D5036 

- SIL 2 Switch/Proximity Detector Repeater, Relay Output 

G.M. International ISM0269-3 

ON 

Line fault detection 

SW1 

Disabled 

(switch/proximity sensor)  

OFF 

Enabled, for SIL application 

(proximity sensor or switch with end of line resistors, 

detects field open circuit and short circuit, 

de-energizes relay in fault condition) 

ON 

IN/OUT Operation 

SW2 

NO-NE or NC-ND 

ON 

NO-ND or NC-NE 

(for SIL application) 

OFF 

D5036S Configuration Summary Table

 

Channel 

1  

Line fault detection 

SW1 

SW3 

Disabled 

(switch/proximity sensor) 

OFF OFF 

Enabled, for SIL application 

(proximity sensor or switch with end of line resistors, 

detects field open circuit and short circuit, 

de-energizes relay in fault condition) 

ON ON 

IN/OUT Operation 

SW2 

NO-NE or NC-ND 

ON 

NO-ND or NC-NE  

(for SIL application) 

OFF 

Channel 

SW4 

ON 

OFF 

D5036D Configuration Summary Table

 

D5036S 

A configuration DIP switch is located on component side of pcb. This switch allows the configuration of input/output relationship, fault detection functions and operating mode. 

 

 

 

Configuration 

Dip switch configuration 

CH1 

Setting 

Line fault 
detection 

IN / OUT 

Operation 

NO-NE or 

NC-ND 

NO-ND or 

NC-NE 

2

ON 

2

OFF 

Disabled 

(switch / proximity sensor) 

Enabled 

(proximity sensor or switch 

with end of line resistors, 

de-energizes relay in fault condition) 

1

 

OFF 

1

ON  

Input Input 

Input 

Input 

 

NO 

OR 

NC 

 

NO 

OR 

NC 

Output 

1-3 


NE 

Output 

1-3 


NE 

Output 

1-3 


ND 

Output 


ND 

1-3 

Position in fault condition 

1-3 


SW1  SW2  SW3  SW4 

OFF OFF OFF OFF 

DIP Switch factory settings (valid for D5036S and D5036D)

 

Configuration 

1

2

3

4

ON

Dip switch factory settings. All Switches are OFF 

1

2

3

4

ON

CH1

 

3-4 not used

 

Note: SW3 and SW4 not used.

 

 

Note: SW3 and SW4 used only in D5036D.

 

For SIL Application 

For SIL Application 

Summary of Contents for D5036D

Page 1: ...SIL 2 Switch Proximity Detector Repeater Relay Output G M International ISM0269 3 SIL 2 Switch Proximity Detector Repeater Relay Output DIN Rail Models D5036S D5036D D5036S D5036D INSTRUCTION SAFETY M...

Page 2: ...SPDT D5036S relay contact Contact material Ag Alloy Cd free gold plated Contact rating 4 A 250 Vac 1000 VA 4 A 250 Vdc 120 W resistive load Min switching current 1 mA DC Load breaking capacity Mechan...

Page 3: ...P Switch ATEX IECEx UL C UL EAC EX UKR TR n 898 T V Certifications T V Functional Safety Certification High Density two channels per unit Simplified installation using standard DIN Rail and plug in te...

Page 4: ...the effective group See parameters indicated in the table below D5036 Terminals Ch1 Ch2 7 8 9 10 Ch1 Ch2 7 8 9 10 Io Isc 22 mA Ch1 Ch2 7 8 9 10 Po Po 56 mW Ii Imax Pi Pi D5036 Terminals D5036 Associat...

Page 5: ...MODEL D5036D 5 6 1 2 Out 1 SIL 2 10 In 1 Proximity voltage free Contact 7 8 Power and Fault Bus F Supply 24 Vdc 3 4 Out 2 SIL 2 In 2 Proximity voltage free Contact 9 voltage free Contact voltage free...

Page 6: ...OFF OFF ON ON Description For this application enable input line fault open or short detection and direct input to output transfer function by set the internal dip switches in the following mode see...

Page 7: ...ation D5036S Ch 1 OFF operation ON operation Field Input proximity is OFF or switch is open Out relay is de energized out contact is open Channel 1 D5036S Ch 1 Field Input proximity is ON or switch is...

Page 8: ...2 at terminals 3 and 4 For Model D5036S in case of Proximity or Voltage free Contact connect the wires at terminal 7 for positive and 8 for negative For Model D5036D in addition to channel 1 connecti...

Page 9: ...e resistors de energizes relay in fault condition 7 2 OFF NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 1 OFF 1 ON NE 1 2 1 ND 2 Output 1 ND 2 Output NE 1 2 Position in fault condition 1 2 Input Input Output Input...

Page 10: ...annel 1 2 SW4 ON OFF D5036D Configuration Summary Table D5036S A configuration DIP switch is located on component side of pcb This switch allows the configuration of input output relationship fault de...

Reviews: