D5036 

- SIL 2 Switch/Proximity Detector Repeater, Relay Output 

G.M. International ISM0269-3 

Parameters Table 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Device Parameters 

D5036 Associated 

Apparatus Parameters 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Cable Parameters 

Uo / Voc = 10.5 V 

Ui / Vmax 

In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check 
its suitability for the Hazardous Area/Hazardous Locations and group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded 
by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5036 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, 
check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the 
effective group. See parameters indicated in the table below: 

D5036 Terminals 

Ch1 
Ch2 

7 - 8 

9 - 10 

Ch1 
Ch2 

7 - 8 

9 - 10 

Io / Isc = 22 mA 

Ch1 
Ch2 

7 - 8 

9 - 10 

Po / Po = 56 mW 

 

Ii/ Imax 

 

Pi / Pi 

 

D5036 Terminals 

D5036 Associated Apparatus 

Parameters Cenelec (US) 

Ci / Ci  C cable 

 

IIC (A, B) 

Co / Ca = 2.41 µF 
Co / Ca = 16.8 µF 

Co / Ca = 75 µF 

IIB (C) 
IIA (D) 

For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable), 
then 50 % of Co and Lo parameters are applicable and shall not be exceeded 

(50 % of the Co and Lo become the limits which must include the cable such that 

Ci C cable 

 50 % of Co and Li  L cable 

 50 % of Lo). 

If the cable parameters are unknown, the following value may be used: Capacitance 180pF per meter (60pF per foot), Inductance 0.60µH per meter (0.20µH per foot). 

 

Co / Ca = 66 µF 

Co / Ca = 16.8 µF 

IIIC (E, F, G) 

Ch1 

Ch2 

7 - 8 

9 - 10 

Li / Li L cable 

 

IIC (A, B) 

Lo / La = 78.3 mH 

Lo / La = 313.4 mH 
Lo / La = 626.9 mH 

IIB (C) 
IIA (D) 

Lo / La = 1028.6 mH 

Lo / La = 313.4 mH 

IIIC (E, F, G) 

Ch1 

Ch2 

7 - 8 

9 - 10 

Li / Ri device and 

L cable / R cable 

 

IIC (A, B) 

Lo / Ro = 635 µH/

 

Lo / Ro = 2543 µH/

 

Lo / Ro = 5087 µH/

 

IIB (C) 
IIA (D) 

Lo / Ro = 8347 µH/

 

Lo / Ro = 2543 µH/

 

IIIC (E, F, G) 

Ch1 

Ch2 

7 - 8 

9 - 10 

Summary of Contents for D5036D

Page 1: ...SIL 2 Switch Proximity Detector Repeater Relay Output G M International ISM0269 3 SIL 2 Switch Proximity Detector Repeater Relay Output DIN Rail Models D5036S D5036D D5036S D5036D INSTRUCTION SAFETY M...

Page 2: ...SPDT D5036S relay contact Contact material Ag Alloy Cd free gold plated Contact rating 4 A 250 Vac 1000 VA 4 A 250 Vdc 120 W resistive load Min switching current 1 mA DC Load breaking capacity Mechan...

Page 3: ...P Switch ATEX IECEx UL C UL EAC EX UKR TR n 898 T V Certifications T V Functional Safety Certification High Density two channels per unit Simplified installation using standard DIN Rail and plug in te...

Page 4: ...the effective group See parameters indicated in the table below D5036 Terminals Ch1 Ch2 7 8 9 10 Ch1 Ch2 7 8 9 10 Io Isc 22 mA Ch1 Ch2 7 8 9 10 Po Po 56 mW Ii Imax Pi Pi D5036 Terminals D5036 Associat...

Page 5: ...MODEL D5036D 5 6 1 2 Out 1 SIL 2 10 In 1 Proximity voltage free Contact 7 8 Power and Fault Bus F Supply 24 Vdc 3 4 Out 2 SIL 2 In 2 Proximity voltage free Contact 9 voltage free Contact voltage free...

Page 6: ...OFF OFF ON ON Description For this application enable input line fault open or short detection and direct input to output transfer function by set the internal dip switches in the following mode see...

Page 7: ...ation D5036S Ch 1 OFF operation ON operation Field Input proximity is OFF or switch is open Out relay is de energized out contact is open Channel 1 D5036S Ch 1 Field Input proximity is ON or switch is...

Page 8: ...2 at terminals 3 and 4 For Model D5036S in case of Proximity or Voltage free Contact connect the wires at terminal 7 for positive and 8 for negative For Model D5036D in addition to channel 1 connecti...

Page 9: ...e resistors de energizes relay in fault condition 7 2 OFF NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 1 OFF 1 ON NE 1 2 1 ND 2 Output 1 ND 2 Output NE 1 2 Position in fault condition 1 2 Input Input Output Input...

Page 10: ...annel 1 2 SW4 ON OFF D5036D Configuration Summary Table D5036S A configuration DIP switch is located on component side of pcb This switch allows the configuration of input output relationship fault de...

Reviews: