circulating blower motor, condenser 

motor and the combustion fan motor are permanently 

lubricated. No additional oiling is required.

Flame Sensor (Qualified Servicer Only)

A drop in the flame current can be caused by a nearly 

invisible coating on the flame sensor. This coating, created 

by the fuel or combustion air supply, can be removed by 

carefully cleaning the flame sensor with steel wool.

NOTE:

 After cleaning, the microamp signal should be 

stable and in the range of 4 - 6 microamps DC.

Flame

Sensor

Flame Sensor

Flue Passages (Qualified Servicer Only)

At the start of each heating season, inspect and, if 

necessary, clean the unit flue passage.

1.  Shut off electric power and gas supply to the unit. 
2.  Remove burner assembly by disconnecting the gas 

line and removing the manifold bracket from the 

partition panel.

Summary of Contents for APD 14 M Series

Page 1: ...l the product safely and to educate the customer on its safe use Goodman Manufacturing Company L P 19001 Kermier Rd Waller TX 77484 www goodmanmfg com or www amana hac com 2011 2018 2021 Goodman Manuf...

Page 2: ...23 Heating Timing Chart 23 Cooling heat pump Timing Chart 23 Unit Dimensions 24 WIRING DIAGRAM 25 Minimum Clearances 27 Recommended Filter Sizes 27 Blower Performance Data 29 START UP CHECKLIST 30 TO...

Page 3: ...amage personal injury or loss of life AVERTISSEMENT RISQUE D INCENDIE OU D EXPLOSION Si les consignes de s curit ne sont pas suivies la lettre cela peut entra ner la mort de graves blessures ou des do...

Page 4: ...moyen des essais d crits ci dessus les portes les fen tres les ventilateurs les registres de foyer et tous les autres appareils de combustion aliment s au gaz doivent tre remis dans leur tat initial l...

Page 5: ...IER ROAD Houston Texas 77484 877 254 4729 GENERAL INFORMATION This unit is approved for outdoor installation ONLY To assure that your unit operates safely and efficiently it must be installed operated...

Page 6: ...al fresh air damper motorized fresh air damper to become blocked by snow or debris In some climates or locations it may be necessary to elevate the unit to avoid these problems Damper must be in open...

Page 7: ...gas and gas input rating Make sure the unit is equipped to operate on the type of gas available Conversion to LP gas is permitted with the use of the factory authorized conversion kit LPM 08 Natural...

Page 8: ...long 5 Use two pipe wrenches when making connection to the gas valve to keep it from turning 6 Install a manual shut off valve in a convenient location within six feet of unit between the meter and t...

Page 9: ...e based on 1 PSIG Pressure Drop at 10 PSIG Setting Capacities in 1 000 BTU HR 3 8 1 2 5 8 3 4 7 8 1 2 3 4 30 309 700 1 303 2 205 3 394 1 843 3 854 40 265 599 1 115 1 887 2 904 1 577 3 298 50 235 531 9...

Page 10: ...Exercise caution when servicing as only one leg of the power supply is broken with the contractor High Voltage Wiring Rated Voltage Minimum Supply Voltage Maximum Supply Voltage 208 230V 197 253 The u...

Page 11: ...ming the installation In some installations it will be necessary to change the blower speed to provide proper air flow Horizontal Air Flow Single phase models are shipped without horizontal duct cover...

Page 12: ...FLUE HOOD LIP Installation Combustion Air Intake Hood 1 Locate the second hood 2 Using the three screws provided attach the hood with the opening facing down to the heat exchanger access door CONDENSA...

Page 13: ...it delivers heat to the conditioned space until the thermostat is satisfied 8 Gas valve s de energizes The induced draft blower continues operation for a 30 second post purge NOTE Induced draft blower...

Page 14: ...ing etc In general 400 CFM per ton of cooling capacity is a rule of thumb Some applications depending on the sensible and latent capacity requirements may need only 350 CFM or up to 425 CFM per ton Ch...

Page 15: ...supply to the unit 12 Set the thermostat to desired setting On Off Switch Inlet PressureBoss High Fire Coil Terminal HI LowFire Regulator Adjust Manometer Manometer Hose A HighFire Regulator Adjust R...

