D5036 

- SIL 2 Switch/Proximity Detector Repeater, Relay Output 

G.M. International ISM0269-3 

Functional Safety Manual and Application 

Application for D5036D

 

PFDavg vs T[Proof] table 

(assuming Proof Test coverage of 99%), with determination of SIL supposing module contributes 

10% of total SIF dangerous failures:       

Failure rates table according to IEC 61508:2010 Ed.2 :  

Failure rate table:

 

Safety Function and Failure behavior:

  

D5036D is considered to be operating in Low Demand mode, as a Type A module, having Hardware Fault Tolerance (HFT) = 0. 
The failure behavior is described from the following definitions : 
 

 Fail-Safe State: it is defined as the relay output being de-energized (so that the NO contact is open); 

 

 Fail Safe: failure mode that causes the module / (sub)system to go to the defined Fail-Safe state without a demand from the process; 

 

 Fail Dangerous: failure mode that does not respond to a demand from the process (i.e. being unable to go to the defined Fail-Safe state), so that the relay output remains  

     energized (the NO contact is blocked in closed position); 
 

 Fail “No Effect”: failure mode of a component that plays a part in implementing the Safety Function but that is neither a safe failure nor a dangerous failure.  

     When calculating the SFF, this failure mode is not taken into account; 
 

 Fail “Not part”: failure mode of a component that is not part of the Safety Function but that is part of the circuit diagram and is listed for completeness.  

     When calculating the SFF, this failure mode is not taken into account. 
The 2 channels of D5036D module must not be used to increase the hardware fault tolerance, needed for a higher SIL of a certain Safety Function, as they are not completely  
independent each other, containing common components.  
Failure rate date: taken from Siemens Standard SN29500. 

Input signal state 

Pins 7-8 (In 1 - Ch.1) or 9-10 (In 2 - Ch.2) 

Output relay contact state 

Pins 1-2 (Out 1 - Ch.1) or 3-4 (Out 2 - Ch.2) 

Proximity sensor is OFF or switch is open 

Open (De-energize relay) 

Proximity sensor is ON or switch is closed 

Closed (Energized relay) 

Independently from proximity sensor or switch state, the input line is break 

Open (De-energized relay as safe state condition) 

Independently from proximity sensor or switch state, the input line is in short circuit  Open (De-energized relay as safe state condition) 

Channel status 
yellow LED state 

OFF 

ON 

OFF 

OFF 

Channel fault 

red LED state 

OFF 

OFF 

ON 

ON 

Description:

 For this application, enable input line fault (open or short) detection and direct input to output transfer function, by set the internal dip-switches in the following mode (see 

page 9 for more information): 

D5036D 

(Ch.1 and Ch.2) 

OFF operation 

ON operation 

Field Input: proximity is OFF 

or switch is open 

Field Input: proximity is OFF 

or switch is open 

Out 1 relay is de-energized, 

out contact is open 

Out 2 relay is de-energized, 

out contact is open 

Channel 1 

Channel 2 

D5036D 

(Ch.1 and Ch.2) 

Field Input: proximity is ON 

or switch is closed 

Field Input: proximity is ON 

or switch is closed 

Out 1 relay is energized, 

out contact is closed 

Out 2 relay is energized, 

out contact is closed 

Channel 1 

Channel 2 

 

Out 1 

 

Out 2 

 

Out 2 

Safety 

PLC 

Input 

 

Out 1 

Safety 

PLC 

Input 

Safety 

PLC 

Input 

Safety 

PLC 

Input 

  The module is powered by connecting 24 Vdc power supply to Pins 5 (+ positive) - 6 (- negative). The green LED is lit in presence of supply power. 

Input signals from field are applied to Pins 7-8 (In 1 - Ch.1) and Pins 9-10 (In 2 - Ch.2). 
Relay contact outputs Pins 1-2 (for Channel 1) and Pins 3-4 (for Channel 2) are both normally open (or relay de-energized as safe state condition) for OFF operation, 
while they are both closed (or relay energized) for ON operation. 
The following table describes for each channel the state (open or closed) of its output when its input signal is in OFF or ON state, and it gives information about turn-on or turn-off 
of the related channel status LED and channel fault LED: 

Dip-switch position 

1 2 3 4 

ON/OFF state 

ON OFF ON OFF 

 

Supply  
24 Vdc 

5 + 

6 - 

8

 

 

In 1 

 

10 

 

 

In 2 

 

 

Supply  
24 Vdc 

5 + 

6 - 

8

 

 

In 1 

 

10 

 

 

In 2 

 

Systematic capability SIL 3.

