17
Temperature Rise Check
NOTE:
Air temperature rise is the temperature difference
between supply and return air.
With a properly designed system, the proper amount of
temperature rise will normally be obtained when the unit
is operated at rated input with the recommended blower
speed.
If the correct amount of temperature rise is not obtained, it
may be necessary to change the blower speed. A higher
blower speed will lower the temperature rise. A slower
blower speed will increase the temperature rise.
NOTE:
Blower speed MUST be set to give the correct air
temperature rise through the unit as marked on the rating
plate.
External Static Pressure Check
The total external static pressure must be checked on this
unit to determine if the airflow is proper.
1. Using a digital manometer measure the static pressure
of the return duct at the inlet of the unit, (Negative
Pressure).
Total External Static
2. Measure the Static pressure of the supply duct,
(Positive Pressure).
3. Add the two readings togther.
NOTE:
Both readings may be taken simultaneously
and read directly on the manometer if so desired.
4. Consult proper table for quantitu of air.
If the external static pressure exceeds the minimum or
maximum allowable statics, check for closed dampers, dirty
filters, undersizd or poorly laid out ductwork.
Blower Speed Adjustments
WARNING
T
O AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK, REMOVE
ELECTRICAL POWER FROM THE UNIT
B
EFORE CHANGING SPEED TAPS ON THE
B
LOWER MOTOR.
Refer to the wiring diagram and airflow data in the appendix
to verify speed tap settings.
Depending upon the model, blower speeds are changed
at the indoor blower. The ignition control board has four
blower speeds: LOW HEAT, HI HEAT, LOW COOL and
HIGH COOL.
NOTE:
FAN ONLY energizes at LOW HEAT speed.
The *PD14 models are equipped with EEM motors. EEM
motors are constant torque motors with very low power
consumption. This motor is energized by 24VAC. Adjust
the CFM for the unit by changing the 24VAC leads to the
speed terminal block on the motor.
NOTE: Heating airflow must be adjusted to provide the
temperature rise shown on rating plate. A higher speed
tap may not provide more airflow. Blower speeds are
programmed to deliver adequate airflow at rated external
static pressure (ESP). Refer to airflow table provided in the
Appendix for details.
Lead
Color
Speed
Tap
Definition
Lead
Color
Speed
Tap
Definition
White
T1
Low
Speed Heat
T3
Cool/HP
Optional Low
Speed
Brown
T2
High
Speed Heat
Yellow
T4
Cool/HP
Speed
T5
High Static
GAS HEATING
COOLING
Limit Check
Check limit control operation after 15 minutes of operation
by blocking the return air grille(s).
1. After several minutes the main burners must go OFF.
Blower will continue to run.
2. Remove air restrictions and main burners will relight
after a cool down period of a few minutes.
Adjust the thermostat setting below room temperature.
1. Main burners must go OFF.
2. Circulating Air Blower will continue to run for 90, 120,
150 or 180 seconds, depending on the setting.
NOTE:
If necessary, adjust fan OFF delay settings to obtain
satisfactory comfort level.
Summary of Contents for APD 14 M Series
Page 23: ...23 UNIT DIMENSIONS...