Page 16: ...0 W C High Stage 9 7 10 3 W C 10 0 W C Manifold Gas Pressure Gas BTU Input Natural Gas Only Check To measure the gas input use a gas meter and proceed as follows 1 Turn off gas supply to all other ap...

Page 17: ...ING SPEED TAPS ON THE BLOWER MOTOR Refer to the wiring diagram and airflow data in the appendix to verify speed tap settings Depending upon the model blower speeds are changed at the indoor blower The...

Page 18: ...column Follow that line right to the column under the design subcooling value Where the two intersect is the required liquid line temperature Alternately you can convert the liquid line pressure gauge...

Page 19: ...d in the return air duct s or return air filter grille s Consult with your installing dealer for the actual location of the return air filter s for your unit Dirty filters are the most common cause of...

Page 20: ...off Burner Flame At least once a year prior to or during the heating season make a visual check of the burner flames NOTE This will involve removing and reinstalling the heat exchanger door on the un...

Page 21: ...RESSURE SWITCH 3 FLASHES 2 FLASHES 4 FLASHES 5 FLASHES FALSE FLAME DETECTED OPEN LIMIT SWITCH WITHOUT INDUCER ON PRESSURE SWITCH OPEN CHECK FOR SHORTS IN FLAME SENSOR WIRING NORMAL FLAME PRESENT DIAGN...

Page 22: ...3 Flashes Pressure Switch Stuck Closed 4 Flashes Thermal Protection Device Open 5 Flashes Flame Detected with Gas Valve Closed 6 Flashes Short Cycle Compressor Delay Cooling Only 7 Flashes Limit Open...

Page 23: ...23 UNIT DIMENSIONS...

Page 24: ...CER L2 PARK 24VAC COM 5 4 3 2 1 1 2 3 5 6 7 8 9 EM N G L T5 T4 T3 T2 T1 C 1 2 6 4 1 FS LS M C H1 RS VM ALS PS GV IGN H C F LO HEAT 6 3 1 2 4 5 OR BL PU YL OR BR OR P1 PIN 3 P1 PIN 5 P1 PIN 9 P1 PIN 2...

Page 25: ...ED AS AN ALTERNATE CONFIGURATION LINE VOLTAGE OPTIONAL HIGH VOLTAGE HIGH VOLTAGE FIELD WIRING LOW VOLTAGE LOW VOLTAGE BK BLACK WIRE CODE PK PINK OR ORANGE GR GREEN BR BROWN BL BLUE RD RED WH WHITE YL...

Page 26: ...1 1 20 x 25 x 1 1 25 x 25 x1 2 20 x 20 x 1 Clearance in accordance with local installation codes the requirements of the gas supplier and the manufacturer s instal lation instructions D gaugement conf...

Page 27: ...08 144 1023 149 1285 242 0 3 922 165 49 1206 289 50 956 151 976 157 1237 250 0 4 886 173 51 1164 302 52 908 158 928 164 1189 257 0 5 835 182 54 1131 314 53 857 166 880 172 1141 265 0 6 781 188 58 1086...

Page 28: ...9 137 49 1260 213 55 1317 230 1317 230 1453 269 0 2 1008 144 52 1212 221 57 1269 237 1269 237 1405 277 0 3 956 151 54 1165 229 59 1221 245 1221 245 1357 284 0 4 908 158 57 1117 236 62 1174 253 1174 25...

Page 29: ...0 1275 347 59 974 204 1261 338 1612 450 0 5 871 204 65 1224 357 61 910 212 1211 343 1563 458 0 6 811 213 X 1172 364 64 847 220 1168 356 1514 466 0 7 753 210 X 1130 379 X 784 227 1111 373 1466 474 0 8...

Page 30: ...LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Circuit Pressure Suct...

Page 31: ...31 THIS PAGE IS INTENTIONALLY LEFT BLANK...

Page 32: ...trademark of Maytag Corporation or its related companies and is used under license All rights reserved NOTE SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN ARE SUBJECT TO CHANGE WITHOUT NOTICE Quali...

Reviews: