D5031 

- SIL 3 Switch/Proximity Detector Repeater Open Collector Output 

 

G.M. International ISM0107-11 

SIL 3 Switch/Proximity Detector Repeater 

Transistor Open Collector Output, DIN-Rail and 

Termination Board, Models D5031S, D5031D 

 

D5031S - D5031D 

INSTRUCTION MANUAL 

Summary of Contents for D5031D

Page 1: ...Detector Repeater Open Collector Output G M International ISM0107 11 SIL 3 Switch Proximity Detector Repeater Transistor Open Collector Output DIN Rail and Termination Board Models D5031S D5031D D503...

Page 2: ...K typical 8 V no load 8 mA short circuit Output voltage free SPST optocoupled open collector transistor Open collector rating 100 mA at 35 Vdc 1 5 V voltage drop Leakage current 50 A at 35 Vdc Respons...

Page 3: ...safety system In field programmability by DIP Switch ATEX IECEx UL C UL FM FMC INMETRO CCC EAC EX UKR TR n 898 T V Certifications T V Functional Safety Certification Type Approval Certificate DNV and...

Page 4: ...Terminals Ch1 Ch2 7 8 9 10 Ch1 Ch2 7 8 9 10 Io Isc 22 mA Ch1 Ch2 7 8 9 10 Po Po 56 mW Ii Imax Pi Pi D5031 Terminals D5031 Associated Apparatus Parameters Cenelec US Ci Ci device C cable Co Ca 2 4 F C...

Page 5: ...tact In 2 Proximity voltage free Contact voltage free Contact voltage free Contact R1 R2 R1 R2 Resistors R1 R2 used with voltage free contact required for line fault detection MODEL D5031D Duplicator...

Page 6: ...idual conductor per each clamping point use conductors up to 2 5 mm 13 AWG and a torque value of 0 5 0 6 Nm The wiring cables have to be proportionate in base to the current and the length of the cabl...

Page 7: ...ity sensor Enabled proximity sensor or switch with end of line resistors de energizes transistor in fault condition 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 1 OFF 5 OFF 1 ON 5 ON NC 1 2 1 NO 2 Output 1 NO 2...

Page 8: ...C Mode ON OFF OFF ON Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes transistor in fault condition No Fault No Fault 1 OFF 5 OFF 5 ON Output...

Page 9: ...n 1 2 3 4 7 8 must be set to OFF position 3 4 6 Not used 5 6 7 8 ON CH Setting Line fault detection IN OUT Operation NO NC or NC NO NO NO or NC NC Disabled switch proximity sensor Enabled proximity se...

Page 10: ...n fault condition for SIL application if line fault detection enabled SW1 ON ON OFF ON Parallel for SIL applica tion Set equal to SW2 Not specified Fault condition OFF Reverse Set opposite to SW2 OFF...