background image

 

10 

D1054 

- SIL 2 Repeater Power Supply and Trip Amplifiers 

G.M. International ISM0067-18 

Installation 

 

D1054 is a repeater power supply with trip amplifiers housed in a plastic enclosure suitable for installation on T35 DIN Rail according to EN50022. 
D1054 unit can be mounted with any orientation over the entire ambient temperature range, see section “Installation in Cabinet” and "Installation of Electronic Equipments in Cabinet" 
Instruction Manual D1000 series for detailed instructions. 
Electrical connection of conductors up to 2.5 mm2 are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without 
suffering or causing any damage 

(for Zone 2 or Division 2 installations check the area to be nonhazardous before servicing)

The wiring cables have to be proportionate in base to the current and the length of the cable. 
On the section “Function Diagram” and enclosure side a block diagram identifies all connections. 
Identify the function and location of each connection terminal using the wiring diagram on the corresponding section, as an example: 
Connect 12-24 Vdc power supply positive at terminal “3” and negative at terminal “4”. 
Connect positive output of analog channel at terminal “1” and negative output at “2”. 
Connect trip amplifier output of alarm A at terminal “5” and “6” and trip amplifier output of alarm B at terminal “7” and “8”. 
In case of a 2 wire input transmitter, connect the wires at terminal “14” for positive and “15” for negative. 
For separately powered transmitters, connect input signal at terminal “15” for positive and “16” for negative. 

 

Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards 
(e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165, 
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505, 
Canadian Electrical Code CEC), make sure that conductors are well isolated from each other and do not produce any unintentional connection. 
Connect SPST alarm contacts checking the load rating to be within the contact maximum rating (2 A, 250 V, 500 VA 80 W resistive load). 
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation 
requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. 
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. 
If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water. 

Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D1054 must be cleaned only with a damp or antistatic cloth. 

Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. 
According to EN61010, D1054 series must be connected to SELV or SELV-E supplies. 
Relay output contact must be connected to loads non exceeding category I, pollution degree I overvoltage limits. 

Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock 
when connected to live hazardous potential

 

The proof test shall be performed to reveal dangerous faults which are undetected by diagnostic. This means that it is necessary to specify how dangerous undetected fault, 
which have been noted during the FMEDA, can be detected during the proof test. 

Testing procedure at T-proof 

 

Steps

 

Action

 

Bypass the Safety PLC or take other appropriate action to avoid a false trip. 

Connect a mA signal generator to the input terminals (‘14’-‘15’ as passive input transmitter or ‘15’-‘16’ as active input transmitter) of the repeater. 

Force an input current signal value to go module current output to full scale value (

 20 mA) and verify that the analog current reaches that value. 

This tests is for voltage compliance problems, such as low supply voltage or increased wiring resistance, and for other possible failures. 

Force an input current signal value to go module current output to low scale value (

 4 mA) and verify that the analog current reaches that value. 

This tests is for possible quiescent current related failures. 

Restore the loop to full operation. 

Proof test 1A 

(to detect approximately 50 % of possible Dangerous Undetected failures) 

Remove the bypass from the Safety PLC or restore normal operation. 

Steps

 

Action

 

Bypass the Safety PLC or take other appropriate action to avoid a false trip. 

Perform steps 2, 3 and 4 of 

Proof Test 1A

Force some input current signal values, included in the range 4-20 mA, verifying that the module output current related values are within the specified accuracy (3 % (± 0.5 mA) 
of full span) as defined in the Safety Function. This test requires that mA signal generator has already been tested without the repeater and that it works correctly according to 
its specifications. 

Restore the loop to full operation. 

Remove the bypass from the Safety PLC or restore normal operation. 

Proof test 2A

 (to detect approximately 99 % of possible Dangerous Undetected failures) 

Steps

 

Action 

Bypass the Safety PLC or take other appropriate action to avoid a false trip. 

Connect a mA signal generator to the input terminals (‘14’-‘15’ as passive input transmitter or ‘15’-‘16’ as active input transmitter) of the repeater. 

