Global Mainstream Dynamic Energy Technology Ltd.
- 35 -
User Manual
Powervortex 5200TL hybrid inverter
4.1.5.14 Setting Battery State of Charge (SoC)
Figure 37 SoC setting
SOC refers to the left battery capacity ratio. For example, if set SOC as 15% ,the system will stop
discharging the battery when the battery capacity is reduced to 15%;
The SOC default value is 15%, please press “OK” to modify it.
4.1.5.15 Setting Feed-in Grid Percentage
Figure 38 Feed-in grid percentage setting
FED refers to feed-in grid percetage. The system is not allowed to feed any energy into the grid if
the FED value is set to 0%. The system is free to export to the grid if the FED setting to 0100%.If the
FED is set to 10%, then the largest power allowed to be fed into the grid is 5000W*10%=500W.