D1054 

- SIL 2 Repeater Power Supply and Trip Amplifiers 

G.M. International ISM0067-18 

PPC1090 Operation 

The Pocket Portable Configurator type PPC1090 is suitable to configure the “smart” barrier of D1000 series. The PPC1090 unit is not ATEX, UL or FM approved and is only to be used in 
Safe Area/Non Hazardous Locations and prior to installation of the isolator and prior to connection of any I.S. wiring. Do not use PPC1090 configurator in Hazardous Area/Hazardous 
Locations. The PPC1090 configurator is powered by the unit (no battery power) when the telephone jack is plugged into the barrier (RJ12 6 poles connecto type with 1:1 connection). 
It has a 5 digit display, 4 leds and four push buttons with a menu driven configuration software and can be used in Safe Area/Non Hazardous Locations without any certification because 
it plugs into the non intrinsically safe portion of circuit. 

 

PPC1090 Configuration 

The configuration procedure follows a unit specific menu. The display shows the actual menu item, the led shows the channel configured and the push button actuates as “Enter”, 
“Select”, “Down” and “Up” key. The “Enter” key is pressed to confirm the menu item, the “Select” key is pressed to scroll the menu item, the “Down” and “Up” keys are pressed to 
decrement or increment the numeric value of menu item. The “Up” key is also pressed to decrement the menu level. When the PPC1090 is plugged into the unit, the display shows the 
barrier model (first level menu). Then press the “Enter” key to the second level menu and the “Select” key to scroll the menu voice. When the selected menu item is displayed press the 
“Enter” key to confirm the choice. Follow this procedure for every voice of the menu. When a numeric menu item is to be changed, press the “Select” key to highlight the character and 
then the “Up” and “Down” keys to select the number; confirm the modification with the “Enter” key. To return to a higher level menu press the “Up” key. 

 

D1054S Menu 

1) 

D1054S

 

 

[1 Level Menu] 

Displays Model D1054S single channel smart repeater power supply plus trip amplifier. Press “Enter” key to second level menu. 

2) 

CF

 

 

 

[2 Level Menu] 

Displays the parameters configuration menu. Press “Enter” key to configure the functional parameters, press the “Select” key to the next 
menu level item or “Up” key to return to first level. 

3) 

In

 

 

 

[2 Level Menu] 

Displays the input variable monitoring. Press “Enter” to display the current input value reading, press the “Select” key to the next menu 
level item or “Up” key to return to first level. 

4) 

Out

 

 

 

[2 Level Menu] 

Displays the analog output variable monitoring. Press “Enter” to display the current output value reading, press the “Select” key to the 
next menu level item or “Up” key to return to first level. 

5) 

Set A

   

 

[3 Level Menu] 

Displays the SET A Trip Point Value configuration. Press “Enter” to set the trip point value, press the “Select” key to the next menu level 
item or “Up” key to return to second level. If you pressed “Enter” key, you can set the set value; press the “Select” key to highlight the 
character you want to change and then the “Up” and “Down” keys to select the number; confirm the modification with the “Enter” key 

6) 

Set B

   

 

[3 Level Menu] 

Displays the SET B Trip Point Value configuration. Press “Enter” to set the trip point value, press the “Select” key to the next menu level 
item or “Up” key to return to second level. If you pressed “Enter” key, you can set the set value; press the “Select” key to highlight the 
character you want to change and then the “Up” and “Down” keys to select the number; confirm the modification with the “Enter” key 

7) 

Br LO

   

 

[3 Level Menu] 

Displays the Burnout LOW Trip Point Value configuration. Press “Enter” to set the burnout condition trip point value (below this value 
indicate a burnout fault condition, set –5.000 to disable), press the “Select” key to the next menu level item or “Up” key to return to 
second level. If you pressed “Enter” key, you can set the value; press the “Select” key to highlight the character you want to change and 
then the “Up” and “Down” keys to select the number; confirm the modification with the “Enter” key 

8) 

Br HI

   

 

[3 Level Menu] 

Displays the Burnout HIGH Trip Point Value configuration. Press “Enter” to set the burnout condition trip point value (above this value 
indicate a burnout fault condition, set 25.000 to disable), press the “Select” key to the next menu level item or “Up” key to return to 
second level. If you pressed “Enter” key, you can set the value; press the “Select” key to highlight the character you want to change and 
then the “Up” and “Down” keys to select the number; confirm the modification with the “Enter” key 

9) 

Out

 

 

 

[3 Level Menu] 

Displays the analog output type configuration. Press “Enter” to set the analog output type and range, press the “Select” key to the next 
menu level item or “Up” key to return to second level. If you pressed “Enter” key, you can choose between 6 different output types; 
press “Select” key to change the output type and range and then the “Enter” key to confirm the choice. The output types are: 
4-20  4 to 20 mA current output (for SIL applications) 

 

0-20 

0 to 20 mA current output 

1-5 

1 to 5 V voltage output   

 

 

 

0-5 

0 to 5 V voltage output 

2-10  2 to 10 V voltage output    

 

 

 

0-10 

0 to 10 V voltage output

 

10) 

Dn Sc

   

 

[3 Level Menu] 

Displays the input low scale configuration. Press “Enter” to set the low scale input value, press the “Select” key to the next menu level 
item or “Up” key to return to second level. If you pressed “Enter” key, you can set the low input value; press the “Select” key to highlight 
the character you want to change and then the “Up” and “Down” keys to select the number; confirm the modification with the “Enter” key 

11) 

Up Sc

   

 

[3 Level Menu] 

Displays the input high scale configuration. Press “Enter” to set the high scale input value, press the “Select” key to the next menu level 
item or “Up” key to return to second level. If you pressed “Enter” key, you can set the high input value; press the “Select” key to highlight 
the character you want to change and then the “Up” and “Down” keys to select the number; confirm the modification with the “Enter” key 

12) 

Burn

   

 

[3 Level Menu] 

Displays the burnout configuration. Press “Enter” to set the burnout condition, press the “Select” key to the next menu level item or 
“Up” key to return to second level. If you pressed “Enter” key, you can choose between 3 different burnout conditions; 
press “Select” key to change the burnout and then the “Enter” key to confirm the choice. The condition types are:

 

none   

no burnout detection, the analog output follow the input value 

br dn   

when in burnout condition, the analog output goes to down scale (0 mA or 0 V) 

br up   

when in burnout condition, the analog output goes to high scale (22 mA or 11 V)

 

Menu item description 

13) 

Alr A / Alr B

 

 

[3 Level Menu] 

Displays the Alarm A / Alarm B configuration menu. Press “Enter” to set the alarm condition, press the “Select” key to the next menu level item or “Up” key to return to second level. 

14) 

Type

   

 

[4 Level Menu] 

Displays the alarm type (A or B) configuration. Press “Enter” to set the alarm condition, press the “Select” key to the next menu level item or “Up” key to return to third level. 
If you pressed “Enter” key, you can choose between 5 different alarm conditions; press “Select” key to change the type and then the “Enter” key to confirm the choice. 
The condition types are: 
OFF   

no alarm detection, the relay output is always in normal condition 

HI 

 

high alarm condition, the relay output change status when an alarm condition is detected (input variable goes above the set value) 

LO 

 

low alarm condition, the relay output change status when an alarm condition is detected (input variable goes below the set value) 

LOSEC  

low with start-up alarm condition, the relay output change status when an alarm condition after the start-up is detected (input variable starts below the set 

 

 

value but no alarm condition is signaled, after the warm-up the variable goes above the set value arming the alarm detection, then when the variable goes 

 

 

below the set value the alarm condition is signaled) 

BURN   

burnout alarm condition, the alarm condition change status when a burnout condition appear in the input variable (input variable goes below the “Br LO” set 

 

 

value or goes above the “Br HI” set value). 

 

Summary of Contents for D1054S

Page 1: ...D1054 SIL 2 Repeater Power Supply and Trip Amplifiers ISM0067 18 D1054S INSTRUCTION SAFETY MANUAL SIL 2 Repeater Power Supply and Trip Amplifiers Din Rail Model D1054S...

Page 2: ...ectional within 3 dB Hart and higher frequency protocols only with mA direct current output Alarm Trip point range within rated limits of input sensor see input for step resolution ON OFF delay time 0...

Page 3: ...10 V Output Signal linear or reverse Wide Band Smart Communication Hart compatible Input and Output short circuit proof Two independent trip amplifiers Output for burnout detection Common burnout dete...

Page 4: ...te powered intrinsically safe devices check that maximum allowable voltage current Ui Vmax Ii Imax of the D1054 Associated Apparatus are not exceeded by the safety parameters Uo Voc Io Isc of the Intr...

Page 5: ...r Entity Concept or third party approved for Division 2 installations the configuration of Intrinsically Safe Equipment must be FM approved under non incendive field wiring or Entity Concept or third...

Page 6: ...red to detect High failure this failure has been classified as a dangerous detected DD failure Fail Low failure mode that causes the output signal to go below the minimum output current 4 mA Assuming...

Page 7: ...mA of full span Fail High failure mode that causes the output signal to go above the maximum output current 20 mA Assuming that the application program in the Safety logic solver is configured to dete...

Page 8: ...of the circuit diagram and is listed for completeness When calculating the SFF this failure mode is not taken into account Both alarm A and B trip amplifiers must be programmed with equal configuratio...

Page 9: ...to not respond to a demand from the process i e being unable to go to the defined Fail Safe state so that the output relays remain energized or relay contacts remain closed Fail Dangerous Detected a d...

Page 10: ...l The proof test shall be performed to reveal dangerous faults which are undetected by diagnostic This means that it is necessary to specify how dangerous undetected fault which have been noted during...