For each trip amplifier, force an input current signal value to go module to the high alarm current output and verify that the related relay contact (on terminal blocks 5-6 for 
trip amplifier 1 or terminal blocks 7-8 for trip amplifier 2) is switched respect to previous normal condition. 

For each trip amplifier, force an input current signal value to go module to the low alarm current output and verify that the related relay contact (on terminal blocks 5-6 for 
trip amplifier 1 or terminal blocks 7-8 for trip amplifier 2) is switched respect to previous normal condition. 

Restore the loop to full operation. 

Proof test 1B 

(to detect approximately 50 % of possible Dangerous Undetected failures)

 

Remove the bypass from the Safety PLC or restore normal operation. 

Test for D1054S (for each alarm trip amplifier with relay output): 

Steps  Action

 

Bypass the Safety PLC or take other appropriate action to avoid a false trip. 

Perform steps 2, 3 and 4 of 

Proof Test 1B

Force some input current signal values, included in the range 4-20 mA, and for each trip amplifier set an alarm current value in the range 4-20 mA. Verify that the related 
relay contact (on terminal blocks 5-6 for trip amplifier 1 or terminal blocks 7-8 for trip amplifier 2) is switched when input signal increases / decreases (according to high / low 
alarm setting) above / below the alarm current value, considering a maximum error of 3% between input signal value and set alarm current value. 

Restore the loop to full operation. 

Remove the bypass from the Safety PLC or restore normal operation. 

Proof test 2B 

(to detect approximately 99 % of possible Dangerous Undetected failures) 

 

Test for D1054S (analog current output): 

 

Summary of Contents for D1054S

Page 1: ...D1054 SIL 2 Repeater Power Supply and Trip Amplifiers ISM0067 18 D1054S INSTRUCTION SAFETY MANUAL SIL 2 Repeater Power Supply and Trip Amplifiers Din Rail Model D1054S...

Page 2: ...ectional within 3 dB Hart and higher frequency protocols only with mA direct current output Alarm Trip point range within rated limits of input sensor see input for step resolution ON OFF delay time 0...

Page 3: ...10 V Output Signal linear or reverse Wide Band Smart Communication Hart compatible Input and Output short circuit proof Two independent trip amplifiers Output for burnout detection Common burnout dete...

Page 4: ...te powered intrinsically safe devices check that maximum allowable voltage current Ui Vmax Ii Imax of the D1054 Associated Apparatus are not exceeded by the safety parameters Uo Voc Io Isc of the Intr...

Page 5: ...r Entity Concept or third party approved for Division 2 installations the configuration of Intrinsically Safe Equipment must be FM approved under non incendive field wiring or Entity Concept or third...

Page 6: ...red to detect High failure this failure has been classified as a dangerous detected DD failure Fail Low failure mode that causes the output signal to go below the minimum output current 4 mA Assuming...

Page 7: ...mA of full span Fail High failure mode that causes the output signal to go above the maximum output current 20 mA Assuming that the application program in the Safety logic solver is configured to dete...

Page 8: ...of the circuit diagram and is listed for completeness When calculating the SFF this failure mode is not taken into account Both alarm A and B trip amplifiers must be programmed with equal configuratio...

Page 9: ...to not respond to a demand from the process i e being unable to go to the defined Fail Safe state so that the output relays remain energized or relay contacts remain closed Fail Dangerous Detected a d...

Page 10: ...l The proof test shall be performed to reveal dangerous faults which are undetected by diagnostic This means that it is necessary to specify how dangerous undetected fault which have been noted during...

Page 11: ...in Hazardous Area Hazardous Locations or unless area is known to be onhazardous Warning substitution of components may impair Intrinsic Safety and suitability for Division 2 Zone 2 Warning de energiz...

Page 12: ...and Down keys to select the number confirm the modification with the Enter key 8 Br HI 3 Level Menu Displays the Burnout HIGH Trip Point Value configuration Press Enter to set the burnout condition tr...

Page 13: ...ring range corresponding to defined low output value Upscale input value of measuring range corresponding to defined high output value Burnout Low low burnout condition trip point value below this val...

Reviews: