D5036 

- SIL 2 Switch/Proximity Detector Repeater, Relay Output 

G.M. International ISM0269-3 

ON 

D5036D 

A configuration DIP switch is located on component side of pcb. This switch allows the configuration of input/output relationship, fault detection functions and operating mode.

 

 

Configuration 

Dip switch configuration 

Input Input 

Output 

Input 

Output 

Input 

2

CH1 

Setting 

Line fault 
detection 

IN / OUT 

Operation 

NO-NE or 

NC-ND 

NO-ND or 

NC-NE 

ON 

Disabled 

(switch / proximity sensor) 

Enabled 

(proximity sensor or switch 

with end of line resistors, 

de-energizes relay in fault condition) 

 

2

OFF 

NO 

OR 

NC 

 

NO 

OR 

NC 

1

OFF 

1

ON 

 

 

NE 

ND 

Output 

ND 

Output 

NE 

Position in fault condition 

Input Input 

Output 

Input 

Output 

Input 

CH2 

Setting 

Line fault 
detection 

IN / OUT 

Operation 

NO-NE or 

NC-ND 

NO-ND or 

NC-NE 

Disabled 

(switch / proximity sensor) 

Enabled 

(proximity sensor or switch 

with end of line resistors, 

de-energizes relay in fault condition) 

 

NO 

10 

OR 

NC 

10 

 

NO 

10 

OR 

NC 

10 

NE 

ND 

Output 

ND 

Output 

NE 

3

3

ON 

OFF 

4

4

ON 

OFF 

Position in fault condition 

1

2

3

4

ON

Dip switch factory settings. All Switches are OFF 

1

2

3

4

ON

CH1

 

CH2

 

For SIL Application 

For SIL Application 

For SIL Application 

For SIL Application 

Summary of Contents for D5036D

Page 1: ...SIL 2 Switch Proximity Detector Repeater Relay Output G M International ISM0269 3 SIL 2 Switch Proximity Detector Repeater Relay Output DIN Rail Models D5036S D5036D D5036S D5036D INSTRUCTION SAFETY M...

Page 2: ...SPDT D5036S relay contact Contact material Ag Alloy Cd free gold plated Contact rating 4 A 250 Vac 1000 VA 4 A 250 Vdc 120 W resistive load Min switching current 1 mA DC Load breaking capacity Mechan...

Page 3: ...P Switch ATEX IECEx UL C UL EAC EX UKR TR n 898 T V Certifications T V Functional Safety Certification High Density two channels per unit Simplified installation using standard DIN Rail and plug in te...

Page 4: ...the effective group See parameters indicated in the table below D5036 Terminals Ch1 Ch2 7 8 9 10 Ch1 Ch2 7 8 9 10 Io Isc 22 mA Ch1 Ch2 7 8 9 10 Po Po 56 mW Ii Imax Pi Pi D5036 Terminals D5036 Associat...

Page 5: ...MODEL D5036D 5 6 1 2 Out 1 SIL 2 10 In 1 Proximity voltage free Contact 7 8 Power and Fault Bus F Supply 24 Vdc 3 4 Out 2 SIL 2 In 2 Proximity voltage free Contact 9 voltage free Contact voltage free...

Page 6: ...OFF OFF ON ON Description For this application enable input line fault open or short detection and direct input to output transfer function by set the internal dip switches in the following mode see...

Page 7: ...ation D5036S Ch 1 OFF operation ON operation Field Input proximity is OFF or switch is open Out relay is de energized out contact is open Channel 1 D5036S Ch 1 Field Input proximity is ON or switch is...

Page 8: ...2 at terminals 3 and 4 For Model D5036S in case of Proximity or Voltage free Contact connect the wires at terminal 7 for positive and 8 for negative For Model D5036D in addition to channel 1 connecti...

Page 9: ...e resistors de energizes relay in fault condition 7 2 OFF NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 1 OFF 1 ON NE 1 2 1 ND 2 Output 1 ND 2 Output NE 1 2 Position in fault condition 1 2 Input Input Output Input...

Page 10: ...annel 1 2 SW4 ON OFF D5036D Configuration Summary Table D5036S A configuration DIP switch is located on component side of pcb This switch allows the configuration of input output relationship fault de...

Reviews: