Installation
10
WARNING
This appliance must be installed by a qualified gas fitter or plumber and in accordance with
AS5601 & AS/NZS5601.
5.4 Gas Connection
This appliance has been tested and pre-set before leaving the factory, however minor adjustments
may be necessary to suit the gas supply pressure. Correct operation of the appliance must be tested
as part of the installation procedure.
Note: Gas fitting must only be carried out by an authorised and qualified person.
1.
Have a licensed gas fitter or your gas supply company
connect & check that the gas supply line pressure and
volume are adequate for the appliance being installed.
The required pressure and input rating is shown on the
rating plate behind the door.
2.
Install the appliance in accordance with AS5601 &
AS/NZS5601. Ensure that the appliance gas type
corresponds with the gas supply. Different gas types
are NOT compatible; however, the appliance can be converted from one gas type to
another. Please see conversion instructions for more details and contact the dealer for any
necessary components.
3.
Fit an individual manual isolating valve to the appliance gas supply.
4.
Connect the appliance to the gas supply. Location of the connection is shown in Dimensions
section 3 and is at the rear of the appliance wit
h a ¾” B.S.P male fittin
g.
5.
Ensure all gas connections are tight and free of leaks using appropriate gas detecting
equipment.
6.
Bleed out any air in the lines.
7.
Fill the tank and then measure the appliance
operating pressure at the manifold test point
with the appliance running. If required, adjust
the pressure at the gas valve to the value shown
in Specifications section 3.3- Gas Supply
Requirements.
8.
Although the pilot is set in the factory, check that
the pilot flame does not interrupt the main burner and ensure it
lights quickly. Final adjustments can be made through the pilot
adjustment hole.
Rating Plate
Img 1
Manifold
Pressure
Test Point
Pilot Adjustment
Gas Pressure
Adjustment
WARNING
Never use an open flame to detect gas leaks and ensure the tank is filled before operating
Pilot Adjustment
Gas Pressure
Adjustment
Alternative gas control valve