 

Failure category

 

Failure rates (FIT)

 

λ

dd

 = Total Dangerous Detected failures 

0.00 

λ

du

 = Total Dangerous Undetected failures 

51.22 

λ

sd

 = Total Safe Detected failures 

0.00 

λ

su

 = Total Safe Undetected failures 

130.16 

λ

tot safe

 = Total Failure Rate (Safety Function) = 

λ

dd

 + 

λ

du

 + 

λ

sd

 + 

λ

su

 181.38

 

MTBF (safety function, one channel) = (1 / 

λ

tot safe

) + MTTR (8 hours) 

629 years

 

λ

no effect

 = “No Effect” failures 

138.62 

λ

not part

 = “Not Part” failures 

200.20 

λ

tot device

 = Total Failure Rate (Device) = 

λ

tot safe

 + 

λ

no effect

 + 

λ

not part

  

520.20

 

MTBF (device, one channel) = (1 / 

λ

tot device

) + MTTR (8 hours) 

219 years

 

λ

sd

 

λ

su

 

λ

dd

 

λ

du

 

SFF

 

0.00 FIT 

130.16 FIT 

0.00 FIT 

51.22 FIT 

71.76% 

T[Proof] = 20 years

 

PFDavg = 4.50 E-03 Valid for 

SIL 2

 

T[Proof] = 1 year

 

T[Proof] = 4 years

 

PFDavg = 2.25 E-04 Valid for 

SIL 2

  PFDavg = 8.99 E-04 Valid for 

SIL 2

 

PFDavg vs T[Proof] table 

(assuming Proof Test coverage of 99%), with determination of SIL supposing module contributes >10% of total SIF dangerous failures:  

Summary of Contents for D5036D

Page 1: ...SIL 2 Switch Proximity Detector Repeater Relay Output G M International ISM0269 3 SIL 2 Switch Proximity Detector Repeater Relay Output DIN Rail Models D5036S D5036D D5036S D5036D INSTRUCTION SAFETY M...

Page 2: ...SPDT D5036S relay contact Contact material Ag Alloy Cd free gold plated Contact rating 4 A 250 Vac 1000 VA 4 A 250 Vdc 120 W resistive load Min switching current 1 mA DC Load breaking capacity Mechan...

Page 3: ...P Switch ATEX IECEx UL C UL EAC EX UKR TR n 898 T V Certifications T V Functional Safety Certification High Density two channels per unit Simplified installation using standard DIN Rail and plug in te...

Page 4: ...the effective group See parameters indicated in the table below D5036 Terminals Ch1 Ch2 7 8 9 10 Ch1 Ch2 7 8 9 10 Io Isc 22 mA Ch1 Ch2 7 8 9 10 Po Po 56 mW Ii Imax Pi Pi D5036 Terminals D5036 Associat...

Page 5: ...MODEL D5036D 5 6 1 2 Out 1 SIL 2 10 In 1 Proximity voltage free Contact 7 8 Power and Fault Bus F Supply 24 Vdc 3 4 Out 2 SIL 2 In 2 Proximity voltage free Contact 9 voltage free Contact voltage free...

Page 6: ...OFF OFF ON ON Description For this application enable input line fault open or short detection and direct input to output transfer function by set the internal dip switches in the following mode see...

Page 7: ...ation D5036S Ch 1 OFF operation ON operation Field Input proximity is OFF or switch is open Out relay is de energized out contact is open Channel 1 D5036S Ch 1 Field Input proximity is ON or switch is...

Page 8: ...2 at terminals 3 and 4 For Model D5036S in case of Proximity or Voltage free Contact connect the wires at terminal 7 for positive and 8 for negative For Model D5036D in addition to channel 1 connecti...

Page 9: ...e resistors de energizes relay in fault condition 7 2 OFF NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 1 OFF 1 ON NE 1 2 1 ND 2 Output 1 ND 2 Output NE 1 2 Position in fault condition 1 2 Input Input Output Input...

Page 10: ...annel 1 2 SW4 ON OFF D5036D Configuration Summary Table D5036S A configuration DIP switch is located on component side of pcb This switch allows the configuration of input output relationship fault de...

Reviews: